Metrel MI 3152-ES Multifunction Tester & A 2214 Ring Continuity Adaptor

All Metrel Products
  • Metrel MI 3152 Multifunction Tester
  • Automated RCD testing procedure
  • Metrel A 2214 Ring Continuity Adapter
  • No risk of forgotten connections
SKU
RINGKIT2
MPN
RINGKIT2

Read More

View All Multifunction Testers

This entry set kit includes the Metrel MI 3152 Multifunction Tester and the A 2214 Ring Continuity Adaptor, please the 'What's Included?' section for full kit details.

Metrel MI 3152 Multifunction Tester

The Metrel MI 3152 EurotestXC Multifunction Tester represents the latest generation of Metrel’s multifunctional measuring instruments. It retains well-known features such as comprehensive installation safety testing in accordance with IEC/EN 61557 and AUTO SEQUENCE testing for TN, TT, and IT earthing systems, all managed through a new user interface with a large colour touchscreen display.

The device offers a comprehensive range of functions, including online voltage monitoring, phase sequence testing, earth resistance measurement, illuminance measurement, and TRMS current measurement. It also performs RCD tests, line and loop impedance tests, earth resistance measurements, ISFL measurements, and IMD tests.

Key Features

  • Predefined Automatic tests:
    • Auto TT (U, Zln, Zs, Uc);
    • Auto TN/RCD (U, Zln, Zs, Rpe)
    • Auto TN (U, Zln, Zlpe, Rpe)
    • Auto IT (U, Zln, Isc, Isfl, IMD)
  • Built-in help screens for referencing on site.
  • Built-in fuse tables for automatic evaluation of the line/loop impedance result.
  • Monitoring of all 3 voltages in real-time.
  • Automatic polarity reversal on continuity test.
  • Automated RCD testing procedure.
  • Built-in charger and rechargeable batteries as standard accessory.
  • BT communication with PC, Android tablets and smartphones via built-in BT.
  • PC SW Metrel ES Manager for creation of test structures and uploading, downloading of test results and report creation.
  • Support for aMESM Android APP and data management tool (option).
  • Dimensions (w x h x l): 230 x 103 x 115 mm.
  • Mass (without accessories): 1.3 kg.

Metrel A 2214 Ring Continuity Adapter

The Metrel A 2214 Ring Continuity Adapter measures continuity in ring final circuits. It automatically conducts r1, rn, r2, and R1 + RN, R1 + R2 measurements.

The A 2214 quickly connects to the distribution board's colour-coded L, N, and PE wires. Managed by the tester, it conducts all required ring continuity tests. This streamlined method significantly simplifies and reduces the time needed for comprehensive testing of ring final circuits.

Key Features

  • Automated continuity testing (patented) of ring final circuits: r1, rn, r2 and R1+RN, R1+R2.
  • Live, neutral and PE resistance are all measured at the press of a button.
  • Automatic calculation of (r1+rn)/4 and (r1+r2)/4 for easy results evaluation.
  • Connected once, no need to change leads until all continuity tests are complete.
  • Quick, efficient and easy. Optimize and significantly speed up (up to 60% or more) continuity tests of ring final circuits.
  • Safety, no risk of forgotten connections.
  • Convenience, no need to exchange leads or use connectors.
  • Thoroughness, R1+RN also measured simultaneously.
  • Test speed, connections made by the adapter.
  • Accuracy, with the easy-null capability.
  • Usability can be magnetically attached to the distribution board.

What's Included?

  • Metrel MI 3152 Multifunction Tester
  • Metrel A 2214 Ring Continuity Adapter
  • Test lead, 3 x 1.5 m
  • Power supply adapter
  • 6 NiMH rechargeable batteries, type AA
  • Test probe, 3 pcs (blue, brown, green)
  • Crocodile clip, 3 pcs (blue, brown, green)
  • RS232 - PS/2 cable
  • USB cable
  • Soft carrying bag
  • Soft carrying neck belt
  • Short instruction manual
  • Instruction manual on CD
  • Handbook on CD
  • Calibration certificate
  • Small soft carrying bag A 1020 (A 2214)
  • Crocodile clip A 1297, brown, 2 pieces (A 2214)
  • Crocodile clip A 1309, green, 2 pieces (A 2214)
  • Crocodile clip A 1310, blue, 2 pieces (A 2214)
  • Battery A 1784, size AA, 1.5V alkaline, 4 pieces (A 2214)
  • Instruction manual (A 2214)

Videos

MI 3152 Multifunction Tester Promotional

Electrical Installation Testing | MI 3152 EurotestXC | Features Overview

A 2214 Ring Continuity Adapter Promotional

A 2214 | Ring Continuity Adapter | Promotional (UK)

Β£1,683.00
£2,019.60 inc vat
Free Delivery*
Important Notice
This item is made-to-order exclusively for you once your order is placed. As a result, it is not eligible for cancellation or return under our standard policy. Your statutory rights remain unaffected.
1683 Reward Points 60 Days Return

Ask An Expert
Price Match
Technical Information
Specification

Metrel MI 3152 Multifunction Tester

Extra Features Workspaces El. LV Installation Safety Modes βœ”
Industrial Mode β—‰
Medical Mode βœ”
EVSE Mode β—‰
IT Vehicles / Mobile Units Mode βœ”
Lightning Mode βœ”
Project Structure βœ”
Visual Inspection Mode βœ”
Functional Inspection Mode βœ”
Auto Tests AUTO TT (U, Zln, Zs, Uc) βœ”
AUTO TN/RCD (U, Zln, Zs, Rpe) βœ”
AUTO TN (U, Zln, Zlpe, Rpe) βœ”
AUTO IT (U, Zln, Isc, Isfl, IMD) βœ”
Auto Test Line/Loop Impedance TN/TT βœ”
AUTOSEQUENCES AUTOSEQUENCE profile βœ”
AUTOSEQUENCE EVSE β—‰
AUTOSEQUENCE Barcode testing βœ”
PASS/FAIL System Evaluation βœ”
On-site Parameter Settings βœ”
Automatic test sequences Multitest sequence βœ”
Advanced User Interface Colour display βœ”
Touch screen βœ”
Adaptable user interface βœ”
Graphical Help Menus βœ”
Database System Built-In βœ”
Programmable Memory Structure βœ”
Multi-level Memory Organiser βœ”
SDK support Upload structure βœ”
Upload measurements βœ”
Download βœ”
Main Features
Voltage AC Frequency βœ”
Voltage TRMS βœ”
Three Phase 3-Phase system (Phase SEQUENCE) βœ”
Differential leakage current β—‰
Earth Bond / Continuity PE lead resistance 200 mA 3-wire βœ”
Ring Test 200 mA (UK installations) βœ”
Ring Auto 200 mA (UK installations) β—‰
Max Test Current 7 mA 2-wire βœ”
Max Test Current 200 mA 2-wire βœ”
Automatic polarity reversal βœ”
Insulation Resistance Test Voltage 50 V βœ”
Test Voltage 100 V βœ”
Test Voltage 250 V βœ”
Test Voltage 500 V βœ”
Test Voltage 1000 V βœ”
Test of IMD βœ”
Test of ELM βœ”
DC Ramp Voltage Test/Varistor test βœ”
Automatic Discharge βœ”
Leakage Current Differential Leakage β—‰
Leakage Current (with optional Clamp) β—‰
ISFL: L1, L2 (First Fault Leakage) βœ”
AC Insulation Leakage βœ”
Z Line / Loop Impedance Zline L-L, L-N Ipsc - 3 Wire βœ”
Zline L-L, L-N Ipsc - 2 Wire βœ”
Zloop L-PE, Ipfc - 3 Wire βœ”
Zloop L-PE, Ipfc - 2 Wire βœ”
Zs (rcd) - 3 Wire βœ”
Zref, Ξ”U% βœ”
Fuse Tables βœ”
Max. Ipfc = 20kA βœ”
RCD RCD type AC βœ”
RCD type A βœ”
RCD type F βœ”
RCD type B βœ”
RCD type B+ βœ”
RCD Uc βœ”
RCD (t) βœ”
10 mA βœ”
30 mA βœ”
100 mA βœ”
300 mA βœ”
500 mA βœ”
1000 mA βœ”
RCD I Ramp βœ”
RCD Auto βœ”
RCD 3-Phase βœ”
EV-RCD βœ”
MI-RCD βœ”
RCD-S (Selective) βœ”
PRCD PRCD-S, PRCD-K βœ”
Earth (Electric) Leakage Relay β—‰
Earth/Ground Resistance Earth Resistance 2-wire βœ”
Earth Resistance 3-wire βœ”
Wenner 4-wire Specific Earth Resistance β—‰
Two Iron Clamps Earth Resistance β—‰
Functional test and troubleshooting Load test βœ”
Power Measurements Active power βœ”
Reactive power βœ”
Apparent power βœ”
Power factor βœ”
Harmonics Analysis THD current βœ”
THD voltage βœ”
Current harmonics βœ”
Voltage harmonics βœ”
EVSE measurements Monitoring of voltage β—‰
Monitoring of current β—‰
Simulation of external load β—‰
Additional Features Cable location Cable location β—‰
Hand-Held Hand-Held βœ”
Security User Accounts βœ”
PASS / FAIL Indicators PASS/FAIL Indicators βœ”
Voltage Monitoring Voltage Monitoring βœ”
Display LCD βœ”
Back Light βœ”
Keyboard QWERTY Keyboard βœ”
Virtual Keyboard βœ”
Power Supply Rechargeable Batteries in standard delivery βœ”
Battery Powered βœ”
Power Supply 115 V (50-60Hz) βœ”
Power Supply 230 V (50-60Hz) βœ”
Mains Supply / PE Check βœ”
Test Lead Compensation Test Lead Compensation βœ”
Buzzer Buzzer βœ”
Graphical user interface Graphical Online Help βœ”
Communication Port Communication Port USB βœ”
Communication Port RS232 - PS/2 βœ”
Built-in Bluetooth Built-in Bluetooth βœ”
Mobile Application Android Application βœ”
Printing / Scanning QR-Code Printing / Scanning β—‰
Memory Internal memory βœ”
microSD memory card βœ”
Downloadable βœ”
Uploadable βœ”
IP protection IP 40 βœ”
Protection category CAT IV 300 V βœ”
CAT III 600 V βœ”
Special Accessories EVSE adapter A 1832 Mode 3 Charging cable adapter βœ”
Passive 3-Phase Adapter Passive 3-Phase Adapter β—‰
Active Impedance Adapter Active Impedance Adapter β—‰
Adapter for specific resistance ρ ρ adapter β—‰
Active Euro Checkbox Active Euro Checkbox β—‰
Active Ring Adapter EASYswitch Active Ring Adapter EASYswitch (UK only) β—‰
Cable Locator Cable Locator β—‰
Tip Commander Tip Commander β—‰
Plug Commander Plug Commander βœ”
Current clamps DC - Current Clamp β—‰
Generator Current Clamp β—‰
AC Leakage Current Clamp β—‰
Lux Sensor Lux Sensor β—‰
Smartphones scanner Smartphones scanner β—‰
PC Software Package PC Software Package βœ”
MESM Compatible βœ”
Report creation β—‰
Professional reporting β—‰
Battery Charger Battery Charger βœ”
Electrical Energetics Power generation Earthing and lightning protection in thermal energy power plants βœ”
Renewable energy sources Generator stator testing βœ”
Lightning protection testing in wind plants βœ”
Two-clamp method for measuring earth loops in a solar plant βœ”
Power distribution Insulation of long cables βœ”
Industrial installations Remote antenna tower earthing resistance βœ”
Specific earth resistance measurement methods β—‰
Building Facilities Low voltage electrical installation safety Substation electrical safety βœ”
Mains bonding and touch voltages during fault βœ”
Switchboards and automatic trip-out protection βœ”
Public places electrical safety βœ”
Low voltage earthing and lightning protection Earthing measurement with fall of potential method βœ”
2-clamps method for measuring lightning and earth protection βœ”
Surge protection devices βœ”
Special locations Wet and outdoor locations βœ”
IT system βœ”
DC installations βœ”
EVSE construction and testing βœ”
Transportation e-Mobility EVSE domestic installation testing β—‰
EVSE periodic inspection β—‰
Renewable power and car charging β—‰
Mobile installations Vehicles with an on-board generator β—‰
Emergency response vehicles βœ”
Telecommunication equipment in mobile installations βœ”
Medical Facilities Hospital earthing and lightning protection Two clamps method for measuring lightning and earth protection βœ”
Hospital earthing measurement with fall of potential method βœ”
Mains bonding and touch voltages during fault current βœ”
Surge protection devices in hospitals βœ”
Power supply and power distribution Hospital switchboards and automatic trip-out protection βœ”
Surgery rooms or operating theatres Medical IT system βœ”
Isolated areas RCDs βœ”
Patient recovery rooms and hospital wards Public and workspace electrical safety in healthcare βœ”
Electrical safety in hospital wet areas βœ”
Secondary power sources in healthcare Generator safety βœ”
Ambulances βœ”
Field hospital βœ”
Standards Applied Building LV Installation EISinsp Competences: Low Voltage Electrical Installation Safety Inspection βœ”
EISc Competences: Low Voltage Electrical Installation Safety for Contractors and Maintainers βœ”
IEC/EN 60364 Electrical Installations for Buildings series βœ”
IEC/EN 60364-6 Electrical Installations for Buildings - Verification βœ”
IEC/EN 60364-4-41 Electrical Installations for Buildings - Protection against electric shock βœ”
IEC/EN 60755 General safety requirements for residual current operated protective devices βœ”
IEC/EN 61008-1 Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) βœ”
IEC/EN 61009 Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs) βœ”
IEC/EN 61557 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - series βœ”
IEC/EN 61557-1 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 1: General requirements βœ”
IEC/EN 61557-2 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 2: Insulation resistance βœ”
IEC/EN 61557-3 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 3: Loop impedance βœ”
IEC/EN 61557-6 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 6: Effectiveness of residual current devices (RCD) in TT, TN and IT systems βœ”
IEC/EN 61557-7 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 7: Phase sequence βœ”
IEC/EN 61557-10 Electrical safety in low voltage distribution systems up to 1 000 v a.c. and 1 500 v d.c. - Equipment for testing, measuring or monitoring of protective measures - Part 10: Combined measuring equipment for testing, measuring and monitoring of protective measures βœ”
VDE 0413 (IEC 61557) Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - series βœ”
AS / NZ 3017 Electrical installations – Verification guidelines βœ”
AS / NZ 3018 Electrical installations - Domestic installations βœ”
BS 7671 IEE Wiring Regulations (18th edition) βœ”
CEI 64.8 V4 rated electrical equipment not exceeding 1,000 VAC and 1,500V DC βœ”
Earthing and lightning protection LPSinsp Competences: Lightning Protection of Buildings Inspection βœ”
LPSc Competences: Lightning Protection of Buildings for Contractors and Maintainers βœ”
IEC 62305 Protection against Lightning - series βœ”
IEC/EN 61557-5 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 5: Resistance to earth βœ”
IEC/EN 61557-4 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 4: Resistance of earth connection and equipotential bonding βœ”
Power quality PQA Competences: Power Quality Analyzing & Reporting βœ”
IEC/EN 61557-12 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 12: Power metering and monitoring devices (PMD) βœ”
Electrical switchboards safety ESB Competences: Electrical Switchboard Safety Testing βœ”
IEC/EN 62271 High-voltage switchgear and controlgear - series βœ”
IEC/EN 62271-1 High-voltage switchgear and control gear - Part 1: Common specifications for alternating current switchgear and control gear βœ”
IEC/EN 62271-100 High-voltage switchgear and controlgear - Part 100: Alternating current circuit-breakers βœ”
Mobile Units Electrical Safety eMOB Competences: Electrical LV Installations in Mobile Units Safety βœ”
IEC/EN/HD 60364-7-717 Low-voltage electrical installations: Requirements for special installations or locations – Supplies for Electrical Vehicles βœ”
ISO 6469-3 - Electrically propelled road vehicles Safety specification Part 3: Electrical safety βœ”
Electrical Vehicle Supply Equipment EVSE Competences: Electrical Vehicle Supply Equipment Safety β—‰
IEC/EN 61851 Electric vehicle conductive charging system βœ”
IEC/EN 62752 In-cable control and protection device for mode 2 charging of electric road vehicles (IC-CPD) βœ”
Medical electrical equipment AS/NZS 3551 Management programs for medical devices βœ”
Medical and surgery room installations MEDi Competences: Medical and Surgery Rooms Electrical Installations Safety βœ”
Instrument safety towards the user Directive EMC 89/336/EE on electromagnetic compatibility βœ”
IEC/EN 61010 Safety requirements for electrical equipment for measurement, control, and laboratory use - series βœ”
IEC/EN 61010-2-033 Safety requirements for electrical equipment for measurement, control, and laboratory use - Part 2-033: Particular requirements for hand-held multimeters and other meters for domestic and professional use, capable of measuring mains voltage βœ”
EMC safety IEC/EN 61326 Electrical equipment for measurement, control and laboratory use - EMC requirements - series βœ”
Key βœ” Supported | β—‰ Optional

Metrel A 2214 Ring Continuity Adapter

Main Features Earth Bond / Continuity Ring Test 200 mA (UK installations) βœ”
Additional Features Power Supply Rechargeable Batteries in standard delivery βœ”
Battery Powered βœ”
Test Lead Compensation Test Lead Compensation βœ”
IP protection IP 40 βœ”
Other applications Preventative maintenance Testing ring final circuits βœ”
Standards Applied Building LV Installation BS 7671 IEE Wiring Regulations (18th edition) βœ”
Instrument safety towards the user IEC/EN 61010 Safety requirements for electrical equipment for measurement, control, and laboratory use - series βœ”
EMC safety IEC/EN 61326 Electrical equipment for measurement, control and laboratory use - EMC requirements - series βœ”
IEC/EN 61326-1 Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 1: General requirements βœ”
Document Downloads
Metrel MI 3152XC Multifunction Tester Datasheet Datasheet
Metrel A 2214 Ring Continuity Adapter Datasheet Datasheet
Additional Information
SKU
RINGKIT2
Manufacturer Part Code
RINGKIT2
Country of Origin
Slovenia

Customer Reviews

 
Metrel MI 3152-ES Multifunction Tester & A 2214 Ring Continuity Adaptor
Β£1,683.00
£2,019.60 inc vat
Β£1,683.00
£2,019.60 inc vat