Chauvin Arnoux PEL52 2-Channel Power & Energy Logger
A power and energy meter with two channels, the Chauvin Arnoux PEL52 2-Channel Power & Energy Logger is suitable for conducting energy efficiency surveys on installations with split-phase or two single-phase channels.
Measurement Capabilities
It can measure the following power values:
- Active P (W)
- Fundamental Active Pf (W)
- Fundamental Reactive Qf (var)
- Non-active N (var)
- Distortion D (var)
- Apparent S (VA)
In addition to this, it can determine all relevant energy measurements as well as true-RMS voltage and current.
Mini94 Current Clamp (Optional)
Using the PEL52 with an optional Chauvin Arnoux Mini94 Current Clamp allows you to gather current measurements without interfering with installations. The Mini94 Current Clamp delivers excellent accuracy and can measure AC currents between 50mA and 200 A.
Data Recording
Data may be recorded at intervals ranging from every minute to every hour to an SD or SDHC card.
PEL Transfer Software
Chauvin Arnoux’s PEL Transfer Software allows you to download data to your PC from where it may be analysed, annotated, saved, or exported.
Wi-Fi Interface
A VNC mode allows the Chauvin Arnoux PEL52 2-Channel Power & Energy Logger to be controlled via a web browser (Chrome, Firefox, Windows, Android, iOS, etc). It also supports a connection via an IRD server.
The Chauvin Arnoux PEL52 2-Channel Power & Energy Logger is a simple-to-use, precise, power and energy efficiency meter suitable for measuring installations with a split-phase or two single-phase channels.
Key Features
- Power and energy meter with two channels
- Conduct energy efficiency surveys on split-phase or two single-phase installations
- Active power P (W)
- Fundamental Active power Pf (W)
- Fundamental Reactive power Qf (var)
- Non-active power N (var)
- Distortion power D (var)
- Apparent power S (VA)
- True-RMS voltage
- True-RMS current
- Determines all relevant energy measurements
- Can be used with a Mini94 Current Clamp to measure AC currents (50mA-200A) without interfering with the installation
- Record data to an SD or SDHC card
- Record data at intervals ranging from every minute to every hour
- Use Chauvin Arnoux’s PEL Transfer Software to download, analyse, annotate, save, and export data via your PC
- VNC mode enables control via a web browser
- Supports connection to an IRD server
- A simple-to-use, precise power and energy efficiency meter suitable for measuring installations with a split-phase or two single-phase channels
Key | What's Included? | PEL51 | PEL52 |
---|---|---|---|
1
|
PEL51 or PEL52 | 1 | 1 |
2
|
Safety leads, 3 m, banana-banana, straight-straight | 1 red, 1 black | 1 red, 1 blue, 1 black |
3
|
Crocodile clips | 1 red, 1 black | 1 red, 1 blue, 1 black |
4
|
MiniFlex MA194 250 mm current sensor | 1 | 0 |
5
|
Power cord | 1 | 1 |
6
|
C8 male / 2 banana plugs adapter | 1 | 1 |
7
|
8 GB SD card (in the device) | 1 | 1 |
8
|
SD card-USB adapter | 1 | 1 |
9
|
Test report | 1 | 1 |
10
|
Multilingual quick start guide | 1 | 1 |
11
|
Multilingual device safety data sheet | 1 | 1 |
12
|
Multilingual safety data sheet for current sensors and leads | 2 | 2 |
13
|
Carrying bag | 1 | 0 |
In the Box
Manuals & Guides
Brochures & Catalogues
PEL52 | |
---|---|
Display | Multi-display backlit LCD |
Types of Installations | Split-phase or 2 single-phase channels |
Number of channels | 2V/2I |
Network Frequency | 50 and 60 Hz |
Voltage | 10 V to 600 V |
Ratios | Yes |
Power/Energy Values | P, Pf, N, S, Qf, D / Up to 4 Exa |
Min - Max | Yes |
THD | Yes |
Acquisition Rate | 1 measurement / s |
Aggregation | 1 min to 60 min |
Storage Mode | SD / SD-HC card, 8 GB (expandable to 32 GB) |
Ethernet | Yes (via simplified Wifi) |
Safety | IEC 61010 CAT III 600 V |
Power Supply | Via the measurement phase (90 - 600 V) |
Battery | NiMH - Battery life 1 hour |
Dimensions | 180 x 88 x 37 mm |
Weight | 400 g |
Casing | IP54 |
Reviews
SKU | P01157167 |
---|---|
Manufacturer Part Code | P01157167 |
Country of Origin | France |