T & R KV10-120 mk2 High Voltage AC Test Set - 10kV, 120mA

Please note that this is a price-on-request item. Please call us for more information.

This high voltage AC tester can generate voltage output from 0 to 10kV and is used in testing insulation systems and breakdown voltage.

Voltage on the KV10-120 is completely variable across the entire range. A special zero-voltage interlocking function is included which ensures that the output may only be energised with the voltage control set up zero.

Both output voltage and current values are measured and displayed by two separate analogue indicators built into the body of the tester. The voltmeter scale has range of x0.5, while the mA (current) meter has x0.1 range.

For extra safety, the KV10-120's output and - in extension - the object being tested are protected by a user-adjustable electronic current trip. This can be set from 10 to 110% of the rated output in 10% steps. When voltage breakdown occurs in the test object, the KV10-120 uses visual indicators to display this fault condition.

T & R KV10-120 mk2 High Voltage AC Test Set Key Features

  • Output voltage range from 0 to 10kV
  • Maximum current of 120mA
  • Automatic mains voltage selection
  • Key operated - prevents unauthorised use
  • Dual overload protection
  • Variable electronic trip from 10 to 110% of rated output
  • Analogue scales for both voltage and current
  • Zero volt interlock
  • External 24V DC interlocking circuit
  • Visual indicator upon voltage breakdown

What's Included?

  • T & R KV10-120 mk2 High Voltage AC Test Set
  • Supply Lead
  • Spare Fuse Set
  • Operating Manual
  • Earth Lead
  • ES30 Earthing Stick

T & R KV Series Technical Specifications

Supply Requirements 115V/230V: ±10% auto selecting
50/60Hz 1ph 1200VA max, 50/60Hz 1ph 650VA (VC24-24)
Output
Output The output of the KV series units is a permanently connected partially-screened high voltage cable
Unit Output Voltage Current (Continuous) Current (5 Min)
KV6-200 0-6kV 100mA 200mA
KV10-120 mk2 0-10kV 60mA 120mA
KV15-80 mk2 0-15kV 40mA 80mA
KV30-40 mk2 0-30kV 20mA 40mA
VC24-24 0-24kV 15mA 24mA
Note The above intermittent on times must be followed by fan off time of 15 minutes, and are based on an ambient temperature of 25°C.
Output Metering (Voltage)
Unit x0.5 Range x1 Range Accuracy
KV6-200 3.25kV 6.5kV ±2% of FS
KV10-120 mk2 0-6kV 0 to 12kV ±2% of FS
KV15-80 mk2 0-10kV 0 to 20kV ±2% of FS
KV30-40 mk2 0-20kV 0 to 40kV ±2% of FS
VC24-24 - 0 to 24kV ±2% of FS
Output Metering (Current)
Unit x0.1 Range x1 Range Accuracy
KV6-200 25mA 250mA ±2% of FS
KV10-120 mk2 14mA 140mA ±2% of FS
KV15-80 mk2 10mA 100mA ±2% of FS
KV30-40 mk2 5mA 50mA ±2% of FS
VC24-24 3mA 30mA ±2% of FS
Other Specs
Overload Protection Two overload protection circuits are provided on the units. The first is user-selectable and allows trip currents between 10 and 110% of the rated output to be a set. A trip condition is indicated by an illuminated push button and audible alarm. The second trip circuit is a magnetic circuit breaker operating on the primary of the HV transformer. This operates on large overloads (such as under flashovers)
Protection and Safety Fuse protection
Meets requirements of BS EN61010
Earth terminal on transformers which must be connected to a low impedance local earth
Storage Temperature -20 to 60°C
Operating Temperature 0 to 45°C
Dimensions & Weight
Unit Dimensions Weight
KV6-200 300 x 400 x 470mm 34kg
KV10-120 300 x 400 x 470mm 42kg
KV15-80 300 x 400 x 470mm 42kg
KV30-40 300 x 400 x 470mm 42kg
VC24-24 300 x 400 x 470mm 27kg