Chauvin Arnoux PEL51 1-Channel Power & Energy Logger
The Chauvin Arnoux PEL51 1-Channel Power & Energy Logger is a power and energy meter suitable for conducting energy efficiency surveys on single-phase installations. For an introduction to the benefits of Chauvin Arnoux's PELs, please watch our PASS Presents Video.
PEL51 Measurement Capabilities
In addition to true-RMS voltage and current measurement, the Power & Energy Logger can ascertain the following power values:
- Active P (W)
- Fundamental Active Pf (W)
- Fundamental Reactive Qf (var)
- Non-active N (var)
- Distortion D (var)
- Apparent S (VA)
It will also determine all the relevant energy measurements.
Mini94 Current Clamp (Optional)
When used with an optional Mini94 Current Clamp, it can measure AC currents between 50mA and 200 A. It delivers excellent accuracy and allows installations to be measured without interfering with the running of the circuit.
Data Recording
The Chauvin Arnoux PEL51-1 can be programmed to record data to an SD or SDHC at intervals from one minute to one hour. Saved measurements can be easily read on a PC.
PEL Transfer Software
Using Chauvin Arnoux’s PEL program you can download recorded data to your PC where it can be analysed, annotated, saved, or exported.
Wi-Fi Interface
A VNC mode enables the Chauvin Arnoux Power & Energy Logger to be controlled via a web browser (Chrome, Firefox, Windows, Android, iOS, etc.). It also supports connection via an IRD server. The Chauvin Arnoux PEL51 1-Channel Power & Energy Logger is a simple-to-use, precise power and energy efficiency meter suitable for single-phase installations.
Videos
PASS Presents Power Analysis with an Energy Logger Can Reduce Usage Costs
How To Videos
A Quick Start Guide to the Chauvin Arnoux PEL51 Power & Energy Logger
How To Setup the Chauvin Arnoux PEL51 Via Wi-Fi
How To Setup the Chauvin Arnoux PEL51 Via a PC
Key Features
- Power and energy meter
- Suitable for conducting energy efficiency surveys on single-phase installations
- Power supply via base
- True-RMS voltage and current measurements
- Active power P (W)
- Fundamental Active power Pf (W)
- Fundamental Reactive power Qf (var)
- Non-active power N (var)
- Distortion power D (var)
- Apparent power S (VA)
- Determines all relevant energy measurements
- Can be used with a Mini94 Current Clamp to measure AC currents (50mA-200A) without interfering with the installation
- Record data to an SD or SDHC card
- Record data at intervals ranging from every minute to every hour
- Use the supplied PEL Software to download, save, analyse, and annotate data on a PC
- Wi-Fi interface
- Can be controlled via a web browser
- Supports connection via an IRD server
- Simple-to-use, precise power and energy efficiency meter
What's Included?
Key | What's Included? | PEL51 | PEL52 |
---|---|---|---|
1
|
PEL51 or PEL52 | 1 | 1 |
2
|
Safety leads, 3 m, banana-banana, straight-straight | 1 red, 1 black | 1 red, 1 blue, 1 black |
3
|
Crocodile clips | 1 red, 1 black | 1 red, 1 blue, 1 black |
4
|
MiniFlex MA194 250 mm current sensor | 1 | 0 |
5
|
Power cord | 1 | 1 |
6
|
C8 male / 2 banana plugs adapter | 1 | 1 |
7
|
8 GB SD card (in the device) | 1 | 1 |
8
|
SD card-USB adapter | 1 | 1 |
9
|
Test report | 1 | 1 |
10
|
Multilingual quick start guide | 1 | 1 |
11
|
Multilingual device safety data sheet | 1 | 1 |
12
|
Multilingual safety data sheet for current sensors and leads | 2 | 2 |
13
|
Carrying bag | 1 | 0 |
In the Box
Manuals & Guides
Brochures & Catalogues
PEL51 | |
---|---|
Display | Multi-display backlit LCD |
Types of Installations | Single-phase |
Number of channels | 1V/1I |
Network Frequency | 50 and 60 Hz |
Voltage | 10 V to 600 V |
Ratios | Yes |
Power/Energy Values | P, Pf, N, S, Qf, D / Up to 4 Exa |
Min - Max | Yes |
THD | Yes |
Acquisition Rate | 1 measurement / s |
Aggregation | 1 min to 60 min |
Storage Mode | SD / SD-HC card, 8 GB (expandable to 32 GB) |
Ethernet | Yes (via simplified Wifi) |
Safety | IEC 61010 CAT III 600 V |
Power Supply | Via the measurement phase (90 - 600 V) |
Battery | NiMH - Battery life 1 hour |
Dimensions | 180 x 88 x 37 mm |
Weight | 400 g |
Casing | IP54 |
Reviews
SKU | P01157166 |
---|---|
Manufacturer Part Code | P01157166 |
Country of Origin | France |