The Seaward Clare SafeCheck 8 is a bench-mounted automatic safety tester used for checking the electrical safety of Class I and Class II tools and equipment as well as IEC extension power cords used within the hire and rental sectors.
With fast, automated testing sequences, and fixed test limits, the SafeCheck 8 will help you to perform the tests you need in the smallest amount of time possible. You can even combine it together with a barcode scanner for faster asset scanning, or connect to a printer to print out customised labels.
The SafeCheck 8 performs a wide variety of different electrical safety tests: it can test earth/ground bond, AC dielectric strength (flash/hipot), insulation resistance, earth/ground leakage and touch leakage tests.
Once you're done testing, you can store results directly on the SafeCheck 8's internal 5000 record memory. You can then recall results as needed, or use the optional printer to easily create PASS/FAIL labels for your appliances.
Seaward Clare SafeCheck 8 Bench-Mounted Automatic Safety Tester Key Features
- Quick, fast and reliable checks of the electrical safety of Class I and Class II tools and equipment + IEC extension power cords
- Ideal for use in hire/rental sectors
- Fast, automatic test sequences with fixed test limits
- Large-size LCD display
- Internal memory storage for up to 5000 results
- Combine with an optional Desk Test n Tag Printer to create custom PASS/FAIL labels
- Earth/ground bond testing
- AC dielectric strength testing (flash/hipot)
- Insulation resistance tests
- Earth/ground leakage tests
- Touch leakage tests
What's Included?
- Seaward Clare SafeCheck 8 Tester
- HT Probe
- 3 Pin Guard Link Connector
- Earth Bond Clip
- Instruction Manual
- Calibration Certificate
Seaward STM/L and SC08 Tester Comparison Chart
Key Features | STM/L | SC08 |
6000-result memory | 5000-result memory | |
Manual and semi-automatic testing | Automatic testing | |
- | Fixed test limits | |
On-screen instructions | - | |
Integration into ISO quality control systems | - | |
Applications | Conduct safety tests on electrical and electronic components to CE and International standards |
Class I, Class II and IEC power cord tests |
Ideal For | Small scale electrical manufacturers and service/ repair centres | Hire and rental sector |
Production and Manufacturing Engineers/Managers/Directors |
Service engineers | |
Quality Managers/Directors | - | |
Operations Managers/Directors | - | |
Electrical Test Function | ||
Earth/ground bond test | ✔ | ✔ |
AC/flash/hipot test | ✔ | ✔ |
Insulation resistance | DC | ✔ |
Leakage test | ✔ | Earth/ Ground and Touch |
Load test | ✔ | ✖ |
Power/run test | ✔ | ✖ |
Optional Accessories
- 194A922 - CCD Barcode Scanner
- Desk Test n Tag Labels (Blue, Green, Orange, Red, White and Yellow Available)
- Desk Test n Tag Printer
- Desk Test n Tag Printer Ribbon
- Guard Plug with Link
- Hipot Test Probe
- PAT Checkbox
- PatGuard 3 PAT Testing Software
Seaward Clare SafeCheck 8 Technical Specifications
Flash/Hipot Test (Class I) | |
---|---|
Test Voltage Class I | 1.25kV AC |
Display Range | 0.1 to 10mA AC |
Resolution | 0.01mA |
Accuracy | ±5% ±2 digits |
Pass Levels | Selectable up to 10mA |
Flash/Hipot Test (Class II) | |
Test Voltage | 2.5kV AC |
Display Range | 0.1 to 10mA AC |
Resolution | 0.01mA |
Accuracy | ±5% ± 2 digits |
Pass Levels | Selectable up to 10mA |
DC Insulation Test | |
Test Voltage | 250/500V |
Display Range | 0.1 to 99.99MΩ |
Accuracy | ±5% ± 2 digits (up to 19.99MΩ) |
Earth/Ground Bond Test | |
Test Voltage | 6V AC (open circuit) |
Test Current | 25A, 10A, 4A, 100mA AC into short circuit |
Range | 0.04 to 20Ω |
Resolution | 1mΩ |
Accuracy | ±5% ±2 digits |
Pass Levels | User-selectable |
Substitute Leakage (Short to Case) Test | |
Test Voltage | 40V AC o/c |
Display Range | 0.1 to 20.0mA AC |
Resolution | 0.01mA |
Accuracy | ±10% ± 2 digits (1.00 to 20mA) |
Earth Leakage | |
Display Range | 0.1 to 20.0mA AC |
Resolution | 0.01mA |
Accuracy | ±10% ±2 digits (1.00 to 20mA) |
Pass Levels | Selectable up to 10mA |
Power/Run/Load Tests | |
Resolution | 0.01kVA |
Measured Load | 0 to 4kVA |
Accuracy | ±10 of reading, ±2 digits |
IEC Power Cord Test | |
Test Voltage | 40V AC |
Detects | Good, open, short, reversed |
General Specifications | |
Dimensions | 450 x 410 x 155mm |
Weight (Approx) | 8.8kg (20lbs) |
Supply Voltage | Selectable 115V / 230V, 50/60Hz |
Operating Temperature | 0 to +40°C |
Storage Temperature | -10 to +50°C |
EN50191 | Compliant when used with appropriate accessories |
Reviews
SKU | SC08 |
---|---|
Manufacturer Part Code | SC08 |