All Megger Products

Megger SVERKER900 Three-Phase Relay & Substation Test System-Basic Kit

SKU
CR-19090
Rating:
0%
(0)
Call For Pricing

We require additional information before you purchase this product

or Call 01642 931 329 to discuss product options

Megger SVERKER900 Three-Phase Relay & Substation Test System - Basic Kit

This is the Megger SVERKER900, the ultimate engineer's toolbox for secondary and primary testing of substations, renewable power generation stations and industrial applications.

Powered by a fast-response, easy-to-use touchscreen for quick and easy configuration of all procedures, the Megger SVERKER900 can be used for a wide variety of tasks including testing protection relays, plotting current transformer excitation curves, polarity (direction) tests, primary injection in switchgear (both three and single phase), wiring checks and much, much more.

The SVERKER900 is equipped with three current and four voltage sources, allowing it to be used in either series of parallel, catering for current to 105A (AC) or 900V (AC) output. All sources can be individually adjusted with respect to their amplitude, phase angle and frequency, while the fourth voltage source can be used to test numerical relays which need a reference voltage simulating the busbar.

SVERKER900 Relay and Substation Test System

For added convenience, the SVERKER900 comes built inside its own carrying case for transportation and protection of the unit when moving from test to test. The lid of the case is also uniquely designed - it houses a selection of jumpers in specific holders as well as a touch screen pen and a quick reference guide for ease of use.

With the SVERKER900, there's no need to use a computer when testing. The tester's unique interface with fully configurable options using the touchscreen, plus integrated datalogging capabilities, make it ideal for both measuring and logging data. When done testing, simply connect the SVERKER900 to PC via USB connection to transfer your files and data in standard CSV format (compatible with Microsoft Excel).

Megger SVERKER900 Interface Breakdown

The following table outlines exactly what's included on the SVERKER900's front interface.

1 - Binary Inputs (1-4) The binary inputs are independtly programmable gate circuits that permit simple selection of the desired mode for voltage or contact monitoring operations. Binary input 1 has a selectable threshold voltage
2 - Extra Timer With separate start/stop inputs, the timer can be used to measure both external cycles and sequences initiated by the SVERKER900. The measured time appears on the display. Each input can be set to respond to the presence of abscence of voltage (AC/DC) at a contact
3 - Binary Output The binary output is used to simulate normally open/normally closed contacts for testing breaker failure schemes, or similar power system operations. In addition it may also be used to switch AC/DC voltages and currents
4 - Current/Voltage Current and voltage are measured by the built-in ammeter and voltmeter. Resistance, impedance, phase angle, pwer and power factor can also be measured. Readings appear on the display. These instruments can also be used to take measurements in external circuits
5 - Current Generators The current generators can be used separately, in parallel or series.
The current generators deliver maximum compliance voltage to the load constantly during the test, and range changing is done automatically, on-the-fly, under load.
6 - Voltage Generators The voltage generators can be used separately, in parallel or series
7 - USB For external keyboard, mouse, saving test data and for updating internal SW
8 - Mains Inlet  
9 - Ground (Earth) Connection  
10 - On/Off Switch  
11 - Ethernet Port For authorised service actions
12 - Touch Screen 5.7" full colour LCD
13 - Control Knob For setting of current, voltage and other parameter values

Megger SVERKER900 Three-Phase Relay/Substation Test System Key Features

  • Full toolbox for substation 3-phase testing
  • Three current and four voltage sources
  • Standalone functionality
  • Rugged and reliable with integrated carrying handle for use in the field
  • Generation 900V and 105A in single-phase mode
  • Secondary and primary testing
  • Fast response LCD colour touchscreen

What's Included?

  • SVERKER900 Test Unit
  • Ten Jumpers
  • Touch Screen Pen
  • Test Cable Set
  • Protective Cable
  • Cable Set (up to 900V)
  • Flight Case with Wheels

Megger SVERKER900 Technical Specifications

For the full list of tech specs, please see the attached datasheet.

Specifications are valid for resistive load, at 170-240 voltage supply and ambient temperature +25°C ±3°C (77°F ±5.4°F) after 30 minutes warmup time and in the frequency range of 10Hz to 70Hz.
All hardware data are for full scale values.
Specifications are subject to change without notice.
Environment
Application Field For use in high-voltage substations and industrial environments
Operating Temperature 0 to 50°C (32 to +122°F)
Storage/Transport Temperature -40 to +70°C (-40 to +158°F)
Humidiity 5 to 95% RH, non-condensing
Altitude (Operational) 2000m (6500ft)
Shock and Vibration IEC 60068-2-27
Vibration IEC 60068-2-6
CE-Marking
EMC IEC61326-1
LVD IEC61010-1: 2010
General
Mains Input 100 to 240V AC, 50/60Hz
Current Consumption 10A (max)
Power Consumption 1800VA (max)
Instrument Dimensions 350 x 270 x 220mm (13.8 x 10.6 x 8.7")
Flight Case with Wheels 615 x 295 x 500mm (24.2 x 11.6 x 19.7")
Flight Case 620 x 295 x 500mm (24.4 x 11.6 x 14.4")
Weight 14.9kg (32.8lbs) - instrument only
29.0kg (64lbs) with accessories and flight case (with wheels, GD-00185)
23.9kg (52.7lbs) with accessories and flight case (GD-00182)
Display 5.7" LCD touch screen
Available Lanugages English, French, German, Spanish and Swedish
Measurement Section
Binary Inputs 1,2, 3, 4 and EXTERNAL TIMER Start/Stop
Number 6
Type Dry or wet contacts max, 240V AC or 340V DC
Galvanic Isolation 35 minutes
Max Measuring Time Settable, 0 to 999ms
BINARY INPUT 1 Settable, 0 to 999ms
Timer  
Range Inaccuracy
0 to 50ms ≤1ms
50 to 500ms ≤2ms
>500ms ≤1%
Resolution 1ms
Voltmeter
Measurement Method AC true RMS
DC mean value
Insulation 900V, 1273 peak
Input Rating 900V
Inaccuracy (DC Ranges)
0 to 1V ±0.5% of reading + 3mV
0 to 10V ±0.5% of reading + 7mV
0 to 100V ±0.5% of reading + 30mV
0 to 900V ±0.5% of reading + 300mV
Inaccuracy (AC Ranges)
0 to 1V ±1% of reading + 5mV
0 to 10V ±1% of reading + 10mV
0 to 100V ±1% of reading + 50mV
0 to 900V ±1% of reading + 300mV
Resolution 1mV
Frequency
Range 10Hz to 600Hz
Inaccuracy <0.01%
Resolution >10mHz
Ammeter  
Measurement Method AC true RMS
DC mean value
Inaccuracy (DC Ranges)
0 to 200mA ±0.5% of reading + 2mA
0 to 1.5A ±0.5% of reading + 3mA
0 to 10A ±0.5% of reading + 10mA
Inaccuracy (AC Ranges)
0 to 200mA ±1% of reading + 2mA
0 to 1.5A ±1% of reading + 3mA
0 to 10A ±1% of reading + 20mA
Frequency
Range 10Hz to 600Hz
Inaccuracy <0.01%
Resolution <10mHz
Extra Measurements
Power Factor   
Range 0.01 (cap) to 1 to +0.01 (ind)
Resolution <0.01
Inaccuracy <0.04
Phase Angle (°)  
Range 0 to 360°
Resolution <0.1°
Inaccuracy <0.8°
Impedance and Power Measurement
AC Z(Ω), R(Ω),X (Ω), P(W), S(VA), Q(VAR)
DC R(Ω), P(W)
Range Up to 999kX (X = unit)
Binary Outputs
Insulation 250V AC
Current 1A (max)
Voltage 250V AC
Generation Section
Voltage outputs U1, U2, U3 and U4/DC out
All voltage sources/generators are galvanically separated from each other and from ground.
Floating common return is made by using jumper connectors
Ranges
4-Phase AC 4 x 300V
4-Channel DC 4 x 300V
Power
4-Phase AC 4 x 125VA (max)
4-Channel DC 4 x 125W (max)
Inaccuracy 0.03% range + 0.05% of reading)
Distortion (THD + N) <0.14% typical (0.25% max)
Resolution 10mV
Phase
Angle Range 0 to 360°
Inaccuracy <0.5° (at 50-60Hz)
Resolution 0.1°
Frequency
Range 10Hz to 600Hz
Inaccuracy <0.03% (45 to 66Hz)
Resolution 1mHz
Megger SVERKER900 Three-Phase Relay Test Set - Datasheet Datasheets Application for Testing Automatic Reclosing Manuals & Guides Testing G59-3 Protection with SVERKER 900 Manuals & Guides Directional EF Protection with LCA 01 Manuals & Guides Testing Protection Functions in Distributed Energy Resources (DER) AN en Manuals & Guides SVERKER 900 Directional Overcurrent Protection Manuals & Guides TG-Testing Self-Powered Relays with SVERKER 900 - CR036201AE V01 - Released Manuals & Guides SVERKER-900 Testing Directional Earth Fault AN en Manuals & Guides

Reviews

Additional Information
SKU CR-19090
Manufacturer Part Code CR-19090
Model Ref SVERKER900 BASIC