Megger SVERKER650 Single Phase Relay Tester

The Megger SVERKER650 is a powerful, compact and simple-to-use relay test set suitable for testing a wide variety of power, voltage and current relays.

Created with years of experience, the SVERKER 650's intuitive interface, powerful functionality and other features combine together to create a comprehensive system for fully testing virtually all types of single phase protection.

Made for use in both high voltage substations and industrial conditions, the SVERKER650 includes a built-in capacitor to provide phase shift when testing directional protective relays and also has built-in resistors to divide voltages as and when needed.

The SVERKER650 is compact and portable enough to easily be transferred from testing point to testing point and is supplied as standard with a rugged carrying case.

Megger SVERKER650 Terminal/Function Breakdown

The following table outlines exactly what each part of the SVERKER650 is capable of. The following image includes reference codes which are also in the table below.


Terminals Unloaded (Mains 230V)  
U1 0 to 10A 85 to 90V AC Settable with T1
U2 0 to 40A 25 to 27V AC Settable with T1
U3 0 to 100A 10.0 to 11.0V AC Settable with T1
U4 0-250V, 3A 250 to 270V AC Settable with T1
U5 0-350V, 2A 350-370V DC Settable with T1
U6  20-220V DC - Settable with R5
  The voltage is stabilised and variable in two steps with the switch S3.
Characteristics at input voltage 220V AC +10%
Ripple (peak to peak) max 4%
Load regulation 3%
Line regulation less than 4%
 
U7 110V, 0.3A 110-125V AC -
F1 Automatic cut-out for mains voltage, 4A
F2 Automatic cut-out, 3A
F3 Automatic cut-out, 0.5A
E1 Green indicator for mains voltage
E2 Yellow signal lamp in the trip circuit
MI Mains Input
MO Mains Output
P1 Electric timer, independent of mains frequency.
Measuring range of 0 to 999.999 seconds.
Accuracy: 0.002% of readout +0, -2ms
P2 Input for stop of timer
P3 Ammeter class 1.5
R Resistors
C1 Capacitactor, 10μF/450V AC for reactive power relays
S1 Main switch
S2 On/off switch for terminals U6 and U7
S3 Selector voltage range terminal U6
S4 Make/break switch for timer
R5 Voltage adjustment terminal U6
W1 Terminal for connection of a resistor on the primary side of the output transformer
W2 Terminal for an external ammeter
W3 Terminal for external start and stop of timer

Megger SVERKER650 Single Phase Relay Tester Key Features

  • Rugged, portable design for use out in the field
  • 0 to 100A output current
  • Suitable for testing many different types of relays including power, voltage and current
  • Easy to understand and operate
  • Ideal for use in HV substations and industrial conditions
  • Optional ACA120 voltage source available for easier testing of directional relays
  • Built-in capacitor provides phase shift
  • Set of resistors for voltage division

What's Included?

  • Megger SVERKER650 Single Phase Relay Tester (230V Mains Voltage)
  • OPTIONAL Test Lead Set (GA-00030)
  • OPTIONAL Transport Case (GD-00010)

Optional Accessories

  • ACA120 Variable Voltage Output Source (0 to 120V AC)

Megger SVERKER650 Technical Specifications

Specifications are valid at nominal input voltage and an ambient temperature of +25°C (77°F). Specifications are subject to change without notice.

Environment
Application Field The instrument is intended for use in high voltage subsations and industrial environments
Operating Temperature 0 to 50°C (32 to 122°F)
Storage Tempewrature -40 to 70°C (-40 to +158°F)
Humidity 5 to 95% RH, non-condensing
CE-Marking
LVD 2006/95/EC
EMC 2004/108/EC
General
Mains Voltage 115/230V AC, 50/60Hz
Power Consumption 1100VA (max)
Protection Thermal cutouts, miniature circuit breakers
Dimensions Instrument: 280 x 178 x 250mm (11 x 7 x 9.8 inches)
Transport Case: 560 x 260 x 360mm (22 x 10.2 x 14.2")
Weight 16kg (35.3lbs)
26kg (57.3lbs) with accessories and transport case
Measurement Section
Current Measurements (Built-In Ammeter)
Ranges 0 to 10A
0 to 100A
Inaccuracy ±3%
Current Measurements (External Ammeter)
Output for External Ammeter Connected to built-in current transformer
Inaccuracy ±0.5%
Timer  
Range 0 to 999.999s
Resolution 1ms
Inaccuracy ±0.02% of displayed value, +2ms
Independent of mains frequency
Outputs
Current Outputs, AC
Range No-Load Voltage (Min) Output Voltage (min) Load/Unload Times On (MAX)/Off (MIN)
0-10A 85V 75V (10A) 2min/30min
0-40A 25V 19V (40A) 20s/15min
0-100A 10V 7.7V (100A) 20s/5min
Voltage Outputs, AC/DC
Range Output Voltage
0-250V AC 220V (2.7A)
110V AC (fixed) 110V (0.3A)
0-350V DC 280V (2A)
20-220V DC (Stab) 200V (0.25A)