This version of the Megger EZ-THUMP-12 comes with a 15ft test lead. An alternative version with a 50ft test lead is also available.
This advanced tester accurately determines fault locations along with power cables, ensuring that corrective action can be taken quickly in the right location.
To make testing easier, the EZ-THUMP-12 includes both beginner and expert modes which will guide users through the process of testing with this instrument. It can test DC voltage up to a high threshold of 12kV and includes a built-in TDR with range of up to 7.6km (25000 feet).
Call 01642 931 329 or complete the form:
Testing | |
Output | 0 - 4kV, 35mA DC (EZ-THUMP4) 0-12kV, 12mA DC (EZ-THUMP12) |
Prelocation | |
TDR | Range: 25000 ft (7.6km) Sampling Rate: 100MHz Resolution: 2.5ft @ 250 ft/fs 0.8m @ 80m / fs |
Arc Reflection | 0 - 4kV or 0 - 12kV (model dependent) |
Pinpoint Fault Location | |
Surge | 0 - 4kV @ 500J (EZT4) 0 - 12kV @ 500J (EZT12) |
Impulse Sequence | 10 seconds Single shot |
Display | |
Type | 5.7" (14.48cm) transflective TFT Colour LCD - 640 x 480 pixels |
Memory | |
Trace Number | 1000 |
Interface | |
Port Type | USB |
Cables/Terminations | |
Types | 15ft (4.6m) HV flexible shielded cable with MC connector and hotline clamp HV return with hotline clamp 15ft (4.6m) ground/earth cable with hotline clamp 6ft (1.8m) mains supply lead set (US/SCHUKO/UK) |
Supply | |
Battery | Internal 24V NiMH battery 5AH approx 30 mins or surge/thumping approx 3 hours recharge time 100-240V AC - 24V DC charger with connection lead set (US/SCHUKO/UK) |
AC Line | 100 - 230V AC ± 50/60Hz |
Safety | |
Functions | Emergency stop Key switch interlock Auto time out |
Environmental | |
Operating Temperature | -4 to 122°F (-20 to +50°C) |
Storage Temperature | -12 to 160°F (-25 to +70°C) |
Ingress Protection | |
Rating | IP54 |
Weight/Dimensions | |
Weight | 71lbs (32kgs) |
Dimensions | 14 x 11 x 21" (35.5 x 28 x 53.3cm) |