The Kewtech SMARTPAT PAT Tester is a battery-operated, manual PAT tester with a large, easy-to-read, backlit display and simple user interface. It can be converted into a downloading PAT tester using the free KEWPAT App (not included). The Kewtech SMARTPAT PAT Tester performs a range of tests including 250V and 500V insulation tests, extension lead tests, 10mA and 30mA RCD tests, substitute leakage tests with selectable limits, five-second continuity and quick-check continuity tests, and IT-safe 200mA earth bond tests. Results are accompanied by a green or red PASS or FAIL screen. The Kewtech SMARTPAT PAT Tester also supports appliance status pre-checks and includes a test lead nulling function.
Please follow this link for more information.
The Kewtech KEW80L Bluetooth Label Printer is a compact, lightweight, easy-to-use barcode and QR label printer. It can accommodate print rolls with a width of up to 58mm and a diameter of 50mm. Furthermore, the Kewtech KEW80L Bluetooth Label Printer has been designed to connect to the KEWPAT App wirelessly.
Please follow this link and view the video below for more information.
Protective Conductor Resistance Test | ||
Measuring range | 0.00 - 20.00 Ω (NULL value inc)* | |
Over-range indication | > 20.00 Ω | |
Resolution | 0.01Ω | |
Open-circuit voltage | 5 V ±0.4 V DC | |
Measuring current | 200 mA DC (nominal value) | |
Accuracy | ±3%rdg ±5dgt | |
* Resistances exceeding 3 Ω cannot be cancelled by NULL function | ||
Mains Voltage | ||
Display range | 30 - 270 V | |
Hi/ Lo indication | < 30 V: No voltage indication > 270 V: 270 V | |
Resolution & Accuracy | 1 V ±3%rdg ±5dgt | |
Insulation | ||
Rated Voltage | 250V | 500V |
Measuring range | 0.00 - 20.00 MΩ | |
Over-range indicatio | > 20.00 MΩ | |
Resolution | 0.01 MΩ | |
No-load voltage | 250 V DC +20%, -0% | 500 V DC +20%, -0% |
Short-circuit current | 1.5 mA DC or less | |
Rated current | 1 -1.2 mA with a load of 0.25 MΩ | 1 to 1.2 mA with a load of 0.5 MΩ |
Accuracy | ±2%rdg±3dgt | |
Substitute Leakage | ||
Measuring range | 0.10 - 12.00 mA rms | |
Over-range indication | > 12.00 mA | |
Resolution | 0.01mA | |
Open-circuit voltage/ Freq | 30 V ±5 V rms / 50 Hz ±5% | |
Measuring current | 1.2 mA AC ±0.5 mA (when measuring 12.00 mA) | |
Accuracy | ±3%rdg±5dgt | |
Insuyltation Test Between L-N | ||
Open-circuit voltage | 4.5 V ±0.5 V DC | |
Criteria of judgement | 100 kΩ ±20 kΩ or less: LCD shows “<0.10 MΩ” and the measurement is halted | |
Run Leakage | ||
Item | Load Current | Leakage Current |
Mains voltage range | 100 - 253 V / 50 Hz | |
Measuring range | 0.10 - 13.00 A rms | 0.10 - 20.00 mA rms |
Display range | 0.00 - 13.00 A | 0.00 - 20.00 mA |
Over-range indication | > 13.00 A | > 20.00 mA |
Resolution | 0.01A | 0.01mA |
Accuracy | ±10%rdg ±5dgt | ±3%rdg ±5dvgt |
Max. rating | 3 kVA max. / 15 sec. cont. | |
RCD Test | ||
Rated voltage | 230 V - 15% to +10% / 50Hz | |
Rated current | 10 mA / 30 mA | |
Test duration | ×1: 0.0 ms - 500.0 ms | ×5: 0.0 ms - 40.0 ms |
Test current accuracy | 2% - 8% | |
Operating time accuracy | ±2 ms ( 40 ms) ±8 ms (>40 ms) |
Printing Method | Thermal Transfer |
Print width | 72mm (max) |
Paper roll / label width | 80mm (max) |
Print Speed | 90mm/s |
Max roll diameter | 50mm |
Print density | 576 Dots/line |
Input buffer | 25K |
Power adaptor output | 9V 1A |
Charging time | 3 hrs (can print whilst charging) |
Battery | Lithium 2600mAh / 7.2V |
Operating temperature range | 0°C ~50°C |
Operating humidity | 20%~85% RH |
Storage temperature range | -20°C~60°C |
Storage humidity range | 5%~95% RH |
Mechanical life | 50Km |
Dimensions | 130 x 60 x 115 approx |
Weight | 450g approx. (without print roll) |