Looking for a reliable PAT tester with downloadable memory storage, allowing you to store all your results, then catalogue them on a PC? The Megger PAT410 is an excellent choice. The entry-level model in Megger's series of fully downloadable PAT testers, the PAT410 is designed for PAT testing in any application. The tester can be used in hotels, public houses, schools, colleges, nurseries, shops, offices, theatres, banks, restaurants, cafes, sports and leisure facilities and absolutely anywhere where you'll be testing a large amount of appliances and need to store the appliance ID numbers alongside their testing results.
Megger's Portable Appliance Tester (EET) makes cataloguing PAT testing results as simple as possible. The tester can store up to 10,000 individual testing records and - thanks to a built-in QWERTY keyboard - making amendments to your appliance notes is extremely simple. Done with testing? Insert a USB stick into the tester, download to it, then plug into your PC and view your results in either CSV format (compatible with Microsoft Excel) or buy SIMPLYPATS software (sold separately) for full database asset management, certificate generation and much more.
Designed to help you speed up testing, with the QWERTY keyboard and 5 soft keys for direct access to your frequently used functions. Automatic testing routines also help you to speed up your tests, or you can use the manual mode to configure your test times and select different appliance pass limits as needed.
This PAT tester is suitable for checking a wide variety of appliances, including class I and II, IT equipment and power leads (including extension leads). The PAT Tester will carry out all tests as defined in the IET Code of Practice, including Earth bond/continuity, insulation (at 250 and 500V), substitute/differential/touch current leakage tests, operational checks and also performs specific earth bond, insulation, polarity and portable RCD tests on extension leads.
It also features a full-colour graphical display, built-in lead storage pouch and a fuse check function.
Note: although the PAT410 does not include a 110V socket as the PAT420 and PAT450 do, it can still be used for 110V testing by using an appropriate 110V adapter kit.
Why buy the standard tester when you can get one of these amazing value kits instead?
You'll get everything you get as standard, plus all of the accessories you'll need when PAT testing!
This table outlines exactly what's in each kit.
Item | PAT Essentials Kit (Bundle 1) | PAT Business Kit (Bundle 2) | PAT Premium Kit (Bundle 3) | PAT Elite Printer Kit (Bundle 4) |
---|---|---|---|---|
UNI-T UT07A Socket Tester Need to check if your sockets are working right? Just plug this in to a standard UK plug socket and if there's a problem, the socket tester will let you know about it! |
Yes | Yes | Yes | Yes |
CK Tools AV05050 Screwdriver Set This bundle pack includes a set of 5 fully insulated electrical screwdrivers which are suitable for live electrical work to 1000V |
Yes | Yes | Yes | Yes |
eLearning PAT Testing Course - Includes Exam and Certificate Gain a certificate of competency to carry out PAT testing in just two hours with our online PAT course and exam. Teams may be trained by purchasing the course multiple times; each staff member will be assigned a unique activation code and login. |
Yes | Yes | Yes | Yes |
PASS PAT Testing Handbook A comprehensive, extremely detailed guidebook with useful information, diagrams, pictures and case studies related to PAT testing. |
Yes | Yes | Yes | Yes |
Microwave Leakage Detector It's common practice to check microwave radiation levels while you're PAT testing - use this portable, easy-to-use microwave leakage detector to do so |
Yes | Yes | Yes | Yes |
IEC Adapter Set A special bundle pack with three IEC adapters, allowing you to use your PAT tester with various types of IEC cables and power supplies |
Yes | Yes | Yes | Yes |
110V Adapter Set Use these two 110V connector leads to connect your PAT tester to 110V equipment commonly found on construction sites and similar applications |
Yes | Yes | Yes | Yes |
Passed PAT Testing Labels A PAT essential! We include two 500 label rolls in your purchase, ensuring you have everything you need for labelling appliances after testing |
Yes, 1000x | Yes, 1000x | Yes, 1000x | Yes, 500x |
1000 x Circular Passed PAT Labels Uniquely-designed passed PAT testing labels with circular design - ideal for smaller plugs or appliances where you can't easily fit other labels |
Yes, 500x | Yes, 1000x | Yes, 1000x | Yes, 500x |
500 x PAT Testing Cable Wrap Labels These labels wrap around cables, and are great for labelling appliance power leads where you can't fix a suitable label |
Yes, 500x | Yes, 500x | Yes, 500x | Yes, 500x |
500 x Failed PAT Testing Labels You won't need these very often, but if an appliance ever fails testing you should place one of these labels and take it out of use for repair or replacement |
Yes, 500x | Yes, 500x | Yes, 500x | Yes, 500x |
Visual Inspection Labels You should check your appliances over for obvious signs of damage before testing. Look for frayed wires, loose connection and damaged plugs, then place one of these labels on if the appliance passes |
No | Yes | Yes | Yes |
SIMPLYPATS Software Use SIMPLYPATS software alongside your PAT tester to download your results to PC and keep a database of all of your findings |
No | Yes | Yes | Yes |
Barcode Scanner This Bluetooth/USB barcode scanner is great for speeding up your record-keeping by using your Megger PAT tester and barcode labels |
No | No | Yes | Yes |
Barcode Labels Pair these up with your Bluetooth barcode scanner and quickly recall your previous records, or make new records, using your Apollo series PAT tester |
No | No | Yes, 2000x | Yes, 1000x |
Brother Printer and Printer Cartridge Create customised labels when out testing with this portable printer and cartridge pack! |
No | No | No | Yes |
Enjoy peace of mind with a Free PAT Card included with every purchase. Keep track of essential safety checks effortlessly!
Electrical Supply Range | 230V ±10 @ 50/60Hz |
Continuity Test (200mA) | |
Continuity Test Voltage | 9V AC ± 10% ± 0.1V (supply: 230V 50Hz) |
Continuity Resistance Accuracy | ±5% ± 3 digits (0 to 0.49Ω) ±5% ± 5 digits (0.5 to 0.99Ω) |
Continuity Resistance Resolution | 10mΩ (1 to 19.99Ω) |
Display Range | 0 to 19.99Ω |
Insulation Test (250V and 500V) | |
Insulation Resistance Accuracy (230V) | ±2% ±5 digits (0 to 19.99MΩ) ±5% ± 10 digits (20 to 99.99MΩ) |
Insulation Resistance Resolution | 0.01MΩ |
Display Range | 0 to 99.99MΩ |
Substitute Leakage Test | |
Test Voltage and Frequency | 40V AC ±10% nominal mains frequency |
Leakage Current Accuracy | ±5% ± 5 digits |
Leakage Current Resolution | 0.01mA |
Display Range | 0 to 19.99mA |
Differential Leakage Current | |
Test Voltage | Nominal mains 110/230V AC |
Test Frequency | Nominal mains 50/60Hz |
Differential Leakage Current Accuracy | ±5% ± 0.05mA (1.0mA to 9.99mA) ±5% ± 0.1mA (0.1mA to 0.99mA) |
Resolution | 0.01mA |
Display/Measurement Range | 0.10mA to 19.99mA |
Test Duration | User-selectable from 1 sec 10 sec to infinity |
Touch Current Test | |
Test Voltage and Frequency | Nominal mains supply |
Touch Current Accuracy | ±5% ± 5 digits |
Touch Current Resolution | 0.01mA |
Display | 0 to 10mA |
Operational Test | |
Test Voltage and Frequency | Nominal mains supply |
VA Rating | 230V 3700VA 110V 1800VA |
VA Accuracy | ±5% ± 10 digits (0 to 99VA) ±5% ± 50 digits (100VA to 999VA) ±5% ± 100 digits (1000VA to 3700VA) |
Resolution | 1VA (0 to 3700VA) |
Display Range | 0 to 3990VA |
Extension Lead Test | |
Tests Performed | Bond, insulation and polarity |
Polarity Test Voltage | 12V |
Polarity checks | Lead ok Live neutral S/C Live neutral reversed Live/neutral O/C |
Portable RCD Test | |
Test Voltage and Frequency | Nominal mains supply |
Test Current Accuracy | -8% to -2% (1/2 x I) +2 to +8% (1 x I, 5 x I) |
Trip Time Accuracy | ±1% ± 5 digits |
Trip Time Resolution | 0.1ms |
Display Range | 0 to 1999ms (1/2 x I) 0 to 300ms (1 x I) 0 to 40ms (5 x I) |
Fuse Test | |
Test Voltage | 3.3V |
Warning | Audible beep if fuse is OK |
Environmental | |
Operating Temperature | -10 to 50°C |
Storage Temperature | -20 to 60°C |
Humidity | 90% RH @ -10 to 30°C 75% RH @ +30 to 50°C |
Maximum Altitude | 2000m |
Ingress Protection | IP40 |
Other | |
Weight | 2.7kg |
Dimensions | 145 (H) x 255 (W) x 320mm (L) |
Safety | IEC 61010-1: CAT II 300V |