Megger's MIT2500 is an industrial-grade handheld high voltage insulation tester suitable for testing insulation resistance up to 200GΩ.
The MIT2500 includes fixed voltage ranges of 50V, 100V, 250V, 500V, 1000V (1kV) and 2500V (2.5kV) and also includes a variable range which allows the user to 'dial in' a variable voltage between the full range of 50 to 2500V. A voltage feedback control is used to maintain the output test voltage to within 2% of the selected range, even when tests are currently ongoing.
This high voltage insulation tester is highly recommended for use in electrical and industrial applications such as single and three phase rotating machnery, single and multi-core cable testing or for the testing of motors. It's also ideally suited for any CAT IV 600V application.
This model is an upgraded, newer version of Megger's older insulation testers. It's packed with new, improved features, including:
The Megger MIT2500 is a datalogging insulation resistance tester - it gives you the ability to store your readings in built-in memory storage, ready for further analysis.
Files are stored in Excel format for easy transfer to PC with Bluetooth wireless connection to make transferring results as simple and seamless as possible.
There are a number of accessories for the Megger MIT2500 Industrial/ Utility High Voltage Insulation Tester. For further information regarding the items listed below, please contact our sales team.
Our SKU | Megger's Part Number | Product |
MEGITA1 | 1002-001B | Test lead Set - Comprising Two Unfused Leads (Red/Black) with right angle plugs, Long & Short prods & croc clips (Boxed) |
1000-562 | 1000-562 | Test Lead Replacement Probe Cap [Clear] Bag of 20 |
MEGRCDA4 | 1002-015B | Fused Test Lead Set Red/Black Red FF500mA 50kA (Boxed) |
1002-491 | 1002-491B | Probe & Clip Set - Insulation Testers |
SP4F | 1007-156 | SP4F Remote Switched Probe |
6121-561 | 6121-561 | Fuse Set 5x500mA(F) 600V |
1007-464 | 1007-464 | Battery Charger Kit MIT400/2 |
MEGLOA20 | 1004-183 | 12V DC Car Battery Charger 2.5mm PIN |
1002-774 | 1007-157 | Remote Switched probe SP5 CAT IV 600 (Boxed) |
1002-735 | 1002-735 | Battery NiMH (X6) |
Please note that the accessories listed above and the attached datasheets are subject to change. Both were correct at the time of publication. |
All quoted accuracies are at +20°C.
Insulation | |
---|---|
Insulation Accuracy | 50 Volts: 10 GΩ ± 2% ± 2 digits ± 4.0% per GΩ 100 Volts: 20 GΩ ± 2% ± 2 digits ± 2.0% per GΩ 250 Volts: 50 GΩ ± 2% ± 2 digits ± 0.8% per GΩ 500 Volts: 100 GΩ ± 2% ± 2 digits ± 0.4% per GΩ 1000 Volts: 200 GΩ ± 2% ± 2 digits ± 0.2% per GΩ 2500 Volts: 200 GΩ ± 2% ± 2 digits ± 0.2% per GΩ Service Error: BS EN 61557-2 (2007). 50V: ± 2.0% ± 2d, 100kΩ - 900kΩ ± 10.5% 100V: ± 2.0% ± 2d, 100kΩ - 900kΩ ± 10.3% 250V: ± 2.0% ± 2d, 100kΩ - 900kΩ ± 10.3% 500V: ± 2.0% ± 2d, 100kΩ - 900kΩ ± 10.3% 1000V: ± 2.0% ± 2d, 100kΩ - 900kΩ ± 11.5% |
Guard Terminal Performance | <5% erros on 500kΩ parallel circuit resistance with 100MΩ load |
Display Range | Analogue: 1GΩ full scale |
Short Circuit/Charge Current | 2mA +0 to -50% t EN 61557-2 (2007) (except 2500V) |
Terminal Voltage Accuracy | -0 +2% ±2V |
Test Current | 1mA at minimum pass values of insulation to a maximum of 2mA max |
Operation | EN61557: 0.10MΩ to 1.0GΩ |
Leakage Current Display | 10% ±3 digits |
Voltage | ±3% ±2 digits ±0.5% of rated voltage |
Timer Control | Countdown timer 60 seconds (adjustable to 10 minutes) |
Note | Above specs only apply when high quality silicone leads are used |
Continuity | |
Continuity Measurement | 0.01Ω to 1MΩ (0 to 1000kΩ on analogue scale) |
Continuity Accuracy | ± 3% ± 2 digits (0 to 100 Ω ) ± 5% ± 2 digits (100 Ω - 500 k Ω) Service Error: BS EN 61557-4 (2007) - ± 2.0%, 0.1Ω - 2Ω ± 6.8% |
Open Circuit Voltage | 5V ±1V |
Test Current | 200mA (-0mA to +20mA) (0.01Ω to 4Ω) |
Polarity | Single polarity (default) / dual polarity (configurable on setup) |
Lead Resistance | Null Up to 10Ω |
Voltage | |
Voltage Range | DC: 0 to 600V AC: 10mV to 600V TRMS sinusoidal (15Hz to 400HZ) Unspecified: 0 to 10mV (15 to 400Hz) |
Voltage Range Accuracy | DC: ±2% ±2 digits AC: ±2% ±2 digits Service Errors: BS EN 61557-1 (2007) - ±2.0% ±2d. 0V to 300V AC/DC ±5.1% |
Waveform | Non-sinusoidal: ± 3% ± 2 digits >100 mV to 600 V TRMS ± 8% ± 2 digits 10 mV to 100 mV TRMS |
Frequency | |
Measurement Range | 15 to 400Hz |
Accuracy | ±0.5% ± 1 digit |
Capacitance | |
Range | 0.1nF to 10μF |
Accuracy | ±5.0% ±2 digits (1nf to 10μF) |
General Specifications | |
Storage Capacity | >1000 test results |
Data Download | Bluetooth wireless Bluetooth class II |
Range | Up to 10m |
Power Supply | 6 x 1.5V cells type IEC LR6 (AA, MN1500, HP7, AM3 R6HP) alkaline 6 x 1.2 NiMH rechargeable cells may be used |
Battery Life | 3000 insulation tests with duty cycle of 5 sec ON/55 sec OFF @ 1000V into 1MΩ Charger (optional) 12-15V DC (accessory interface) |
Dimensions | 228 x 108 x 63mm |
Weight | 815g |
Fuse | Use only 2 x 500mA (FF) 1000V 32 x 6mm ceramic fuse of high breaking capacity HBC 30kA minimu, Glass fuses MUST NOT BE FITTED |
Safety Protection | Meets EN 61010-1 (1995) to 600V phase to earth, Category IV. Refer to safety warnings supplied |
EMC | In accordance with IEC 61326 including amendment No 1 |
Temperature Coefficient | <0,1% per °C up to 1 GΩ <0,1% per °C per GΩ above 1 GΩ |
Operating Temperature Range | -10 to +55°C |
Storage Temperature Range | -25 to +70°C |
Humidity | 90% RH at 40°C max |
Calibration Temperature | +20°C |
Maximum Alititude | 2000m |
IP Rating | IP54 |