or Call 01642 931 329 to discuss product options
This is the most advanced Megger SVERKER900 test set available, improving upon the basic and standard versions which are also available.
The Expert SVERKER900 is the only model in the series which includes all of the following:
- Main Instrument - with timing tests, manual determination of pick-up and drop-out of relay contact and set, inject and measure functions
- Prefault-Fault Instrument - perform timing tests which require simulation of a prefault state before fault simulation
- CT Magnetisiation Instrument - determine the knee point of voltage of the current transformer
- Ramping Instrument - automatically determine pickup threshold and perform time testing
- Sequencer Instrument - simulate sequences such as auto recloser, motor start or re-striking earth faults
- Impedance Instrument (NEW for expert model) - allows testing of relays directly from impedance plane, where the conversion from the impedance into voltage or current is performed automatically by the SVERKER900
About the SVERKER900
Specifically created for testing protection devices, the Megger SVERKER900 is a powerful, multifunctional relay testing set designed to perform basic, manual three-phase secondary and primary testing.
With the SVERKER900, you'll have absolutely everything you need for commissioning and maintenance of distributed and generator power substations, for testing electromechanical, static and numerical relays and even for specific applications such as plotting current transformer excitation curves, performing current and voltage transformer ratio tests and much, much more.
Megger's SVERKER900 is powered by a simple front HMI interface. Using this, the engineer using the relay tester can manually or use the semi-automatic modes to perform tests with everything from making simple primary injections into a switchgear or more complex secondary relay testing all being possible. It's all controlled via a built-in computer and touchscreen system, giving you easy access to the tests you want in absolutely every application.
The front HMI also doubles up as memory storage; the SVERKER900 is able to store your test results directly in its memory, then can be plugged into a PC via the USB port and information can be ported across in CSV Excel format so you can create reports on your PC.
Megger SVERKER900 Interface Breakdown
The following table outlines exactly what's included on the SVERKER900's front interface.
1 - Binary Inputs (1-4) | The binary inputs are independtly programmable gate circuits that permit simple selection of the desired mode for voltage or contact monitoring operations. Binary input 1 has a selectable threshold voltage |
2 - Extra Timer | With separate start/stop inputs, the timer can be used to measure both external cycles and sequences initiated by the SVERKER900. The measured time appears on the display. Each input can be set to respond to the presence of abscence of voltage (AC/DC) at a contact |
3 - Binary Output | The binary output is used to simulate normally open/normally closed contacts for testing breaker failure schemes, or similar power system operations. In addition it may also be used to switch AC/DC voltages and currents |
4 - Current/Voltage | Current and voltage are measured by the built-in ammeter and voltmeter. Resistance, impedance, phase angle, pwer and power factor can also be measured. Readings appear on the display. These instruments can also be used to take measurements in external circuits |
5 - Current Generators | The current generators can be used separately, in parallel or series. The current generators deliver maximum compliance voltage to the load constantly during the test, and range changing is done automatically, on-the-fly, under load. |
6 - Voltage Generators | The voltage generators can be used separately, in parallel or series |
7 - USB | For external keyboard, mouse, saving test data and for updating internal SW |
8 - Mains Inlet | |
9 - Ground (Earth) Connection | |
10 - On/Off Switch | |
11 - Ethernet Port | For authorised service actions |
12 - Touch Screen | 5.7" full colour LCD |
13 - Control Knob | For setting of current, voltage and other parameter values |
Megger SVERKER900 Three-Phase Relay/Substation Test System Key Features
- Full toolbox for substation 3-phase testing
- Three current and four voltage sources
- Standalone functionality
- Rugged and reliable with integrated carrying handle for use in the field
- Generation 900V and 105A in single-phase mode
- Secondary and primary testing
- Fast response LCD colour touchscreen
What's Included?
- SVERKER900 Test Unit
- Ten Jumpers
- Touch Screen Pen
- Test Cable Set
- Protective Cable
- Cable Set (up to 900V)
- Flight Case with Wheels
Megger SVERKER900 Technical Specifications
For the full list of tech specs, please see the attached datasheet.
Specifications are valid for resistive load, at 170-240 voltage supply and ambient temperature +25°C ±3°C (77°F ±5.4°F) after 30 minutes warmup time and in the frequency range of 10Hz to 70Hz. All hardware data are for full scale values. Specifications are subject to change without notice. |
|
Environment | |
---|---|
Application Field | For use in high-voltage substations and industrial environments |
Operating Temperature | 0 to 50°C (32 to +122°F) |
Storage/Transport Temperature | -40 to +70°C (-40 to +158°F) |
Humidiity | 5 to 95% RH, non-condensing |
Altitude (Operational) | 2000m (6500ft) |
Shock and Vibration | IEC 60068-2-27 |
Vibration | IEC 60068-2-6 |
CE-Marking | |
EMC | IEC61326-1 |
LVD | IEC61010-1: 2010 |
General | |
Mains Input | 100 to 240V AC, 50/60Hz |
Current Consumption | 10A (max) |
Power Consumption | 1800VA (max) |
Instrument Dimensions | 350 x 270 x 220mm (13.8 x 10.6 x 8.7") |
Flight Case with Wheels | 615 x 295 x 500mm (24.2 x 11.6 x 19.7") |
Flight Case | 620 x 295 x 500mm (24.4 x 11.6 x 14.4") |
Weight | 14.9kg (32.8lbs) - instrument only |
29.0kg (64lbs) with accessories and flight case (with wheels, GD-00185) | |
23.9kg (52.7lbs) with accessories and flight case (GD-00182) | |
Display | 5.7" LCD touch screen |
Available Lanugages | English, French, German, Spanish and Swedish |
Measurement Section Binary Inputs 1,2, 3, 4 and EXTERNAL TIMER Start/Stop | |
Number | 6 |
Type | Dry or wet contacts max, 240V AC or 340V DC |
Galvanic Isolation | 35 minutes |
Max Measuring Time | Settable, 0 to 999ms |
BINARY INPUT 1 | Settable, 0 to 999ms |
Timer | |
Range | Inaccuracy |
0 to 50ms | ≤1ms |
50 to 500ms | ≤2ms |
>500ms | ≤1% |
Resolution | 1ms |
Voltmeter | |
Measurement Method | AC true RMS DC mean value |
Insulation | 900V, 1273 peak |
Input Rating | 900V |
Inaccuracy (DC Ranges) | |
0 to 1V | ±0.5% of reading + 3mV |
0 to 10V | ±0.5% of reading + 7mV |
0 to 100V | ±0.5% of reading + 30mV |
0 to 900V | ±0.5% of reading + 300mV |
Inaccuracy (AC Ranges) | |
0 to 1V | ±1% of reading + 5mV |
0 to 10V | ±1% of reading + 10mV |
0 to 100V | ±1% of reading + 50mV |
0 to 900V | ±1% of reading + 300mV |
Resolution | 1mV |
Frequency | |
Range | 10Hz to 600Hz |
Inaccuracy | <0.01% |
Resolution | >10mHz |
Ammeter | |
Measurement Method | AC true RMS DC mean value |
Inaccuracy (DC Ranges) | |
0 to 200mA | ±0.5% of reading + 2mA |
0 to 1.5A | ±0.5% of reading + 3mA |
0 to 10A | ±0.5% of reading + 10mA |
Inaccuracy (AC Ranges) | |
0 to 200mA | ±1% of reading + 2mA |
0 to 1.5A | ±1% of reading + 3mA |
0 to 10A | ±1% of reading + 20mA |
Frequency | |
Range | 10Hz to 600Hz |
Inaccuracy | <0.01% |
Resolution | <10mHz |
Extra Measurements | |
Power Factor | |
Range | 0.01 (cap) to 1 to +0.01 (ind) |
Resolution | <0.01 |
Inaccuracy | <0.04 |
Phase Angle (°) | |
Range | 0 to 360° |
Resolution | <0.1° |
Inaccuracy | <0.8° |
Impedance and Power Measurement | |
AC | Z(Ω), R(Ω),X (Ω), P(W), S(VA), Q(VAR) |
DC | R(Ω), P(W) |
Range | Up to 999kX (X = unit) |
Binary Outputs | |
Insulation | 250V AC |
Current | 1A (max) |
Voltage | 250V AC |
Generation Section | |
Voltage outputs U1, U2, U3 and U4/DC out All voltage sources/generators are galvanically separated from each other and from ground. Floating common return is made by using jumper connectors |
|
Ranges | |
4-Phase AC | 4 x 300V |
4-Channel DC | 4 x 300V |
Power | |
4-Phase AC | 4 x 125VA (max) |
4-Channel DC | 4 x 125W (max) |
Inaccuracy | 0.03% range + 0.05% of reading) |
Distortion (THD + N) | <0.14% typical (0.25% max) |
Resolution | 10mV |
Phase | |
Angle Range | 0 to 360° |
Inaccuracy | <0.5° (at 50-60Hz) |
Resolution | 0.1° |
Frequency | |
Range | 10Hz to 600Hz |
Inaccuracy | <0.03% (45 to 66Hz) |
Resolution | 1mHz |
Reviews
SKU | CR-19094 |
---|---|
Manufacturer Part Code | CR-19094 |
Model Ref | SVERKER900 EXP |