The Megger EGIL circuit breaker tester is intended for circuit breakers with one contact per phase. The EGIL incorporates features commonly found on more complex test systems but is designed to be smaller, simpler to use, and less expensive than other similar test sets.
The EGIL has three channels connected on one side and two separate time channels for measuring auxiliary contacts. Events at parallel contacts are recorded and displayed simultaneously via pre-insertion resistors.
To simplify on-site connection, the EGIL comes with ready-made multi-cable sets for both the main and auxiliary contacts. Coil currents are measured automatically and presented, together with other readings, immediately after testing on the display window or via the built-in printer. Additionally, the EGIL has a built-in breaker control unit that sets the instrument automatically for the next sequential breaker operation, making it easy and intuitive to use.
Using the EGIL with the SDRM and the SDRM accessory enables you to perform static and dynamic resistance tests and the EGIL can also be equipped with an optional USB interface for communication with a PC and the CABA Win circuit breaker analysis software.
Key Features
- Mains voltage changeover switch
- SDRM (optional)
- Built-in coil current measurement
- Breaker control unit for coil signals
- Three timing channels
- Two galvanically isolated timing channels
- Optional analog input channel
- USB (optional)
- Built-in printer
- Galvanically isolated sockets
- Breaker state indicator
- Buttons for sequence
- Switch used to set the breaker
- Menu-driven procedures
- MEASURE knob
- AUX 1 & 2 buttons
Click an image to enlarge the view.
What's Included
EGIL Basic Unit - BM-19090
- Cables timing measurement
- Extension cable timing
- Cable set for the breaker control unit
- Transport case
EGIL with USB Port - BM-19092
- CABA Win
- Cables timing measurement
- Extension cable timing
- Cable set for the breaker control unit
- Transport case
Egil with Analog Input Channel and USB Port - BM-19093
- CABA Win
- Cables timing measurement
- Extension cable timing
- Cable set for the breaker control unit
- Transducer cable XLR-open
- Transducer cable XLR-XLR
- Transport case
Egil with SDRM Option and USB Port - BM-19095
- CABA Win
- Cables timing measurement
- Extension cable timing
- Cable set for the breaker control unit
- Transducer cable XLR-open
- Transducer cable XLR-XLR
- Transport case
Product Range
- Megger BM-19000 EGIL Basic Unit without Options
- Megger BM-19003 EGIL with Analog/PC
- Megger BM-19090 EGIL Basic Unit without Options, with Accessories
- Megger BM-19092 EGIL Basic Unit with PC, with Accessories incl CABA Win
- Megger BM-19093 EGIL Basic Unit with Analog/PC, with Accessories incl CABA Win
- Megger BM-19095 EGIL SDRM with Accessories incl CABA Win
Datasheets
SPECIFICATIONS | ||
---|---|---|
*Specifications are valid at nominal input voltage and an ambient temperature of +25°C, (77°F). Specifications are subject to change without notice* | ||
Environment | ||
Application Field | The instrument is intended for use in medium-voltage substations and industrial environments | |
Operating Temperature | 0°C to +50°C (32°F to +122°F) | |
Storage & Transport Temperature | -40°C to +70°C (-40°F to +158°F) | |
Humidity | 5% - 95% RH, non-condensing | |
CE-Marking | ||
LVD | 2006/95/EC | |
EMC | 2014/30/EU | |
RoHS | 2011/65/EU | |
General | ||
Mains Voltage | 115 / 230 V AC (switchable), 50 / 60 Hz | |
Power Consumption | 100 VA (max) | |
Instrument Dimensions | 360 x 210 x 190 mm (14.2" x 8.3" x 7.5") |
|
Transport Case Dimensions | 420 x 300 x 230 mm (16.5" x 11.8" x 9.0") |
|
Weight | 6.3 kg (14 lbs). 10 kg (22 lbs) with accessories and transport case | |
Display | LCD | |
Available Languages | English, German, French, Spanish, Swedish | |
Time Measurement | ||
Measurement Time | 1 to 100 s | |
Resolution | 0.1 to 10 ms | |
Number of Channels | 3 with common ground | |
Time Base Inaccuracy | 0.05% of the reading ± resolution | |
Closed Status Threshold | < 10 Ω ±20% | |
Resistor Status Threshold | 10 Ω ±20% to 3 kΩ ±20% | |
Open Status Threshold | > 3 kΩ ±20% | |
Open Circuit Voltage | 24 V ±20% | |
Short Circuit Current | 100 mA ±20% | |
AUX 1&2 | ||
Number of Channels | 2, galvanically isolated | |
Contact-Sensing (Dry) | ||
Closed Status Threshold | < 600 Ω ±30% | |
Open Status Threshold | > 600 Ω ±30% | |
Open Circuit Voltage | 20 V ±20% DC | |
Short Circuit Current | 25 mA ±20% | |
Voltage Sensing (Wet) | ||
Open Indication Threshold | < 8 V (polarity insensitive) | |
Close Indication Threshold | > 13 V (polarity insensitive) | |
Working Voltage | 250 V AC / DC | |
Current Measurement | ||
Range | ±25 A per channel | |
Resolution | 25 mA | |
Inaccuracy | 1% of the reading ±100 mA | |
Working Voltage | 250 V AC / DC | |
Breaker Operation | ||
Sequences | C, O, C-O, O-C, O-C-O | |
Continuous Current | 5 A | |
Max Current | 25 A during 300 ms, rest time 1 min | |
Contact Function | Two independent control functions | |
Contact Characteristics | Non-bouncing, closing time max. 0.1 ms | |
Make/Break Capacity | 25 A, 250 V (AC or DC) per contact function | |
Start Breaker Operation | By rotary switch | |
Pulse Length | Adjustable in steps of 10 ms | |
Pulse Delay | Adjustable in steps of 10 ms | |
Working Voltage | 250 V AC / DC | |
Motion (Optional) | ||
Number of Channels | 1 independent | |
Max Cable Length | 10 m (33 ft) | |
Motion Input | ||
Range | -4 V to +4 V | |
Resolution | 2 mV | |
Inaccuracy | 1% of the measurement range | |
Transducer Resistance | 1 kΩ to 5 kΩ | |
Input Impedance | 150 kΩ | |
Motion Output | ||
Open Circuit Voltage | 4,095 V ±4 mV | |
Short Circuit Current | 115 mA | |
Printout | ||
Type of Printout | Graphic and numeric | |
Printer | Thermal printer with a fixed print head | |
Graphic Resolution | 8 dots/mm - 203 dpi | |
Paper Width | 114 mm (4.5") |
Reviews
SKU | EGIL-BM-190XX |
---|