Free Beanie Hat. Spend £250+ (ex VAT) View
All Megger Products

Megger EGIL200 Circuit Breaker Analyser - Configurable Model

SKU
EGIL200
Rating:
0%
(0)
Call For Pricing

We require additional information before you purchase this product

or Call 01642 931 329 to discuss product options

Megger EGIL200 Circuit Breaker Analyser
Description

The Megger EGIL200 Circuit Breaker Analyser is a mid-range tester designed for use with medium- to high-voltage circuit breakers. It delivers accurate standard measurements, meeting the requirements of international regulations.

The Megger EGIL200 Circuit Breaker Analyser is an entirely configurable instrument that can be adapted to meet your requirements. The image below from Megger's datasheet explains how to build your custom model and highlights the options available.

Easy-to-Use & Intuitive

Efficiency and ease of use are at the forefront of the Megger EGIL200 Circuit Breaker Analyser’s design; it has been optimised to ensure minimum user input is required from start-up to documentation. For instance, the test setup is kept to a minimum so you can gather measurements quickly, while one-click reporting to PDF or printing (depending on your chosen configuration) makes documenting measurements simple and fast.

Furthermore, the Megger EGIL200 Circuit Breaker Analyser only features one hook-up to streamline connection to test objects. Other practical features include:

  • Dedicated control output for coil 2
  • Multifunctional control channels for managing control pulses and measuring station voltages and coil currents via a single connection
  • Galvanically insulated and polarity independent auxiliary contact timing channels which are automatically adapted for dry and wet contacts

Standard Measurements to International Requirements

The Megger EGIL200 Circuit Breaker Analyser can perform all the following measurements and operations to international IEC 62271 and IEEE C37 standards:

  • Timing of main and PIR contacts
  • Coil current analysis of close, open 1 and 2 coils
  • Station voltage measurements
  • Motion measurements
  • Motor current measurements
  • Minimum pickup voltage test for close, open 1, and open 2

Patented Active Interference Suppression technology guarantees accurate pre-insertion contact timing and resistance value measurement.

Ideal for Challenging Environments

Both the Megger EGIL200 Circuit Breaker Analyser and any supplied accessories (these vary depending on your chosen configuration) have been designed for use under demanding field conditions. For example, the Megger EGIL200 Circuit Breaker Analyser is housed in a rugged, IP67-rated case.

The Megger EGIL200 Circuit Breaker Analyser is a rugged, reliable, precise medium- and high-voltage circuit breaker analyser.

Megger EGIL200 Circuit Breaker Analyser Key Features

  • A mid-range circuit breaker analyser designed for use with medium- to high-voltage circuit breakers
  • Completely configurable
  • Efficient and easy to use, requiring minimum user input
  • Test setup is kept to a minimum
  • One-click reporting to PDF or printing (depending on your chosen configuration)
  • One hook-up to streamline connection to test objects
  • Dedicated control output for coil 2
  • Multifunctional control channels for managing control pulses and measuring station voltages and coil currents via a single connection
  • Galvanically insulated and polarity independent auxiliary contact timing channels which are automatically adapted for dry and wet contacts
  • Standard measurements to international IEC 62271 and IEEE C37 regulations
  • Timing of main and PIR contacts
  • Coil current analysis of close, open 1 and 2 coils
  • Station voltage measurements
  • Motion measurements
  • Motor current measurements
  • Minimum pickup voltage test for close, open 1, and open 2
  • Patented Active Interference Suppression technology
  • Designed for use in demanding field environments
  • Rugged, IP67-rated case
  • A rugged, reliable, precise medium- and high-voltage circuit breaker analyser

What’s Included?

  • Your Choice of Megger EGIL200 Circuit Breaker Analyser and Accessories

Benefits Key

1 CONTROL Breaker control (close, open 1, and open 2) Station voltage and coil current measurement
2 PARKING SPACE For safe disconnection of coil circuits
3 TIMING AUX 3 channels for auxiliary contact timing
4 DIGITAL 3 digital inputs for incremental motion transducers
5 1-3 BNC INPUTS 1-3 BNC inputs dedicated for current clamps
6 MULTI-PURPOSE CHANNELS 1-3 multi-purpose analogue channels
7 TIMING M/R, DRM/VDS Timing of main and resistor contacts, DRM, SRM, and VDS-timing on 1 break per phase
(Only EGIL211, EGIL213)
8 TIMING M/R Timing of main and resistor contacts on up to 4 breaks per phase
(Only EGIL221, EGIL223, EGIL241, EGIL243)
9 DCM DualGround™ AND DRM For future use Input for DualGround™ timing (opt. accessory) & DRM control output (opt. accessory)
10 USB AND ETHERNET PORT 3 x USB A, 1 x USB B and 1 x RJ45
11 LCD SCREEN 7” high visibility touchscreen
12 OPERATE / MEASURE ROTARY SWITCH -
13 ICONOGRAPHY Contrast rich iconography for the best visibility and understanding
14 USER INTERFACE Workflow-based (Nameplate, test settings, connections, results, report)
15 PRINTER Optional 4” thermal printer
16 COLOUR CODED CONNECTORS AND LEADS For easy verification of connections
Megger EGIL200 Circuit Breaker Analyser numbered benefits image.
Tech Specs
Environment
Application Field For use in medium and high voltage sub-stations and industrial environments
Operating Temperature -20 °C to +55 °C (-4 °F to +131 °F)
Storage & Transport Temperature -30 °C to +70 °C (-40 °F to +158 °F)
Humidity 5 % - 95 % RH, non-condensing
Altitude Operating Up to 2000 m (6562 ft) max. 240 V AC / 250 V DC on mains, max. 250 V AC / 300 V DC on CONTROL and TIMING AUX inputs
Between 2000 m (6562 ft) and 5000 m (16404 ft) max. 150 V AC / DC on mains, CONTROL and TIMING AUX inputs
CE-Marking
LVD 2014/35/EU
EMC 2014/30/EU
RoHS 2011/65/EU
General
Mains Input (Nominal) 100 - 240 V AC
50 / 60 Hz
110 - 250 V DC
Power Consumption 200 VA (max.)
Dimensions 474 x 415 x 214 mm (18.7” 16.3” 8.4)
Weight 12 kg (26.5 lbs)
IP-rating (IEC 60529) Closed Case IP67
Open Case IP20
Display 7" (17.8 cm) LCD, Capacitive touchscreen
Available Languages English, French, German, Spanish and Swedish
Communication Interfaces
Image of a USB. 3 USB A, 1 USB B for connection to external PC
Image of an RJ45. RJ45 for connection to external PC
Keyboard On-screen and optional USB keyboard
External Outputs
Trig Output for SDRM20X Output Voltage 12 V DC ±10 %
Short Circuit Protection PTC 250 mA
Switching Current <250 mA, resistive load
Control Section
General Control Pulse Outputs Close, open 1, and open 2 (Galvanically insulated from earth and each other)
Time Base Inaccuracy ±0.01 % of reading ±1 sample interval
Max. Sample Rate 40 kHz
Measurement Time 36 s at 10 kHz sample rate
Non-Bouncing Switch Max. Current 20 A AC / DC, pulse ≤ 20 ms
Max. Continuous Current 5 A
Duration User configurable in steps of 1 ms
Delay User configurable in steps of 1 ms
Current Measurement Measurement Range ±20 A
Resolution 16 bits
Inaccuracy ±2 % of reading ±0.1 % of range
Voltage Measurement Max. Voltage 250 V AC, ±300 V DC
Measurement Range ± 400V
Resolution 16 bit
Inaccuracy ±1 % of reading ±0.1 % of range
Timing M/R Section
General No. of Channels 3,6 or 12 selectable at ordering
Time Base Inaccuracy ±0.01 % of reading ±1 sample interval
Min. Resolution 0.05 ms
Max. Sample Rate 40 kHz
Measurement Time 36 s at 10 kHz sample rate
Timing of Main and Resistor Contacts Open Circuit Voltage Toggling ±12 V ±10 %
Short Circuit Current 22 mA ±10 %
50/60 Hz Interference Suppression Active Interference Suppression, Megger patent
Transient Disturbance Suppression Smart digital filter
Status Threshold - User Configurable Thresholds Main Closed < 10 Ω < Open (Factory default)
Main and Resistor Main < 10 Ω < PIR < 10 kΩ < Open (Factory default)
PIR Resistance Measurement Supported PIR Types Linear PIR
Measurement Range 10 Ω - 10 kΩ
Inaccuracy ±5 % of reading ±0.1 % of range*
Voltage Measurement (Only TIMING M/R, DRM/VDS Inputs) Measurement Ranges ±50 V and ±2.5 V
Resolution 16 bits
Inaccuracy ±1 % of reading ±0.1 % of range
Analogue Section
General No. of Channels 1 or 3 isolated channels
Time Base Inaccuracy ±0.01 % of reading ±1 sample interval
Max. Sample Rate 40 kHz
Measurement Time 36 s at 10 kHz sample rate
Transducer Resistance 500 Ω - 5 kΩ
Output Voltage 10 V DC ±5 %
Max. Output Current 30 mA
Voltage Measurement Max. Voltage ±10 V peak
Measurement Ranges ±1 V and ±10 V
Resolution 16 bits
Inaccuracy 1 V Range ±0.1 % of reading ±0.1 % of range
10 V Range ±1 % of reading ±0.1 % of range
External Current Measurement Max. Input ±1 V peak
Scaling Selectable in Software
Digital Section
General No. of Channels 3
Supported Types Incremental transducers, RS422
Time Base Inaccuracy ±0.01 % of reading ±1 sample interval
Max. Sample Rate 40 kHz
Measurement Time 36 s at 10 kHz sample rate
Output Voltage 12 V DC ±5 %
Max. Output Current 300 mA
Digital Input Range ±32000 pulses
Resolution 1 pulse
Inaccuracy ±1 pulse
Timing Aux Section
General No. of Channels 3 isolated channels
Time Base Inaccuracy ±0.01 % of reading ±1 sample interval
Max. Sample Rate 40 kHz
Measurement Time 36 s at 10 kHz sample rate
Max. Voltage 250 V AC, ±300 V DC
Contact Mode Open Circuit Voltage 24 V DC ± 5 %
Short Circuit Current 10 mA DC ±5%
User Configurable Status Threshold Open < -10 V < Closed < 10 V < Open (Factory default)
Printer (optional) Type Thermal printer
Paper Width 112 mm, 114 mm (4.41", 4.48")
Operating Temperature 0 °C to +60 °C (32 °F to +140 °F)
Storage & Transport -20 °C to +70 °C (-4 °F to +158 °F)
Specifications are valid after 30 minutes warm-up time
System time base drift 0.001 % per year
Specifications are subject to change without notice
* With standard 5 m test leads and floating test object

Reviews

Additional Information
SKU EGIL200
Manufacturer Part Code EGIL200

Made to Order item: This item is made-to-order with a lead time once the order is placed. Once an order is placed it cannot be cancelled or returned unless the unit is found to be faulty.