The Sonel PQM-700 Power Quality Analyser measures and records electrical parameters according to IEC 61000-4-30 Class S. It is a cost-effective load parameter recorder making it suitable for electricians and maintenance personnel, as well as consumers and producers of renewable energy (wind farms, solar farms) who require 4-quadrant power analysis. It has four current inputs and can provide a current measurement for the neutral conductor.
Measurement and Logging Capabilities
- Current L1, L2, L3, N (four measurement inputs): supports a maximum measurement range of 6kA, depending on the current clamp used, and can determine the average, minimum, maximum and instant current measurements; provides interoperability with current transducers
- Voltages L1, L2, L3, N (four measurement inputs): supports interoperability with voltage transducers and can measure average, minimum, maximum and instant voltages up to 760V
- Unbalance of voltage and currents
- Current and voltage event logging with oscillograms and half-period RMS charts
- Power measurements: active power (P), reactive power (Q), distortive power (D), and apparent power (S) with identification of the nature of the reactive power (capacitive, inductive); reactive power is calculated using the Budeanu and IEEE 1459 methods
- Power factor (PF): cosφ, tanφ
- Energy measurements: active energy (EP), reactive energy (EQ) and apparent energy (ES)
- Crest factors for current (CFI) and voltage (CFU)
- Frequency: 40Hz-70Hz
- Harmonics up to the 40th in voltage and current
- Total harmonic distortion THD for current and voltage
- Short-term (PST) and long-term (PLT) light flicker index
The Sonel PQM-700 Power Quality Analyser is equipped with a built-in heater enabling it to deliver high-accuracy readings compliant with IEC 61000-4-30 Class S in conditions as cold as -20°C.
Up to 1100 parameters, including average, minimum, maximum and instantaneous readings, can be saved to the Sonel PQM-700 Power Quality Analyser. Its internal, rechargeable battery ensures that the Sonel PQM-700 can continue to record data for up to six hours after power failure. Data is recorded onto a removable 2GB memory card; it can be downloaded to a PC using a USB connection or a card reader.
Once downloaded, data, including events, can be evaluated using Sonel’s free Analysis Software. This application also includes advanced features enabling the user to save results on his/her PC’s hard drive as either raw data or in a report. Sonel’s Analysis Software is continually revised to ensure it meets the latest standards and requirements.
Finally, the Sonel PQM-700 Power Quality Analyser is IP65-rated, making it suitable for use in rugged environments and in rain, snow and high-humidity. It is a rugged, accurate and reliable PQA suitable for analysing a range of mains systems including single-phase, split-phase with common N, three-phase WYE with and without N conductor, three-phase Delta, three-phase WYE and Delta Aron, and systems with current and voltage transducers.
Key Features
- Measures and records electrical parameters according to IEC 61000-4-30 Class S
- Cost-effective load parameter recorder suitable for electricians and maintenance personnel
- Ideal for consumers and producers of renewable energy (wind farms, solar farms) who require 4-quadrant power analysis
- Four current inputs
- Provides a measurement for the current in the neutral conductor
- Current L1, L2, L3, N (four measurement inputs) up to 6kA (depending on the current clamp used)
- Interoperability with current transducers
- Voltages L1, L2, L3, N (four measurement inputs): up to 760V
- Interoperability with voltage transducers
- Unbalance of voltage and currents
- Current and voltage event logging with oscillograms and half-period RMS charts
- Active power (P)
- Reactive power (Q)
- Distortive power (D)
- Apparent power (S) with identification of the nature of the reactive power (capacitive, inductive)
- Reactive power is calculated using the Budeanu and IEEE 1459 methods
- Power factor (PF): cosφ, tanφ
- Active energy (EP)
- Reactive energy (EQ)
- Apparent energy (ES)
- Crest factors for current (CFI) and voltage (CFU)
- Frequency: 40Hz-70Hz
- Harmonics up to the 40th in voltage and current
- Total harmonic distortion THD for current and voltage
- Short-term (PST) and long-term (PLT) light flicker index
- Built-in heater to enable accurate measurement at temperatures as low as -20°C
- Save up to 1100 parameters with average, minimum, maximum and instantaneous readings
- Internal, rechargeable battery provides up to six hours of power
- Removable 2GB memory card
- Download data to a PC using a USB connection or using a card reader
- Use Sonel’s free Analysis Software to view, analyse and save data and create reports
- IP65
- Suitable for use in rain, snow and high-humidity
- Analyse mains systems including single-phase, split-phase with common N, three-phase WYE with and without N conductor, three-phase Delta, three-phase WYE and Delta Aron
- Analyse mains systems with current and voltage transducers
- A rugged, accurate and reliable PQA
What’s Included?
- Sonel PQM-700 Power Quality Analyser
- 4x F3-A Flexible Clamps, Class S, IP65
- 3x Black Crocodile Clips, 1kV, 20A
- 2x Red Crocodile Clips, 1kV, 20A
- 1x Blue Crocodile Clip, 1kV, 20A
- 2m Straps for Mounting the PQA on a Pole
- DIN Rail-mounting Bracket with Positioning Catches
- 2x Fasteners and Bands for Mounting the PQA
- AZ-1 Power Supply Adapter (mains plug/ banana inputs)
- USB Cable
- Sonel Analysis Software
- PASS Power Bank & Magnetic Wireless Charger (10 000mAh 15W) - PASSPOWER-PLUS, typically £49.00
Sonel PQM-700 Power Quality Analyser Technical Specifications
Specification | Range | Resolution | Accuracy | |
AC voltage (TRMS) | - | 0.0…760,0 V | 0.01 % Un | ±0.5% Un |
Crest Factor | Voltage | 1.0…10.00 (≤1,65 for voltage 690 V) | 0.01 | ±5% |
Crest Factor | Current | 1.00…10,00 (≤3,6 Inom) | 0.01 | ± 5% m.v. |
AC current TRMS | - | depends on the clamp* | 0.01 % of nominal range | ±1% of nominal range (add clamps accuracy) |
Frequency | - | 40.00...70.00 Hz | 0.01 Hz | ±0.05 Hz |
Active, reactive, apparent power and distortion | - | depends of configuration (transformers, clamp) | up to 4 decimal places | depends on configuration (transformers, clamp) |
Active, reactive apparent energy | - | depends of configuration (transformers, clamp) | up to 4 decimal places | the same as above |
cosφ and Power Factor (PF) | - | 0.00...1.00 | 0.01 | ±0.03 |
tgφ | - | 0.00...10.00 | 0.01 | depends on Active and Reactive power accuracy |
Harmonics | Voltage | same as for AC voltage TRMS | same as for AC voltage TRMS | ±5% Uh for Uh ≥ 1% Un ±0,05% Un for Uh < 1% Un |
Harmonics | Current | same as for AC current TRMS | same as for AC current TRMS | ± 5% Ih for Ih ≥ 3% In ± 0.15% In for Ih < 3% In |
Total Harmonics Distortion | Voltage | 0.0..100,0% | 0.1% | ±5% |
Total Harmonics Distortion | Current | 0.0..100,0% | 0.1% | ±5% |
Flicker | - | 0.40...10.00 | 0.01 | ±10% |
Unbalance | Voltage and Current | 0.0...10.0% | 0.1% | ±0.3% (absolute error) |
Notes | *Clamp F-1/F-2/F-3:0..3000 A (10000 Ap-p) | |||
*Clamp C-4: 0..1000 A (3600 Ap-p) | ||||
*Clamp C-5: 0..1000 A (3600 Ap-p) | ||||
*Clamp C-6: 0..10 A (36 Ap-p) (without current transformers) | ||||
*Clamp C-7: 0...100 A (360 Ap-p ) |