Kewtech KT66DL 12-in-1 Multifunction Tester with Earth Spike Kit
This kit version of the Kewtech KT66DL Multifunction Tester comes complete with ACCES Earth spike kit enabling testing of TN, TT and independent earthing systems and is compatible with any ER capable tester using 4mm connections.
What’s Included?
Kewtech ESKIT Earth Spike Kit
- 1 Pair Earth spikes
- 1 set of lest leads
- 1x Red 20Mtr
- 1 x Yellow 10Mtr
- 1 x Green 5Mtr (ACC7095)
Kewtech KT66DL 12-in-1 Multifunction Tester
- Kewtech ACC064SP G7 Test Probe with Remote Test Button
- Kewtech ACC065 G7 Test Lead Set
- Batteries
- Software
- Kewtech Kamp 12 Mains Lead
- Test Lead Pouch
- Soft Carry Case
- USB Cable
- Padded Strap
- Instruction Manual
- Calibration Certificate
Videos
Introduction
Overview
Kewtech Multifunction Tester Comparison
FEATURES | KT63DL | KT63PLUS | KT65DL | KT66DL |
Continuity at 200mA with auto null function for test leads | • | • | • | • |
Continuity 15mA test current option | - | - | - | • |
Insulation 250 V, 500 V & 100 V | • | • | • | • |
Insulation 100 V | - | - | - | • |
Polarisation and dielectric absorbtion index | - | - | - | • |
Digital insulation resistance bargraph | - | - | - | • |
PAT testing with optional PAT Adaptor I | • | • | • | • |
PAT results memort, auto ID advance and downlaod with software | - | - | • | • |
Continuous Live Warning | • | • | • | • |
55V Loop test (tests 110V CTE on-site systems) | • | • | • | |
High voltage LED light | - | - | • | - |
2 Wire low current ATT non RCD trip loop tests | - | - | - | • |
EVSE charging point loop tests | - | - | - | • |
High current loop tests | • | • | • | • |
PSC/PFC test | • | • | • | • |
50kA PFC range using 25A test current | - | - | - | • |
Loop test noise level indicator | - | - | - | • |
0.001 ohm resolution high current loop test | - | • | • | • |
Selectable Max Zs table | - | - | • | • |
Selectable loop pulse function to overcome contact resistance | - | - | - | • |
Hands free testing | • | • | • | • |
Backlight | • | • | • | • |
RCD type AC, ACS, A & AS | • | • | • | • |
Single auto & ramp tests | • | • | • | • |
RCD type F, B, BS & EV | - | - | - | • |
EVSE 6mA RDCD ramp, auto & single test | - | - | - | • |
Uc test | - | - | - | • |
Variable RCD test | - | - | - | • |
RCD auto test all results on one screen | - | • | • | • |
Test probe with remote test button | - | • | • | • |
Advanced memory software included | - | - | • | • |
Phase rotation | - | • | • | • |
Earth resistance with optional Acces kit | - | - | • | • |
LCD Dsiplay | • | - | - | - |
Dot Matrix Display | - | - | • | - |
Large Colour Matrix Display | - | • | - | • |
Protective lid on instrument | - | - | • | • |
Carry case | Soft Case | |||
Fused test leads | Optional | |||
Help menu | - | - | - | • |
IP40/54 | 54 | 54 | 40 | 40 |
Wiring & lead polarity check | • | • | • | • |
Mains polarity check | • | • | - | - |
Touch pad for earth potential limits 25V or 50V | - | - | • | • |
Volts measurements | • | • | • | • |
Separate volts function with L-N,L-PE & N-PE simultaneous display | - | - | - | • |
Magnetic feet | • | - | - | - |
Kit Comparison
KT66DL | KT66ET | |
Kewtech KT66DL 12-in-1 Multifunction Tester |
✔ | ✔ |
Kewtech ESKIT Earth Spike Kit |
✖ | ✔ |
Kewtech ACC064SP G7 Test Probe with Remote Test Button |
✔ | ✔ |
Kewtech ACC065 G7 Test Lead Set |
✔ | ✔ |
Batteries |
✔ | ✔ |
Software |
✔ | ✔ |
Kewtech Kamp 12 Mains Lead |
✔ | ✔ |
Test Lead Pouch |
✔ | ✔ |
Soft Carry Case |
✔ | ✔ |
USB Cable |
✔ | ✔ |
Padded Strap |
✔ | ✔ |
Instruction Manual |
✔ | ✔ |
Calibration Certificate |
✔ | ✔ |
Kewtech KT66DL 12-in-1 Multifunction Tester Technical Specifications
Loop Impedance
Range | 20.00/200.0/2000Ω (auto-ranging) |
Display range | 0.00 - 20.99Ω / 16.0 - 209.9Ω / 160 - 2099Ω |
Measuring range | 0 – 2000Ω |
Accuracy | ±2.0%rdg±8dgt |
Open-circuit voltage | 7 – 14V DC |
Test current | 200mA test: 200mA or more (2Ω or less) 15mA test: 15mA±3mA (short-circuit) |
Note |
• Enabled if pre-set NULL value is 9Ω or less. • Buzzer: Buzzer sounds when measured resistance is 2Ω or less. |
Volts
Range | 300.0/600V (Auto-ranging) |
Display range | Voltage: 2.0 – 314.9V, 240 – 629V |
Frequency: 40.0 – 70.0Hz (displayed at 2V or higher) | |
Measuring.range | Voltage: 2 – 600V |
Frequency: 45 – 65Hz | |
Accuracy | Voltage: ±2%rdg±4dgt |
Frequency: ±0.5%rdg±2dgt |
Uc (RCD)
Mains voltage range | 100-260V |
Range | 100V |
Display range | 0.0 - 104.9V |
Measuring range | 0 - 100V |
Accuracy | +5%to+15%rdg ±8dgt 230V |
Test current | 50 % or less of IΔn |
Earth
Precise measurement | Simplified measurement | |
Range | 20.00 / 200.0 / 2000Ω (auto-ranging) | |
Accuracy | 20Ω range; ±2%rdg±0.08Ω The other ranges: ±2%rdg±3dgt (Aux. earth resistance: 100Ω) |
±2%rdg±0.08Ω The other ranges: ±2%rdg±3dgt |
Output current | 20Ω range: approx. 3mA, 200v range: approx. 1.7mA | |
2000Ω range: approx. 0.7mA Frequency: 825Hz |
Phase Rotation
Measuring Range | 48 – 600V / 45 - 65Hz |
Criteria of judgement | Correct sequence: Clockwise symbol and “1, 2, 3” are displayed. |
Reversed sequence: Counter-clockwise symbol and “3, 2, 1” are displayed. |
Insulation
Rated voltage | 100V | 250V | 500V | 1000V | SPD (Varistor) 1000V |
Range | 2.000/20.00/200.0MΩ auto-ranging |
20.00/200.0/1000MΩ auto-ranging |
20.00/200.0/2000MΩ | 0 -1000V (increases in 1V steps) | |
Display range | 0.000 - 2.099MΩ | 0.00 - 20.99MΩ | 0.00 - 20.99MΩ | 1049V | |
1.60 - 20.99MΩ | 16.0 - 209.9MΩ | 16.0 - 209.9MΩ | |||
16.0 - 209.9MΩ | 160 - 1049MΩ | 160 - 2099MΩ | |||
Measuring range | 0 - 200MΩ | 0 - 1000MΩ | 0 - 2000MΩ | 0 - 1049V | |
Accuracy | 2.000MΩ range: ±2%rdg±6dgt | 20.00MΩ range: ±(2%rdg+6dgt), 200.0MΩ range: ±(2%rdg+6dgt) | ±5%rdg±5dgt | ||
20.00MΩ range: ±2%rdg±6dgt | 1000MΩ range: ±(5%rdg+6dgt) | 2000MΩ range: ±(5%rdg+6dgt) | |||
200MΩ range: ±5%rdg±6dgt | |||||
Rated meas. current |
1.0 - 1.2mA at 100kΩ |
1.0 - 1.2mA at 250kΩ |
1.0 - 1.2mA at 500kΩ |
1.0 - 1.2mA at 1MΩ |
1.0 mA |
Loop
Function | LOOP ATT | LOOP HIGH | ||||
3-Wire L-PE | 2-Wire L-PE | L-PE0.01ΩRes | L-PE0.001ΩRes | L-N/L-L | ||
Mains input voltage range |
100 – 260V 50/60Hz (L-N < 20Ω) |
48 – 260V 50/60Hz | 100 - 260V 50/60Hz | 48 - 260V 50/60Hz | ||
Range | LOOP | 20.00/200.0/2000Ω (auto-ranging) | 20.00/200.0/2000Ω | 2.000Ω | 20.00Ω | |
PFC/PSC | 2000A/20kA | 2000A/20kA (PFC only) | 2000A/50kA (PFC only) | 2000A/20kA (PSC only) | 2000A/20kA (PSC only) | |
Display range | LOOP | 0.00 – 20.99Ω 21.0 – 209.9Ω 210 – 2099Ω |
0.00 –20.99Ω 21.0 –209.9Ω 210 –2099Ω |
0.00 - 20.99Ω 21.0 - 209.9Ω 210 –2099Ω |
0.000 - 2.099Ω | 0.00-20.99Ω |
PFC/PSC | 0 – 2099A 2.10 – 20.99kA |
0 – 2099A 2.10 – 20.99kA (PFC only) |
0 – 2099A 2.10 – 50.49kA (PFC only) |
0 – 2099A 2.10 – 20.99kA (PFC only) |
0 – 2099A 2.10 – 20.99kA (PSC only) |
|
Meas. range | LOOP | 0 – 2000Ω | 0 – 2000Ω | 0 – 2000Ω | 0 – 2Ω | 0 – 20 |
Accuracy | LOOP | ±(3%rdg+6dgt) | ±(3%rdg+10dgt) | ±(3%rdg+4dgt) | ±(3%rdg+25mΩ) | ±(3%rdg+4dgt) |
PFC/PSC | Depending on the accuracies of voltage and LOOP measurements | |||||
Test current @ 230V | L-N:6A/60ms N-PE:10mA (5.3Hz) |
L-PE: 15mA | 20Ω: 6A/20ms, 200Ω: 0.5A/20ms 2000Ω: 15mA/500ms |
25A/20ms | 6A/20ms |
RCD
Mode | Rated residual operating current (mA)(IΔn) | Test current | Duration | |||
Current (mA) rms | Accuracy @230V | Meas. time | Accuracy | |||
x 1/2 | AC | G: 10/30/100/300/500/1000 S: 100/300/500 | IΔn×1/2 | -8% to-2% VAR:-10% to 0% | 2000ms | Trip Time ±(1%+2ms) Measuring time ±3% of FS |
A/F | G: 10/30/100/300/500 AS:100/300/500 | IΔn×1/2 | -10% to 0% | |||
B | G: 10/30/100/300 S:100/300 | IΔn×1/2 | -10% to 0% | |||
x 1 | AC | G:10/30/100/300/500/1000 S: 100/300/500 | IΔn | +2% to +8% VAR:0% to +10% | G:550ms S:1000ms |
|
A/F | G: 10/30/100/300/500 AS:100/300/500 | IΔn×1.4 (10mA: IΔn×2) | 0% to +10% | |||
B | G: 10/30/100/300 S:100/300 | IΔn×2 | 0% to +10% | |||
6 mA DC | IΔn | 0% to +10% | 10.5s | |||
x 5 | AC | G: 10/30/100 S: 100 | IΔn×5 | +2% to +8% VAR:0% to +10% | 410ms | |
A/F | G: 10/30/100 AS: 100 | IΔn×5×1.4 | 0% to +10% | |||
B | 10/30 | IΔn×2×5 | 0% to +10% | |||
Ramp 20 to 110% |
AC | 10/30/100/300/500 S: 100/300/500 | IΔn | -4% to +4% | by 10% G: 300ms S: 500ms |
Measuring time ±3% of FS |
A/F | G: 10/30/100/300/500 AS:100/300/500 | IΔn×1.4 (10mA:IΔn×2) | -10% to +10% | |||
B | G: 10/30/100/300 S: 100/300 | IΔn×2 | -10% to +10% | by 2% /150ms | ||
Ramp EV 30 to 100% | 6 mA DC | IΔn | -10% to +10% | by 2% / 500ms |
General Specifications
Applicable Standards | IEC 61010-1 CATIII (600V) CATIV (300V) pollution degree 2, IEC 61010 -Tester , -2-030, -2-034, IEC61557-1,2,3,4,5,6,7,10, IEC 60529 IP40, EN 61326-2-2 (EMC) |
Dimensions & Weight | 136 (L) x 235(W) x 114 (D) mm, 1300g including batteries (8 x AA / LR6) |
Reviews
SKU | KT66ET |
---|---|
Manufacturer Part Code | KT66ET |