All Megger Products

Megger DELTA4000 Series 12 kV Insulation Diagnostic System - Optional Onboard Computer

SKU
DELTA4110/4310A
Rating:
0%
(0)
Call For Pricing

We require additional information before you purchase this product

Black Friday - Free Items With Orders Over £300

Black Friday Freebies
Spend £100 to £749.99
LED Head Torch (Worth: £15.99)

Spend Over £750
Free LED Head Torch & Extendable Flash Light (Worth: £35.98)

Prices Ex VAT

or Call 01642 931 329 to discuss product options

Megger DELTA4000 Series 12 kV Insulation Diagnostic System
Description

The Megger DELTA4000 is an automatic 12 kV insulation power factor/tan delta test set designed for the immediate condition assessment of electrical insulation. In addition to traditional power frequency (50/60 Hz) testing, the DELTA4000 uses a 1 Hz power factor/tan delta to enhance power frequency assessment of high-voltage transformers, bushings, circuit breakers, cables, lightning arresters, and rotating machines. Using the same connection and software as power frequency tests, 1 Hz improves maintenance planning by reducing the need for historical trending and proprietary databases.

DELTA4000 - AC Insulation Testing

The high power variable frequency design generates its test signal independent of line frequency quality, and the hardware design uses the latest technology available for digital filtering of the response signal. As a result, the DELTA4000 series produces reliable results and stable readings in the shortest time with the highest accuracy, even in high interference substations.

The DELTA4000 series operates with PowerDB software for automatic testing and reporting or with Delta Control software for real-time manual testing.

Measurements include voltage, current, power (loss), power factor/tan delta, inductance, power factor, and capacitance. The test results are automatically stored in the computer and can also be downloaded directly to a USB drive or a printer.

Megger DELTA4000 Series 12 kV Insulation Diagnostic System placed in the megger car park. Megger DELTA4000 Series 12 kV Insulation Diagnostic System boxed.
Megger DELTA4000 Series 12 kV Insulation Diagnostic System open ground light. Megger DELTA4000 Series 12 kV Insulation Diagnostic System hv on light.

Key Features

  • Immediate power frequency (50/60 Hz) insulation condition assessment with 1 Hz power factor/tan delta
  • Precise temperature correction based on insulation deterioration with patented Individual Temperature Correction (ITC)
  • Guided test forms streamline testing and condition assessment of critical high-voltage assets
  • Simplified connection to bushing taps using quick disconnect clamps and 4 mm banana plug sockets
  • Portable, lightweight, and rugged two-piece design
  • Accurate measurements under high noise conditions (765 kV substations)
  • Industrial 300 mm (12 in) touchscreen controller option

What's Included

DELTA4110 Insulation Diagnostic System

  • DELTA4100 control unit
  • DELTA4010B HV unit
  • High voltage lead: 21 m (70 ft), double shielded
  • Measurement lead, color-coded red, 21 m (70 ft)
  • Measurement lead, color-coded blue, 21 m (70 ft)
  • Ground lead: 9 m (30 ft)
  • Input power cable 16A EU
  • Input power cable 16A US
  • Input power cable 16A UK
  • Safety hand switch, Interlock #1, 21 m (70 ft)
  • Safety foot interlock, 3m (10 ft)
  • HV unit power cable, 1 m (3 ft)
  • HV unit control cable, 1 m (3 ft)
  • Ground lead interconnect cable, 1 m (3 ft)
  • USB cable, 2 m (7 ft)
  • Ethernet cable, CAT 5, 2 m (7 ft)
  • Backpack lead bag
  • Software DELTA manual control
  • PowerDB Lite software

DELTA4310A Insulation Diagnostic System with Onboard Computer

  • DELTA4300A control unit
  • DELTA4010B HV unit
  • High voltage lead: 21 m (70 ft), double shielded
  • Measurement lead, color-coded red, 21 m (70 ft)
  • Measurement lead, color-coded blue, 21 m (70 ft)
  • Ground lead: 9 m (30 ft)
  • Input power cable 16A EU
  • Input power cable 16A US
  • Input power cable 16A UK
  • Safety hand switch, Interlock #1, 21 m (70 ft)
  • Safety foot interlock, 3m (10 ft)
  • HV unit power cable, 1 m (3 ft)
  • HV unit control cable, 1 m (3 ft)
  • Ground lead interconnect cable, 1 m (3 ft)
  • USB cable, 2 m (7 ft)
  • Ethernet cable, CAT 5, 2 m (7 ft)
  • Backpack lead bag
  • Software DELTA manual control
  • PowerDB Lite software

Product Range

  • Megger DELTA4110 12KV PF TAN DELTA Test System
  • Megger DELTA4310A 12KV PF TAN DELTA with Onboard Computer
Megger DELTA4000 Series 12 kV Insulation Diagnostic System about to be used by an operator. Megger DELTA4000 Series 12 kV Insulation Diagnostic System data screen.
Downloads

Datasheets

Megger DELTA4000 Series Datasheet Datasheets
Tech Specs
DELTA4000 Series
12 kV Insulation Diagnostic System
Input Power 90 - 264 V 45 - 66 Hz
16 A max
No loss in performance when used with a portable generator
Output Voltage 0 to 12 kV, continuously adjustable
Test Frequency Range 45-70 Hz (12 kV)
15-400 Hz (4 kV)
1-505 Hz (250V)
0.0001 Hz maximum resolution
Output Power 3.6 kVA
Output Current 300 mA (4 minutes)
200 mA (30 minutes)
100 mA (continuous)
The power supply capacity can be expanded to 4 A at 12 kV using the optional Resonating Inductor, (Cat. No. 670600-1)
Measuring Ranges
Voltage 25 V to 12 kV, 1 V resolution
Current 0 to 5 Amps, 0.1 μA maximum resolution
The measurement can be corrected to either 2.5 kV or 10 kV equivalents
Capacitance 0 to 100 μF, 0.01 pF maximum resolution
Inductance 6 H to 10 MH, 0.1 mH maximum resolution
Power Factor 0-100% (0-1), 0.001% maximum resolution
Dissipation factor 0-100 (0-10,000%), 0.001% maximum resolution
Watt Loss 0 to 2 kW, actual power, 0 to 100 kW when corrected to 10 kV equivalent
0.1 mW maximum resolution
The measurement can be corrected to either 2.5 kV or 10 kV equivalents
Temperature Correction
Individual Temperature Correction from 5°C to 50°C insulation test temperature to 20°C reference
Standard Tables As by international standards and manufacturers' data
Accuracy Voltage ±(1% of reading)
Current ±(1% of reading)
Capacitance ±(0.5% of reading + 0.1 pF)
Inductance ±(0.5% of reading + 1 mH)
Power Factor and Dissipation Factor ±(0.5% of reading + 0.02%)
Watt Loss ±(1% of reading + 1mW)
Frequency ±0.005% of reading
Noise Immunity
Electrostatic 15mA induced noise into any test lead with no loss of measurement accuracy at maximum interference to specimen current of 20:1
Electromagnetic 500 μT, at 50/60 Hz in any direction
Measurement UST: Ungrounded Specimen Testing
GST: Grounded Specimen Testing
PC Requirements
DELTA4110 Operating system: Windows 7, Windows 8, and Windows 10
Processor: Min Pentium 1 GHz
Memory: Min 1024 Mb RAM
Hard drive: Min 2 Gb available
Interface: USB and Ethernet
DELTA4310A Internal PC (provided)
DELTA4310A Provided Hardware
Touchscreen Display (ruggedised for field use) Size: 300 mm (12 in.)
Resolution: 1024 x 768 (XGA)
Luminance: 1600 nits
Coating: anti-glare
Backlight: LED
Technology: 4-wire resistive touchscreen
Memory: 32 Gigabits (SSD)
Controls & Communication Built-in touchscreen, 2 only USB 2.0 ports, and 1 only Ethernet interface
(10/100 Mbps) provided for data export
Built-in printer
OnBoard computer remote control of the Megger TTR3XX, MTO3XX, MLR10, MWA3XX and S1/MIT series insulation testers
Environment
Temperature Operating: -20 to +55° C (-4 to +131° F)
Storage: -50 to +70° C (-58 to +158° F)
Relative humidity Operating and Storage: 0 to 95% non-condensing
Standards
Safety IEC/EN 61010-1:2001
EMC EN 61326-1:2013
Shock and Vibration IEC 68-2-31 Drop, Topple, Freefall
Dimensions Control Unit: 290 x 290 x 460 mm (11 x 11 x 18 in.)
High Voltage Unit: 290 x 290 x 460 mm (11 x 11 x 18 in.)
*Does not include handles
Weight
DELTA4100 14 kg (31 lbs)
DELTA4300A 17 kg (35 lbs)
DELTA4010 23kg (48 lbs)
HV Cable 8 kg (18 lbs)
Other Cables 10 kg (23 lbs)

Reviews

Additional Information
SKU DELTA4110/4310A