Megger MFT-X1 EVSE Test Kit
Suitable for testing single and three-phase domestic, commercial, and industrial electrical installations as well as checking the functionality and safety of single- and three-phase electric vehicle charge points, the Megger MFT-X1 EVSE Test Kit includes:
- Megger MFT-X1 Multifunction Tester with Accessories
- Megger EVCA210-UK Electric Vehicle Charge-Point Adapter with Accessories
Megger MFT-X1 Multifunction Tester Overview
Carry out detailed fault diagnostics; complete all commissioning and routine maintenance; and meet reporting/certification requirements for single- and three-phase domestic, commercial, and industrial electrical installations. This multifunction installation tester supports a vast range of electrical tests including true loop with a patented confidence meter; high-resolution loop impedance; current; RCD; and EV charge point. Data and relevant test information are indicated on the 480 x 272px, colour, TFT bonded display that changes colour depending on the test selected, making this MFT easy to use in dark or dim environments. Hotkeys and control dials ensure tests and functions are easily accessible, even when wearing protective gloves. The MFT-X1 operating system can be updated using a microSD card, ensuring it is future-proof. Finally, the Megger MFT-X1 Multifunction Tester is compatible with Megger’s CertSuite™ Software Platform.
For more information regarding the Megger MFT-X1 Multifunction Tester, please follow this link.
Megger EVCA210-UK Electric Vehicle Charge-Point Adapter Overview
The Megger EVCA210-UK Electric Vehicle Charge-Point Adapter can be used with the Megger MFT-X1 Multifunction Tester to verify the safety and functionality of single- and three-phase electric vehicle charge points according to IEC/EN 61851-1 and IEC/HD 60364-7-722. It contains a mains socket and 4mm ports for connecting to compatible Megger MFTs and a CP signal terminal enabling use with Megger oscilloscopes. Additionally, the Megger EVCA210-UK Electric Vehicle Charge-Point Adapter is supplied with a type 2 connector for testing charging points with panel-mounted sockets or a fixed cable with a vehicle connector; and a type 1 connector for checking charging points with a fixed type 1 cable connector. This compact and simple-to-use EV charging point tester simulates the connection of an electric vehicle to the charge point. Using the rotary switch, it can be set to either Proximity Pilot (PP) or Control Pilot (CP) state. Dedicated function buttons allow you to simulate CP Errors “E” or PE Errors (Earth Fault) and perform a manual PE Pre-Test.
To find out more about the Megger EVCA210-UK Electric Vehicle Charge-Point Adapter, please click here.
Videos
Overview
Introduction
What Accessories Come with the Megger MFT-X1 EVSE Kit?
Megger MFT-X1 Multifunction Tester
- SP5 Switched Test Probe
- Red Test Lead, Probes, Clips, and Grabbers
- Blue Test Lead, Probe, Clips, and Grabbers
- Li-Ion Battery 4400 mAh
- Li-Ion Battery Charger
- SIA 10 Mains Socket Interface Adapter (UK)
- Neck Strap
- Multipurpose Hard Base Carry Case
- Quick Start Guide for MFT-X1
- Calibration Certificate (from Megger, matches the unit’s verification date)
Megger EVCA210-UK Electric Vehicle Charge-Point Adapter
- Type 1 Charging Plug
- Type 2 Charging Plug
- Soft Carry Case
- Instruction Manual for EVCA210-UK
Megger MFT-X1 Multifunction Tester Techincal Specifications
Voltage Measurement | |
Voltage range | 0.001 V to 2 V (mV range) 2 V to 600 V (V range), 1000 V DC (on-CAT rated circuits) |
Voltage type | Trms, AC, DC |
Phase sequence | Automatic phase sequence testing on detection of valid three phase supplies |
Current Measurement (non-contact) | |
AC Trms | Using optional accessories: MCC1010 current clamp |
Measurement Range | MCC1010: 1 mA to 300 A |
Continuity/Resistance | |
Measurement range Digital display | 0.01 Ω to 999 kΩ Auto-ranging |
Measurement Range Analogue arc | 0 Ω to 1 MΩ log scale |
Test voltage | 4 V DC to 5 V DC |
Test current (Nominal) | >200 mA 0 Ω >< 2 Ω 10 mA Auto reduction on high resistance (actual current reported in display) |
Test polarities | Forward polarity |
Buzzer resistance range | > 0.01 Ω < 2 kΩ |
Buzzer threshold | 0.3, 0.5, 1, 2, 3, 4, 5, 10, 20, 30, 40, 50, 100, 200 Ω |
Insulation Testing | |
Measurement range Digital display | 0.001 MΩ to 999 MΩ Auto-ranging |
Measurement range Analogue arc | 0.001 MΩ to >1000 MΩ log scale |
Insulation test voltages | 50 V DC to 1000 V DC + Variable 50 V to 999 V |
Test current | 1 mA to 2 mA |
Stabilised output voltage | Output test voltage stabilised to -0% +2% +2 V |
Loop Impedance Testing | |
2 Wire – all modes | |
Test types | Mode 1: Non-Trip |
Mode 2: High current | |
Mode 3: High resolution | |
Resolution | Non-Trip: 0.01 Ω |
High current: 0.01 Ω | |
High resolution: 0.001 Ω | |
Voltage range | Non-trip: 48 V AC to 280 V AC |
High current: 48 V AC to 550V AC | |
High resolution: 48 V AC to 550 V AC | |
Frequency range | 45 Hz to 65 Hz (all modes) |
Phases | Non-trip: Single phase |
High current: Three phase | |
High resolution: Three phase | |
3 wire - non-trip | |
Test types | RCD (non-trip) RCD EV (non-trip on 6mA EV RDCs) |
Resolution | 0.01 Ω |
Voltage range | 48 V AC to 280 V |
Frequency range | 45 Hz to 65 Hz |
Phases | Single phase |
Volt Drop | |
Volt drop calculation | Requires Zref (Ze) and circuit current (I-vdrop) |
Accuracy | Dependent on loop impedance accuracy |
RCD Testing | |
RCD types supported | Type AC, A, B, AC(S), A(S), B(S) |
Auto RCD sequence | 1/2x I∆n, 1x I∆n, 2x I∆n, 5x I∆n, Ramp, 0º/180º (customer configurable) |
Ramp testing | 10 mA to 1000 mA |
RDC testing | 6 mA RDC |
Fault (Touch) voltage | 0 V to 253 V |
Earth Testing | |
2 wire | 2 wire earth resistance test |
Megger EVCA210-UK Electric Vehicle Charge-Point Adapter Technical Specifications
Input voltage | Up to 250 V (single phase system) / up to 430 V (three phase system) |
Input Frequency | 50/60 Hz |
PE Pre-Test | Yes - Push button |
CP Error “E” simulation | Push button |
PP Simulation | NC, 13 A, 20 A, 32 A, 63 A |
CP States | A, B, C, D |
CP Error “E” | Yes |
PE Error (Earth fault) | Yes |
Measuring Ports L1, L2, L3, N and PE | Max. 250/430 V, CAT II 300 V, max. 10 A |
Mains socket | Max. 250 V, CAT II 300 V max. 10 A, |
Note: Do not load mains socket simultaneously with measuring ports! |
|
CP Signal Test Ports | Approx. +/-12 V, CAT 0 (under normal condition) |
In case of wrong wiring or error of the charging station these terminals |
|
Measurement category | CAT II 300 V |
Altitude above sea level. | 2000 m max |
Weight | Approx: 780g |
IP-rating | IP54 |
CE directive | Low Voltage Directive LVD 2014/35/EU |
Safety | IEC/EN 61010-1:2010 |
IEC/EN 61010-2-030:2010 | |
Working temperature range | 0 ... +40 °C |
Storage temperature range | -10 ... +50 °C |
Reference humidity range | 10 ... 60% relative humidity w/o condensation |
Working humidity range | 10 ... 85% relative humidity w/o condensation |
Reviews
SKU | MFT-X1EVCA |
---|---|
Manufacturer Part Code | MFT-X1EVCA |
Country of Origin | United Kingdom |