The Megger PMM-2 Power Multimeter is a next generation multifunction instrument suitable for testing substations and commissioning electrical gear. Unique software and an integrated microprocessor-based timer ease the testing and commissioning of protective relay systems, including induction unit pickup and timing tests. The internal timer responds to a variety of start and stop gates such as the application of AC or DC voltage and the opening and closing of dry contacts.

The Megger PMM-2 Power Multimeter measures:

  • AC/DC voltage and current
  • Primary and secondary voltage and current
  • Power
  • Reactive power
  • Power factor
  • Phase angle
  • Frequency of single-phase and three-phase electrical systems
  • Simultaneous harmonic measurement (up to the 50th) on all selected voltages or currents

It delivers accurate phase angle measurements at low current which may be displayed as either lagging or leading angles. Furthermore, any voltage or current transformer ratio up to 9999:1 or 9999:5 may be input into the Megger PMM-2 Power Multimeter eliminating the need for result conversions.

Four isolated voltage and current channels allow you to measure up to four voltages and four currents simultaneously. Alternatively, you can measure eight currents at the same time. Moreover, the fourth channels may be used to measure neutral current and a polarising or synchronising voltage.

The Megger PMM-2 Power Multimeter can be used in single-phase mode and three-phase mode. In single-phase mode, the Megger PMM-2 Power Multimeter measures the amplitude and phase angle between any two voltage and current inputs, displaying the results in an enlarged font size for easy reading. In three-phase mode, all measured parameters (voltage, current, phase angle, power, reactive power, power factor, and frequency) are displayed simultaneously on the Megger PMM-2 Power Multimeter’s large, colour, touchscreen TFT LCD with multicoloured graphics. Intuitive navigation ensures the Megger PMM-2 Power Multimeter is easy to use.

Data can be stored in the Megger PMM-2 Power Multimeter’s non-volatile memory. Offering a sampling rate of 28.8 k samples/second and a 64GB memory, the Megger PMM-2 Power Multimeter can store over sixty-minutes worth of data. The Megger PMM-2 Power Multimeter can be programmed to store data automatically, for instance, it may be set to capture motor starting currents, voltages, and power for analysis. You can also specify a date and time for starting and stopping logging.

In addition to measurements, setup screens and reports may be saved to the Megger PMM-2 Power Multimeter’s integrated memory which reduces both testing time and paperwork. The Megger PMM-2 Power Multimeter also includes a built-in report generator, once again improving efficiency.

Finally, the Megger PMM-2 Power Multimeter is housed in a rugged, ergonomic, lightweight plastic case with an automatic built-in charger. The Megger PMM-2 Power Multimeter can be line or battery-operated.

The Megger PMM-2 Power Multimeter is a compact, comprehensive multifunction instrument.

Megger PMM-2 Power Multimeter Key Features

  • Next-generation multifunction instrument suitable for testing substations and commissioning electrical gear
  • Unique software
  • Microprocessor-based timer
  • Eases the testing and commissioning of protective relay systems
  • Internal timer responds to a variety of start and stop gates
  • AC/DC voltage and current
  • Primary and secondary voltage and current
  • Power
  • Reactive power
  • Power factor
  • Phase angle
  • Frequency of single-phase and three-phase electrical systems
  • Simultaneous harmonic measurement (up to the 50th) on all selected voltages or currents
  • Accurate phase angle measurement at low current
  • Enter voltage or current transformer ratios up to 9999:1 or 9999:5 to avoid the need for result conversions
  • Four isolated voltage and current channels
  • Measure up to four voltages and four currents simultaneously
  • Measure eight currents simultaneously
  • Use the fourth channel to measure neutral current and a polarising/ synchronising voltage
  • Single-phase mode
  • Three-phase mode
  • Measure phase-to-phase voltage and single-phase current to check the revenue of meter installations
  • Wide current and voltage operating ranges, including low-level voltage inputs from clamp-on CTs
  • Measurement and display of primary currents using clamp-on CTs
  • Large, colour, touchscreen TFT LCD with multicoloured graphics
  • Intuitive navigation
  • 64GB non-volatile memory
  • Store over sixty minutes worth of data
  • Program the tester to capture data automatically
  • Program specific dates and times for the meter to start and stop data logging
  • Save setup screens and reports
  • Built-in report generator
  • Rugged, ergonomic, lightweight plastic case
  • Automatic built-in charger
  • Supports line and battery operation
  • A compact, comprehensive multifunction instrument

What’s Included?

  • Megger PMM-2 Power Multimeter
  • Power Cord
  • 210cm Ethernet Cable
  • Instruction Manual on a USB Stick
  • Soft Carry Case

Megger PMM-2 Power Multimeter Technical Specifications 

Input power 90 to 253 V AC, 1Ø, 50/60 Hz, 150 VA
Battery Rechargeable Lithium-ION battery with internal automatic charger. Safety features include internal battery overcharging and charge exhaustion protection. Battery energy is limited to 97.2 Watt-hour (to carry on-board a commercial airliner the battery energy must not
exceed 100 Watt-hour). The battery is RoHS compliant.
Operation time ± 4 hours continuous on full charge – actual operation time limited to 97.2 Watt-hour battery.
Voltage 0 - 1000 V (AC/DC)
4 Independent isolated inputs Isolation voltage: 1200 V
Resolution 0.000 V – 99.999 V
100.00 V – 999.99 V
1,000.0 V
Accuracy2
AC/DC Volts Ranges Accuracy
0 - 299.999 V ± 0.05 % of reading ± 40 mV
300 – 1000.00 V ± 0.05 % of reading ± 65 mV
Input impedance 0 – 34.999 V, 100 kΩ
35 V – 1 kV, 5 MΩ
Measured RMS or AVG
Crest Factor 3 or maximum 1450 Vpk
Current
4 Total isolated inputs
3 Independent isolated inputs
0 - 100 A (AC/DC)
Isolation voltage: 300 V
1 Independent isolated input 0 - 32 A (AC/DC)
Isolation voltage: 300 V
Resolution 0.000 mA – 99.999 mA
0.100 A – 9.999 A
10.000 A – 99.999 A and 100.00 A (Channel 1 – 3)
10.000 A – 32.000 A (Channel 4)
Minimum current measurement 2 mA
Burden at 5 A ≤ 0.1 VA
Crest factor 3 or maximum 145 A peak, Channels 1-3, or maximum
46 A peak Channel 4
Accuracy2 channels 1 – 4
AC/DC current:
Ranges
Accuracy
0 – 0.999999 A ± 0.05 % of reading ± 2 mA
1 – 9.99999 A ± 0.05 % of reading ± 10 mA
10 – 32.0000 A ± 0.1 % of reading ±10 mA, Channel 4
32 – 100 A ± 1 % of reading Ch. 1 – 3
CT inputs (low-level inputs) Each current channel can be selected for low level input from clamp on CT’s. CT secondary current and/or CT primary current scaling can be entered and automatically calculated for display
4 Total isolated inputs 0 – 1 V (AC/DC)
Isolation voltage 50 V AC
Resolution 0.000 V - 1.000 V
Accuracy2 ± 0.05 % of reading ± 25 mV ± CT Accuracy
Phase Angle 0 - 360.00° lead or lag or ± 0 - 180.00°, 0.01° resolution
Accuracy2 ± 0.08° input levels above 30 V and 1.0 A (using current as reference), ± 0.5° input levels below 30 V and above 3 V and 0.02 A, ± 2° input levels down to 0.002 A.
Power ± 0 - 100 KW, 0.1% resolution
Accuracy2 ± 0.2% of VA.
Reactive Power ± 0 - 100 KVAR, 0.1% resolution
Accuracy2 ± 0.2% of VA.
Power Factor ± 1.00 PF
Accuracy2 0.01 PF
Frequency
Resolution 10 - 1000 Hz, 0.001 Hz
Accuracy3 ± 4 ppm (0.0004 %) of reading
Harmonics Measures all harmonic content simultaneously of any selected voltage or current, up to the 50th harmonic.
Accuracy2 ± 5% of total RMS ± 10 mA or ± 40 mV
Seconds 0.0000 to 9.9999 – 5 digits
Greater than 10.0000 – 6 digits
Cycles 5 digits or maximum 0.1 cycle
Seconds mode 200 µs or ± 0.005 % of reading, whichever is greater when initiated by a dry contact, a DC potential above 5 V or an AC potential above 115 V AC*.
Cycles mode ± 0.5 cycle when initiated by a dry contact, a DC potential above 5 V or an AC potential above 115 V AC*.
Note  *AC voltage accuracy is worse at lower voltages and is ± 8 ms in worst case (5 V rms applied just following wave-shape peak).
Start/stop inputs 5-300 V (AC or DC) start or stop inputs. AC or DC applied/removed, or dry contact closure or opening.
Voltage applied Timers start or stop when an AC or DC potential (5 to 300 V) is applied.
Voltage removed Timers start or stop when an AC or DC potential (5 to 300 V) is removed.
Input resistance 1000 Ω min.
Data Input/Output
Ethernet There are two Ethernet ports. IN Port – Primary PC
connection Port. OUT Port – For future use.
USB Type A Ports Two ports available. These ports are used to
update the firmware and software in the system.
USB Type B Port This interface requires a Type B “downstream”
connector and is a communication and control port when used with a PC and Megger software.
Display Screen The display provides high resolution and features a wide viewing angle technology and a large screen with high luminance.
Dimensions 8.5 H X 5.3 W inches (215.9 H X 134.6 W mm),
10.1 inches Diagonal (256.5 mm)
Display 262k Colors, backlit, 800:1 contrast ratio, projected capacitive multi-touch screen, 700 nits panel brightness, 1280 x 800 resolution
Languages English, French, Spanish and German
Unit dimensions 13.5 W x 9 H x 6 D inches - 342.9 W x 228.6 H 152.4 D mm
Weight 13.4 lb. (6.0 kg)
Operating temperature -15° to 55° C (5° to 131° F)
Storage temperature -30° to 75° C (-22° to 167° F)
Ingress protection IP 20
Conformance standards
Safety EN 61010-1, overvoltage category 600V Cat IV, 1000 V Cat III
Shock EN/IEC 60068-2-27
Vibration EN/IEC 60068-2-6
Transit drop ISTA 1A
Free fall EN/IEC 60068-2-32
Drop/topple EN/IEC 60068-2-31
Electromagnetic compatibility Emissions EN 61326-2-1, EN 61000-3-2/3, FCC Subpart B of Part 15 Class A
Immunity EN 61000-4-2/3/4/5/6/8/11
Notes  1 Megger reserves the right to change product specifications at any time
2 Accuracies specified within 23° ± 5° C (73° ± 9° F) in the frequency range of 45 to 65 Hz, and after warm-up of 20 min
3 Accuracies specified within 23° ± 5° C (73° ± 9° F), and after warm-up of 20 min.