Megger 813178 GL 660-1 Earth Fault Locator Set

All Megger Products
  • Pulsed output current
  • Live voltages up to 660 V
  • Low-frequency signal
SKU
813178
MPN
813178

Read More

View All Battery Testers

Use the Megger 813178 Geolux GL 660-1 cable ground fault locator to protect your assets! Important control, signal, and supply systems, such as those for railway installations, hospitals, power plants, or other industrial facilities, are designed to be potentially free (for example IT systems) and are monitored by earth fault indicators to ensure safe and uninterrupted operation. In these systems, a single earth fault will cause no service interruption, however, if a second fault should occur, there is a high risk of a partial or complete breakdown of the installation.

For this reason, any earth fault must be located and repaired as fast as possible and this is where the Geolux GL 660-1 comes in. This cable ground fault locator is directly connected to the faulty line with live voltages up to 660 V and generates a low-frequency signal which allows you to trace a specific receiver along the faulty line to the fault position where it can be repaired. It is highly accurate, filtering out large interference signals, and can locate faults up to 150 kOhm. What's more, you don't need to switch off the power when locating the fault and it uses a pulsed output current to make it easier to detect the test signal.

Key Features

  • Mains filter for direct coupling to live cables up to 660 V
  • Pulsed output current for easier detection of the test signal
  • Filter for the suppression of large interference signals
  • Location of earth/ground faults up to 150 kOhm
  • No switch-off during the fault location required
  • No influence on the signal lines connected to

What's Included?

  • Earth fault locator with compensation
  • Receiver with compensation
  • Carrying strap
  • Generator 5 Hz
  • Set of cables for generator
  • Probe for round conductor
  • Reader clamp 100 mm compensated
  • Connection lead for reader clamp
  • Identification tongs 12 mm compensated
  • Carrying case for generator and receiver
Call for Pricing

We require additional information

Call 01642 931 329 or complete the form:

Technical Information
Specification
  Receiver GLE 660-1
Power Supply Mains 230 V, 45 ... 60 Hz, Battery (rechargeable) 12 V / 2.4 Ah
Operating Time at 80 V approx. 5h
Transmitter Frequency 5 Hz +/- 0.1 Hz
External Dielectric Strength 660 V AC/DC
Operating Temperature - 10 °C ... + 50 °C
Storage Temperature - 25 °C ... + 70 °C
Weight approx. 12kg
Dimensions (W x H x D) 366 mm x 183 mm x 260 mm

 

  Transmitter GLS 660-1
Amplification 70 dB ... 100 dB
Filter 16,66 und 50 Hz Notch
Power Supply 8 x 1.5 V AA batteries (LR 6)
Operating Time approx. 40 hours
Operation Temperature - 10 °C ... + 50 °C
Storage Temperature - 25 °C ... + 70 °C
Max. rel. Humidity < 80 %
Weight ca. 1.2 kg
Dimensions (W x H x D) 220 mm x 100 mm x 130 mm