The ET6300 Multifunction Tester verifies the electrical safety of installations in compliance with the latest 18th Edition Wiring Regulations. The high-current and non-trip loop testing ensures input protection with a CAT IV safety rating.
This tester includes standard voltage measurement and phase sequence indication. Its large colour display, equipped with a backlight, facilitates easy reading of measurements and provides helpful ‘Help’ menus for user guidance.
In addition to 18th Edition testing, the ET6300 can test electric vehicle charge points with the optional Martindale TL305EV adapter. The unit includes AA rechargeable batteries, which can be charged in the tester using the mains adaptor or an optional in-car charger.
ET6000 | ET6300 | ET6500 | |
---|---|---|---|
Insulation resistance | ✔ | ✔ | ✔ |
Fast non-trip loop testing | ✔ | ✔ | ✔ |
Voltage measurement & phase rotation | ✔ | ✔ | ✔ |
High-quality colour display with help screens | ✔ | ✔ | ✔ |
Auto RCD and ramp test with all results on one screen | ✔ | ✔ | ✔ |
CAT III 600V / CAT IV 300V safety rating | ✔ | ✔ | ✔ |
Standard test leads | ✔ | ✔ | ✔ |
TL180 slimline test probe supplied | ✔ | ✔ | |
Three / four wire earth resistance test | ✔ | ||
EV ready (adapter optional) | ✔ | ||
EV ready (adapter supplied) | ✔ |
ET6000 | ET6300 | ET6500 | |
---|---|---|---|
SPECIFICATION | |||
Voltage | 0V - 500V | ||
Frequency | 10HZ - 499HZ | ||
EV Ready | ✔ | ✔ | |
Compliance | BS EN 61010-1 CAT III 600V CAT IV 300V, BS EN 61557, BS 57671:2018 18th Edition, BS EN 61326-1 | ||
Dimensions | 250mm x 107mm x 135mm | ||
Weight | 1.3kg approx (excluding batteries) | ||
INSULATION RESISTANCE | |||
Nominal Voltages 50, 100, 250, 500 and 1,000V DC |
✔ | ✔ | ✔ |
CONTINUITY RESISTANCE | |||
Low R (200mA) | ✔ | ✔ | ✔ |
Continuity (Low Current) | ✔ | ✔ | |
RCD TESTING | |||
Nominal Residual Currents (mA) | 10 / 30 / 100 / 300 / 500 | 6 / 10 / 30 / 100 / 500 / 650 / 1000 | 6 / 10 / 30 / 100 / 500 / 650 / 1000 |
Test Current Shape | A, AC | A, AC, B, B+, F | A, AC, B, B+, F |
RCD Type | G, S | G, S | G, S |
Contact Voltage | ✔ | ✔ | ✔ |
Trip-out Time | ✔ | ✔ | ✔ |
Trip-out Current | ✔ | ✔ | ✔ |
FAULT LOOP IMPEDANCE AND PROSPECTIVE FAULT CURRENT | |||
Z Loop L-PE lpfc | ✔ | ✔ | ✔ |
Z Loop L-PE RCD, lpfc, Non-trip Subfunction | ✔ | ✔ | ✔ |
Loop-Rs | ✔ | ✔ | |
Line Impedance and Prospective Short-circuit Current | ✔ | ✔ | ✔ |
Voltage Drop Detection | ✔ | ✔ | |
EARTH RESISTANCE (Requires optional Martindale ER2KIT-S or Martindale ER4KIT-S Earth Spike Kit) | |||
Re (3-wire and 4-wire) 1Ω / 9999Ω | ✔ | ||
Ro (Specific Earth Resistance Testing) | ✔ | ||
OTHER FEATURES | |||
Automatic Polarity Change | ✔ | ✔ | |
Calibration Date Reminder | ✔ | ✔ | ✔ |
Memory and Reporting (Excel-export) | ✔ | ||
Rechargeable Batteries Suitable for On-board Charging | Optional | ✔ | ✔ |
Networks | TN, TT | TT, TN, IT, LV (2 x 55V) | TT, TN, IT, LV (2 x 55V) |
Supplied with External Probe with Button | ✔ | ✔ | |
Compatible with External Probe with Button | ✔ | ✔ | ✔ |
Supplied with TL305EV Adapter | Optional | ✔ | |