The Megger LRCD220 Single and 3 phase loop/RCD tester is used to diagnose faults with RCDs and to test crucial system circuits.

The Megger LRCD220 can be used flexibly on a variety of different systems. It provides safe 3-phase non trip loop testing and 1/2I, I and 5iI RCD testing on both selective and standard DC RCDs. This means that this tester is perfectly suited for those domestic installers who are seeking to test to UK Part P standards and requirements.

In addition, the Megger LRCD220 also offers the flexibility of 110V loop testing and 2-wire fast testing and the ability to perform phase-to-phase and phase-to-earth measurements.

The Megger LRCD220 tester is built to be entirely practical, with a robust protective rubber armoured case giving it ample protection; it is also weatherproof and has a protective front cover. It can test from 10mA up to 1000mA in complete safety and comes with a three-year warranty, but most of all, for installers and technicians, the tester is quick, simple and effective when in use.

Megger LRCD220 RCD Tester Key Features

  • Non trip loop testing
  • PFC and single phase function
  • High current loop testing
  • 3 phase safe
  • Built-in voltmeter
  • 1.2 x I, 1 x I test and 5 x I testing
  • Auto RCD testing
  • Touch/contact voltage display
  • 10, 30, 100, 300, 500mA ranges
  • 1000mA range
  • Compatible with AC, AC selective, DC and DC selective RCDs
  • Selectable phase
  • Ramp test
  • Frequency testing function
  • Phase rotation calculations
  • Backlight
  • IP54

What's Included?

  • Megger LRCD220 RCD Tester
  • Red/Black/Green 3 Wire Lead Set
  • AS/NZS 3112 Mains Plug Test lead

Accessories

There are a number of accessories available for the Megger LRCD220 RCD Tester. For further information please contact our sales team. 

Our SKU Megger Part Number Product
MEGRCDA1 6231-601 UK Mains Plug Test Leadset 3-pin 1 wire (BS1363 plug)
MEGLTA2 1001-883 Test lead set 3-wire Red/Black/Green with prods/clips (exposed tip)  
1001-976 1003-132B Test Lead Set Red/Green Unfused (Boxed)  
1000-562 1000-562 Test Lead Replacement Probe Cap [Clear] Bag of 20  
6220-810 1004-323B SIA10 Socket Interface Adaptor UK to 3 Leads x 4mm (Boxed)
1005-469 1005-469 SIA10 Socket Interface Adaptor LTW 
1007-003 1007-003 Blow Moulded Case Catch - Pack of 10 
MEGSW1 1000-631 Powersuite Lite - 17th Edition and PAT Certification Software
Please note that the accessories listed above and the attached datasheets are subject to change. Both were correct at the time of publication. 

Megger LRCD210/LRCD220 Technical Specifications

Voltage Measurements 0 V - 500 V
Voltage Accuracy ±2% ±2 digits
Frequency Measurement Range 25Hz to 450Hz
Frequency Accuracy 25.0Hz to 199.9Hz ±0.1Hz
200Hz to 450Hz ±1Hz
Phase Rotation Indicator (LRCD220 only) Three wire identification of phase rotation.
Frequency 45Hz to 65Hz
Loop Testing Loop ranges (to EN 61557-3)
No-Trip Loop Test (3 Wire, Line To Earth) LRCD200/210 200V - 280 V 45Hz to 65Hz
LRCD220 100V - 280 V 45Hz to 65Hz
Nominal Test Current 15 mA
Loop Accuracy 0.01 ½ - 9.99 ½ (±5% ±0.03 ½)
10.0 ½ - 99.9 ½ (±5% ±0.5 ½)
100 ½ - 999 ½ (±5% ±5 ½)
1.00 k½ - 2.00 k½ (±5% ±30 ½)
Hi Current Line/Earth Loop Test (2 Wire, LRCD220 Only) Yes
Supply 100 V - 480 V
Nominal Test Current 15 mA to 2.4 A
Loop Accuracy 0.01½ - 9.99 ½ (±5% ±0.03 ½)
10.0½ - 99.9 ½ (±5% ±0.5 ½)
100½ - 999 ½ (±5% ±5 ½)
1.0 k½ - 2.00 k½ (±5% ±30 ½)
Line/Line (LRCD220 Only) Supply 100 V - 480 V 45Hz to 65Hz
Prospective Fault Current (PSCC) Prospective fault current = Nominal supply voltage/Loop
resistance
Accuracy is derived from loop test
1 A - 199 A 1 A resolution
0.20 kA - 1.99 kA 10 A resolution
2.0 kA - 19.9 kA 100 A resolution
RCD Testing RCD Test Ranges (to EN61557-6)
LRCD200/210 10mA, 30mA,100mA, 300mA, 500mA
LRCD220 10mA, 30mA,100mA, 300mA, 500mA, 1000mA
Supply Voltage LRCD200/210 = 200 V - 280 V 45Hz to 65Hz
LRCD220 = 100 V - 280 V 45Hz to 65Hz