This kit is identical to Seaward's PrimeTest 250+ Pro Bundle, but also comes with a copy of Seaward PATGuard Elite 3 Software (1 Year License).
If you're a professional PAT tester regularly testing appliances, you can't go wrong with this pack. It includes everything you need to test, a printer for easy label creation, a checkbox to verify accuracy and even a large size carrying bag.
The Pro bundle also comes with:
Seaward's easiest-to-use, downloadable tester with internal memory for storing your testing results.
Handheld, portable and designed to make PAT testing as simple as possible, the Seaward PrimeTest 250+ performs all tests required by the IET Code of Practice, instantly prints out labels with the included printer and - at the touch of a button - can transfer stored testing to PC via USB connection.
As standard, records stored on the PT250+ are transferred in CSV format, allowing them to be opened with Excel or a similar program. Alternatively, you can also use the included PATGuard Elite 3 software to create professional reports and certificates based on your data.
With PATGuard 3 you can take full control over every aspect of your PAT testing.
The software is suitable for use with both manual and downloadable PAT testers and can be used for a wide variety of tasks, including tagging photos to sites, locations and asset IDs, performing electrical risk assessments and generating professional reports
Please note that PATGuard 3 elite is a subscription-based software package and will require renewal upon expiry.
Earth Continuity | |
Output Current |
200mA minimum into 2Ω |
Test Voltage (o/c) | 9V DC nominal |
Test Duration (Class I Test) | 2s nominal |
Display Range | 0.01Ω to 19.99Ω |
Pass Value (Class I Test) | 0.2Ω |
Insulation Resistance | |
Test Voltage | 250/500V DC @1mA nominal, <2mA (s/c) |
Test Duration (Class I or II) | 2s |
Display Range | 0.01MΩ to 19.99MΩ |
Pass Value | Class I: 1.0MΩ Class II: 2.0MΩ |
Equivalent Leakage | |
Test Voltage | 40V Nominal AC 50Hz Open Circuit |
Test Duration | 2s |
Display Range | 0.1mA to 19.99mA |
Pass Value | 0.75mA/3.5mA (user selectable with 0.75mA as default)/0.25mA CL II |
IEC Lead Test | |
Test Voltage | 5V DC Nominal |
Test Duration | Time for Test (2s max) |
Test | Live/Neutral Checks for o/c, s/c and crossed |
Protective Conductor Current | |
Test Voltage | Supply voltage, max current 13A |
Test Duration | 120s Maximum |
Display Range | 0.15mA to 9.99mA |
Pass Value | 0.75mA/3.5mA (user selectable with 0.75mA as default) |
Touch Current | |
Test Voltage | Supply voltage, max current 13A |
Test Duration | 120s maximum |
Display Range | 0.10mA to 3.50mA |
Pass Value | 0.25mA |
3 Phase Differential Leakage Current *Requires 3 phase adaptor accessory |
|
Test Voltage | 3 phase supply voltage |
Test Duration | Continuous measurements |
Display Range | 0.10mA to 9.99mA |
Pass Value | 0.75mA/3.5mA (user selectable with 0.75mA as default) |
RCD Trip Time | |
Test Voltage | Mains supply voltage |
Test Current | 30mA/150mA rms sinusoidal |
Test Current Phase | 0/180° auto switched on alternate tests |
Measuring Range | 0ms to 500ms |
Pass Value | 200ms |
Power Socket Check | |
Input Voltage Range | 225-254V AC max current 13A UK |
Indicates configuration of voltage potential: | Line to earth, line to neutral, neutral to earth |
General | |
Memory Size | 999 Test Records |
Power Source | 6 x AA Batteries |