The AVO415 measures voltage up to 1000 V and current up to 10 A with a high-resolution 6000-count display for resistance, continuity, frequency, and capacitance measurements. The Variable Frequency Drive (VFD) minimises the risk of incorrectly diagnosing equipment.
The AVO415 can test semiconductors' forward and reverse bias with the diode testing function. The meter includes auto-ranging, manual range selection, MAX, MIN, and HOLD functions, and a continuity function with an audible and visual buzzer.
The AVO415 also has CAT III 1000 V and CAT IV 600 V safety ratings, an IP67 dustproof and waterproof rating, withstands voltage spikes up to 8.1 kV, protects against arc flash hazards and is suitable for Variable Speed Drive (VSD) conditions.
*Ratings: Double insulated, CAT III 1000 V, CAT IV 600 V, 10 A max
Maximum Voltage Between any Terminal and Earth Ground | 1000 V |
---|---|
F1 Fuse Protection for A Inputs | 10 A, 1000 V, 30 kA |
F2 Fuse Protection for mA Input | 800 mA, 1000 V, 30 kA |
Battery Type | 9 V Alkaline, NEDA 1604A/IEC 6LR61 |
Display | 6000 counts, backlit liquid crystal |
Altitude | 2000 m maximum. |
Operating Temperature | 5 °C to +40 °C (41 °F to 104 °F) |
Storage Temperature | -20 °C to +60 °C (-4 °F to 140 °F) |
Operating Humidity | Max 80% up to 31 °C (87 °F), decreasing linearly to 50% at 40 °C (104 °F). |
Storage Humidity | 50% at 40 °C (104 °F) |
Size (H x W x D) | 180 mm x 82 mm x 55 mm |
Weight | 397 g without battery 427 g with battery |
Safety | IEC 61010-1: Pollution Degree 2 IEC 61010-2-033: CAT IV 600 V CAT III 1000 V |
EMC | IEC 61326-1: Portable Electromagnetic Environment CISPR 11: Group 1, Class A IEC 61326-2-2 Enclosure Double moulded IP67 rating |
Shock (Drop Test) | 6.5 feet (2 meters) |
Continuity Check | Audible signal will sound if the resistance is less than 50 Ω (approx.), the test current <0.35 mA |
Diode Test | Test current of 0.9 mA maximum, open circuit voltage 3.2 V DC typical |
PEAK | Captures peaks > 1 ms |
Temperature Sensor | Requires type K thermocouple |
Input Impedance | > 10 MΩ V DC and >10 MΩ V AC |
Crest Factor | ≤3 at full scale up to 500 V, decreasing linearly to ≤1.5 at 1000 V |
AC Response | True RMS |
ACV Bandwidth | 45 Hz to 1 kHz |
Overrange Indication | OL is displayed |
Auto Power OFF | 15 minutes (approximately) with disable feature |
Polarity | Automatic (no indication for positive) Minus (-) sign for negative |
Low Battery Indication | Battery low warning |
Measurement Rate | 2 times per second |