The Megger DET4TC2 is designed for extended temperature range use with an IP54-rated enclosure making it a genuine outdoor instrument. The instrument provides all the functions required for ground system testing: variable frequency 2 pole, 3 pole, 4 pole, Attached Rod Technique (ART), stakeless, leakage current, and ground noise voltage measurement.
The instrument is easy to use with a large rotary selector switch and one-press test button, both of which permit operation with gloved hands. Unlike some instruments, the design negates the need for a shorting link when making two pole measurements. There are no hidden functions with the instrument: clearly labelled auxiliary controls are used to select the test frequency (94 Hz, 105 Hz, 111 Hz, and 128 Hz), output voltage (50 V or 25 V where local standards apply), and to switch the backlight on or off.
The clear, easy-to-read display provides excellent contrast and viewing angle making the instrument ideally suited to outdoor use. The display is backlit, extending the operational environment of the instrument to cable cellars and other dark locations.
The instrument offers a wide measurement range of 0.01 Ω a to 200 kΩ, ground noise voltage measurement from 1 V to 100 V, and ground current from 1 mA to 20 A. Accurate results can be obtained in electrically noisy environments since the instrument is capable of rejecting noise voltages of 40 V peak to peak and the user can select different test frequencies to minimise the effect of interference.
The DET4TC2 digital ground tester is powered by 8 AA batteries which are widely available and deliver excellent testing time, the battery status is displayed using a bar graph.
The Megger DET4TC2 complies with stringent safety standards and is rated to 100 V CAT IV. They also have selectable 25 V or 50 V output for compliance with IEC 61557-5.
The Megger 1012-521 delivers the DET4TC2 and the ETK50C. The ETK50C kit includes 50m Earth Test Cables, Spikes & Clamps.
Ingress Protection | IP54 |
C Stake, P Stake, and Noise Checks | Automatic |
Noise Rejection | 40V peak to peak |
2 Wire, 3 Wire, and 4 Wire tests | Yes, no shorting links are required |
No Disconnect Testing (ART) | Yes, with MCC CLAMP |
Stakeless Measurement | Yes, with MCC CLAMP and MVC CLAMP |
Instrument Output | Voltage: ±25 V or ±50 V at 94 Hz, 105 Hz, 111 Hz, and 128 Hz Current: 4.5 mA or 0.45 mA or 0.045 mA |
Ground Current Range with Clamp | 0.5 mA to 19.9 A |
Ground Current Accuracy | 5% ±3 digits |
Ground Voltage Range | 0 to 100V AC |
Ground Voltage Accuracy | 2% ±2 V |
Resistance Ranges | 2, 3, 4 pole: 0.01 Ω to 200 kΩ ART: 0.01 Ω to 200 kΩ Stakeless: 0.01 Ω to 200 Ω |
Resistance Accuracy | 2P measurements: 2% ±3 digits 3P measurements: 2% ±3 digits 4P measurements: 2% ±3 digits ART measurements: 5% ±3 digits Stakeless measurements: 7% ±3 digits |
Maximum Probe Resistance | Rp limit: 200 kΩ (50 V output voltage) Rc limit: 200 kΩ (50 V output voltage) Limits reduced to 100 kΩ for 25 V output voltage Limits reduced to 5 kΩ for 0.01 Ω resolution |
Display | 3½ digit high contrast liquid crystal, backlit |
Battery Type | 8 off AA (LR6) cells |
Operating Temperature Range | -15 °C to +55 °C / 5 °F to 131 °F |
Storage Temperature Range | -40 °C to +70 °C / -40 °F to 158 °F |
Safety | Complies with the requirements of IEC 61010-1 100V CAT IV between terminal pairs* |
EMC | Following IEC61326-1 |
Standards Compliance | Complies with the requirements of KEMA K85B Complies with the following parts of EN61557, “Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V d.c. Equipment for testing, measuring or monitoring of protective measures”. Part 1 - General requirements, Part 5 - Resistance to earth |
Dimensions | 203 mm x 148 mm x 78 mm (8 in x 5.8 in x 3 in) |
Weight | 1kg (2.2lb) |
*The CAT IV 100 V rating is dependant on the use of a lead set of at least this rating, for example, the optional two-wire lead set part number 1001-858.