Please see the video below for a quick introduction to Kewtech’s series of KT Single-function 18th Edition Testers.
The Kewtech KT500 Digital RCD Tester is a compact, simple-to-use, single-function tester designed for testing RCDs per 18th Edition regulations.
The Kewtech KT500 Digital RCD Tester can be used to test type AC, ACS and A RCDs. It is able to perform the following tests and measurements:
- 30mA autotest
- Ramp test
- Distribution board polarity test
- AC voltage VLN measurements
This instrument also includes a LED warning light for indicating the presence of polarity and voltage.
Results can be recalled to the Kewtech KT500 Digital RCD Tester’s display using the recall button, allowing the user to see and record measurements relevant to his/her application. Other practical features include a Hands-free function.
The Kewtech KT500 Digital RCD Tester is an accurate, easy-to-use, single-function tester capable of comprehensively testing RCDs as required by the 18th Edition.
Kewtech KT500 Digital RCD Tester Key Features
- A compact, simple-to-use, single-function tester
- Designed for testing RCDs per 18th Edition regulations
- Test type AC, ACS and A RCDs
- 30mA autotest
- Ramp test
- Distribution board polarity test
- AC voltage VLN measurements
- LED warning light for indicating the presence of polarity and voltage
- Results recall button
- Hands-free function
- Accurate, easy-to-use, single-function tester for comprehensively testing RCDs
What’s Included?
- Kewtech KT500 Digital RCD Tester
- Kewtech KAMP 12 Mains Lead
- Carry Case
- Manual
- Calibration Certificate
*** The Kewtech KT500 Digital RCD Tester can be ordered with the Kewtech KT300 Insulation/ Continuity Tester and KT400 Loop Impedance Tester to create a complete 18th Edition testing kit. ***
Kewtech KT500 Digital RCD Tester Technical Specifications
Test Current Accuracy | |
Test Current | Accuracy |
x ½ | - 0% to - 10% |
x 1 , x 5 | + 0% to +10% |
Trip Time Accuracy | |
Test Current | Accuracy |
< 1 second | ± (1% + 1 ms) |
> 1 second | ± (1% + 10 ms) |
RCD Trip Time | |
Measurement Range | 5 ms - 1999 ms |
Operating Range Per BSEN61557-6 | 38 ms - 1999 ms |
Supply Voltage | 195V - 253V AC 50Hz |
General Specifications | |
Power supply | 4 x AA LR6 Batteries |
Battery life | 50 hours |
Overvoltage category | CAT IV 300V |
Operating temperature | 0 - 40ºC |
Storage temperature | -10 to 60ºC |
Operating humidity | 80% @ 31ºC to 50% @ 40ºC |
Safety compliance | BSEN 61010-2-030:2010 |
EMC compliance | BSEN 61326-2-2:2013 |
Performance standard | BSEN 61557-1:2007 |
BSEN 61557-6:2007 | |
Probes | GS38 compliant |
Dimension (mm) | 180mm x 85mm x 50mm |
Weight (g) | Approximately 450g |
Reviews
SKU | KT500 |
---|---|
Manufacturer Part Code | KT500 |