With the use of the Sonel MZC-310S meter, it is possible to test short circuit loop impedance in consumer networks as well as in distribution networks protected with high-current circuit breakers. At the same time as measuring the impedance, the shock and contact voltages can be measured. Where the condition for automatic power off cannot be satisfied, the facility may be authorised to operate based on the voltage criterion.
The application of the four-wire method and the flow of the measuring current in the 150/280 A pulse determine the high precision of the performed test. This single device hides a multitude of measurement capabilities, making it appreciated by specialists in many fields. The meter complies with the requirements specified in the EN 61557 standard.
Measurement Functions | Measurement Range | Display Range | Resolution | Accuracy |
---|---|---|---|---|
Voltage | 0 V…440 V | 0 V…440 V | 1 V | ±(2% m.v. + 2 digits) |
Frequency | 45.0 Hz…65.0 Hz | 45.0 Hz…65.0 Hz | 0.1 Hz | ±(0.1% m.v. + 1 digit) |
Short-circuit Loop Parameters | ||||
4p method - high current measurement maximum current 280 A | 7.2 mΩ…1999 mΩ acc. to EN 61557 | 0.0 mΩ…1999 mΩ | from 0.1 mΩ | ±(2% m.v. + 2 mΩ) |
2p method - standard current measurement maximum current 42 A | from 0.13 Ω…199.9 Ω acc. to EN 61557 | 0.00 Ω…199.9 Ω | from 0.01 Ω | from ±(2% m.v. + 3 digits) |
Short-circuit Current Readings | ||||
4p method - high current measurement network voltage 230 V, 400 V | up to 115.0 A…55.7 kA | 115.0 A…400 kA | from 0.1 A | Calculated based on error for fault loop |
2p method - standard current measurement | from 1.150 A…1607 A acc. to EN 61557 | 115.0 A…400 kA | from 0.001 A | Calculated based on error for fault loop |
Touch and shock voltage | ||||
4p method - high current measurement | 0 V…100 V | 0 V…100 V | 1 V | ±(10% m.v. + 2 digits) |