The EVX100 and MFT-X1 form a comprehensive testing kit for automated diagnostics of single- and three-phase Mode 3 AC electric vehicle charging stations (EVSE). Eliminating the need for manual adaptors or control boxes, the MFT-X1 instantly recognises the EVX100 and provides all necessary testing functions without manual intervention.
The Megger MFT-X1 Multifunction Tester is designed for CAT IV 300V applications, marking Megger’s initial foray into platform-based multifunction testers. It is ideal for testing single-phase and three-phase electrical installations in domestic, commercial, and industrial environments. The tester offers a wide range of tests, enabling in-depth fault diagnostics and fulfilling all commissioning, maintenance, routine checks, and certification needs.
For more information please visit the Megger MFT-X1 Multifunction Tester.
The EVX100 is a fully integrated add-on for the MFT-X1, offering an automated testing interface for single- and three-phase Mode 3 AC electric vehicle charging stations (EVSE). This setup removes the necessity for a conventional remote manual adaptor or control box. Upon connection, the MFT-X1 instantly detects the EVX100 and presents the necessary testing functions without requiring manual input.
For more information please visit the Megger EVX100 Electric Vehicle Charge-Point Adaptor.
Voltage Measurement | |
---|---|
Voltage range | 0.001 V to 2 V (mV range) 2 V to 600 V (V range), 1000 V DC (on-CAT rated circuits) |
Voltage type | Trms, AC, DC |
Phase sequence | Automatic phase sequence testing on detection of valid three-phase supplies |
Current Measurement (non-contact) | |
AC Trms | Using optional accessories: MCC1010 current clamp |
Measurement Range | MCC1010: 1 mA to 300 A |
Continuity/Resistance | |
Measurement range Digital display | 0.01 Ω to 999 kΩ Auto-ranging |
Measurement Range Analogue arc | 0 Ω to 1 MΩ log scale |
Test voltage | 4 V DC to 5 V DC |
Test current (Nominal) | >200 mA 0 Ω >< 2 Ω 10 mA Auto reduction on high resistance (actual current reported in the display) |
Test polarities | Forward polarity |
Buzzer resistance range | > 0.01 Ω < 2 kΩ |
Buzzer threshold | 0.3, 0.5, 1, 2, 3, 4, 5, 10, 20, 30, 40, 50, 100, 200 Ω |
Insulation Testing | |
Measurement range Digital display | 0.001 MΩ to 999 MΩ Auto-ranging |
Measurement range Analogue arc | 0.001 MΩ to >1000 MΩ log scale |
Insulation test voltages | 50 V DC to 1000 V DC + Variable 50 V to 999 V |
Test current | 1 mA to 2 mA |
Stabilised output voltage | Output test voltage stabilised to -0% +2% +2 V |
Loop Impedance Testing | |
2-Wire – all modes | |
Test types | Mode 1: Non-Trip |
Mode 2: High current | |
Mode 3: High resolution | |
Resolution | Non-Trip: 0.01 Ω |
High current: 0.01 Ω | |
High resolution: 0.001 Ω | |
Voltage range | Non-trip: 48 V AC to 280 V AC |
High current: 48 V AC to 550V AC | |
High resolution: 48 V AC to 550 V AC | |
Frequency range | 45 Hz to 65 Hz (all modes) |
Phases | Non-trip: Single phase |
High current: Three-phase | |
High resolution: Three-phase | |
3-Wire - Non-trip | |
Test types | RCD (non-trip) RCD EV (non-trip on 6mA EV RDCs) |
Resolution | 0.01 Ω |
Voltage range | 48 V AC to 280 V |
Frequency range | 45 Hz to 65 Hz |
Phases | Single phase |
Volt Drop | |
Volt drop calculation | Requires Zref (Ze) and circuit current (I-vdrop) |
Accuracy | Dependent on loop impedance accuracy |
RCD Testing | |
RCD types supported | Type AC, A, B, AC(S), A(S), B(S) |
Auto RCD sequence | 1/2x I∆n, 1x I∆n, 2x I∆n, 5x I∆n, Ramp, 0º/180º (customer configurable) |
Ramp testing | 10 mA to 1000 mA |
RDC testing | 6 mA RDC |
Fault (Touch) voltage | 0 V to 253 V |
Earth Testing | |
2-wire | 2-wire earth resistance test |
Power Supply | Internal battery: Li-ion 3180 mAh |
---|---|
Recharging | Type C USB (required supply is 5 V, 1 A maximum) |
Charging Status | LED |
Input Voltage | 230 V AC nominal max 253 V AC 400 V AC nominal max 440 V AC |
Input Frequency | 50/60 Hz |
CP State Verification | A1, A2, B1, B2, C1, C2, E, F |
Connection Options | Fixed Type 2: IEC 62196-1 |
Safety | IEC61010-1:2010 61010-031:2015, CAT II 250 V |
Temperature Range | Working: -10 °C to +55 °C Storage: -25 °C to +70 °C |
Humidity Range | 90% R.H at +40 °C max |
Ingress Protection | IEC 660529: IP 54 - protected against dust and water splashes; suitable for indoor and outdoor use |
Vibration | MIL-PRF-28800F: Class 2 |
Maximum Operating Altitude | 2000 m |
Pollution Degree | 2 |
Mechanical | EVX Case Dimensions: 133.5 x 115 x 56 mm (5.2 x 4.5 x 2.2 inches) excl. cable |
Unpackaged Weight | 976 g |
Packaged Dimensions | 350 x 280 x 75 mm (13.8 x 11.02 x 2.96 inches) |
Packaged Weight | 1580 g |
Cable Length | 2 m |