The Fluke 1663 includes everything a professional electrical installer needs including a huge variety of different measurement functions, built-in memory storage and download and fast, easy-to-configure testing procedures.
The Fluke 1663 firmware has been updated to support 6mA RDC-DD tests in accordance with international standards IEC 60964 and IEC 62752. Together with Fluke’s FEV300 Test Adapter, (sold seperately) this new ability enables comprehensive, accurate, and reliable testing of electric vehicle supply equipment (EVSE). It allows you to conduct all necessary tests in one go and meet the evolving needs of the EVSE market.
On top of this new function, you can also expect all of the typical measurements you'll need such as voltage (AC/DC), frequency, wiring polarity, insulation resistance, loop/line resistance, prospective earth fault current (PEFC/IK), prospective short-circuit current (PSC/IK) and several RCD measurement modes such as RCD tyip time, ramp test (RCD trip current) and more.
Thanks to built-in memory storage, the Fluke 1663 makes it significantly easier to log your testing results (ideal for jobs where you'll be testing a wide variety of different electrical installations). This data can be stored and viewed back on the tester or can be transferred across to PC and interacted with further using either FlukeView or Fluke DMS software packages (sold separately).
There are three models in the 1600 series - the 1662, the 1663 and the 1664 FC. This table outlines the difference between the three units.
Measurement Function | 1662 | 1663 | 1664 FC |
Insulation-PreTest Safety Function | - | - | √ |
Insulation at L-N, L-PE and N-PE inputs | - | - | √ |
Auto Test Sequence | - | - | √ |
Loop and Line Resistance with mΩ Resolution | - | - | √ |
Continuity at L-N, P-PE and N-PE Inputs | - | √ | √ |
Test Smooth, DC-Sensitive RCDs (Type B/B+) | - | √ | √ |
EV Test 6 mA (RCD A/EV, RDC-DD) - NEW FOR 2023 | - | √ | √ |
Earth Resistance | - | √ | √ |
Voltage TRMS (AC/DC) and Frequency | √ | √ | √ |
Wiring Polarity Checker (Detects Broken PE and N Wires) | √ | √ | √ |
Insulation Resistance | √ | √ | √ |
Continuity and Resistance | √ | √ | √ |
Measure Motor Windings with Continuity Test (@10mA) | √ | √ | √ |
Loop/Line Resistance | √ | √ | √ |
Prospective Earth Fault Current (PEFC/IK) | √ | √ | √ |
Prospective Short-Circuit Current (PSC/IK) | √ | √ | √ |
RCD Trip Time | √ | √ | √ |
RCD Trip Current (Ramp Test) | √ | √ | √ |
Measure Trip Time/Current for RCD type A/AC in One Test | √ | √ | √ |
RCD Variable Test Current | √ | √ | √ |
Automatic RCD Test Sequence | √ | √ | √ |
Phase Sequence Test | √ | √ | √ |
Other Features | |||
Fluke Connect Compatibility | - | - | √ |
ShareLive Calling | - | - | √ |
Fluke Cloud Storage | - | - | √ |
On/Off Switchable Auto Start for RCD and Loop Tests | √ | √ | √ |
Self Test | √ | √ | √ |
Illuminated Display | √ | √ | √ |
Memory/Interface | |||
Z Max Memory | - | √ | √ |
Memory | - | √ | √ |
IR-USB and BLE Interface (use with optional Fluke DMS software and FVF) | - | IR-USB | IR-USB/BLE |
AC/DC Voltage (TRMS) | ||||
---|---|---|---|---|
Range | Resolution | Input Impedance | Overload Protection | |
500V | 0.1V | 3.3MΩ | 660V rms | |
Continuity Testing (Rlo) | ||||
Range (Autoranging) | Resolution | Open Circuit Voltage | ||
20Ω | 0.01Ω | >4V | ||
200Ω | 0.1Ω | |||
2000Ω | 1Ω | |||
Insulation Resistance Measurement (Riso) | ||||
Model Number | Test Voltages | |||
1662 | 100, 250, 500 and 1000V | |||
1663/1664 FC | 50, 100, 250, 500 and 1000V | |||
Test Voltage | Insulation Resistance Range | Resolution | Test Current | |
50V | 20MΩ/50MΩ | 0.01MΩ/0.1MΩ | 1mA @ 50kΩ | |
100V |
20MΩ/100MΩ |
0.01MΩ/0.1MΩ | 1mA @ 100kΩ | |
250V | 20MΩ/200MΩ | 0.01MΩ/0.1MΩ | 1mA @ 250kΩ | |
500V | 20MΩ/200MΩ/500MΩ | 0.01MΩ/0.1MΩ/1MΩ | 1mA @ 500kΩ | |
1000V | 20MΩ/200MΩ/1000MΩ | 0.01MΩ/0.1MΩ/1MΩ | 1mA @ 1MΩ | |
Insulation Pretest | ||||
Insulation Safety Pretest | Requires the unit to be connected to L, N and PE | |||
Loop and Line Impedance (Zi) | ||||
Range | Resolution | |||
10Ω (Hi current mΩ mode) 20Ω/200Ω/2000Ω | 1mΩ / 0.01Ω / 0.1Ω / 1Ω | |||
RCD Testing | ||||
Model Number | Types Tested | |||
1662 | AC, G, S, A/F | |||
1663/1664 FC | A/F, AC, B/B+, G and S | |||
RCD Trip Time Test (ΔT) | ||||
Current Range | Step Size | Dwell Time | Measurement Accuracy | |
Type G | Type S | |||
30 to 110% of RCD Rated Current | 10% of index IΔN | 300ms/step | 500ms/step | ±5% |
Notes 30 % to 210 % for Type A IΔN = 10mA 20 % to 210 % for Type B |
Specified trip current ranges (EN 61008-1): 50 % to 100 % for Type AC 35 % to 140 % for Type A (>10 mA) 35 % to 200 % for Type A (≤10 mA) 50 % to 200 % for Type B |
|||
Earth Resistance Test (RE) - Only Available On 1664 FC and 1663 | ||||
Range | Resolution | Frequency | Output Voltage | |
200Ω | 0.1Ω | 128Hz | 25V | |
2000Ω | 1Ω | 128Hz | 25V | |
Phase Sequence Indication | ||||
Icon | Range | Display | ||
Shows icon when active | 100 to 500V | 1-2-3 or 3-2-1 | ||
General Specifications | ||||
Dimensions | 10cm (L) x 25cm (W) x 12.5cm (H) | |||
Weight (Including Batteries) | Approx 1.3kg | |||
Battery Size | 1.5V type AA (IEC LR6) x 6 | |||
Sealing | IP40 | |||
Safety | Complies with IEC/EN61010-1, UL61010, ANSI/ISA - s82.02.01 and CAN/CSA c22.2 No. 1010 | |||
Overvoltage | CAT III 500V, CAT IV 300V | |||
Performance | EC/EN61557-1 to IEC/EN61557-7 and IEC/EN61557-10 |