Designed to prove circuits are dead and maintain compliance with safe isolation regulations, the Kewtech KEWISO5 Safe Isolation Kit includes:
Capable of measuring voltage up to 1000V AC/ 1500V DC and current up to 200A AC, the Kewtech KT5 Open Jaw Current & Voltage Tester is a comprehensive voltage and current indicator ideal for identifying PEN situations. It supports frequency, phase rotation, and diode tests, and features a resistance and continuity buzzer with an adjustable threshold. The Kewtech KT5 Open Jaw Current & Voltage Tester offers non-contact, single-pole, and two-pole voltage detection and will indicate the presence of voltage via the LED/LCD and using buzzer and vibration alerts. Finally, the Kewtech KT5 Open Jaw Current & Voltage Tester is IP64-rated, meets BS EN 61243 and BS EN 61010 CAT IV 600V standards and features GS38 probe tips and built-in probe storage.
Please follow this link for more information regarding the Kewtech KT5 Open Jaw Current & Voltage Tester.
The Kewtech KEWPROVE3 Proving Unit can be used to verify the functionality of low-impedance voltage testers. This fast-responding, 50-690V proving unit features two terminals for testing AC and DC voltage detectors and will ramp down through voltage levels. LEDs indicate that the unit is functioning.
For more information regarding the Kewtech KEWPROVE3 Proving Unit, please follow this link.
The Kewtech KEWLOCK Lockout Device fits MCBs, RCDs, RCBOs, and mains switches. Users can set their own combination and the Kewtech KEWLOCK Lockout Device comes with two re-writable warning labels.
Please follow this link for more information regarding the Kewtech KEWLOCK Lockout Device.
Voltage Range | 1…1000V AC (15…800Hz), 1…1500V DC(±) |
LED nominal Voltage | 120 /230/400/690/1000V |
LED tolerances | EN 61243-3 |
ELV indication LED | >50V AC, >120V DC |
Response time | <1s at 100% of each nominal value |
LCD Range | 1…1000V, AC (15…800Hz), 1…1500V DC(±) |
LCD Resolution | 0.1V (1…29.9V), 1V (30…1500V) |
LCD Accuracy | ±3% ±1.5V (1…29.9V) ±3% ±3dgt (30…1500V) |
LCD Overrange indication | “OL” |
Current Test | 0.1…200A AC(+/-3%+5Dgt) |
Resolution 0.1A | |
Frequency range 45…65Hz | |
Safety current | Is<3.5mA (at 1000V AC), <6mA at 1500V DC |
Measurement Duty | 30 s ON, 240s OFF |
Internal battery consumption | approx. 120mA |
Single-pole phase test voltage range | 100…1000V AC (50/60Hz ) |
Phase rotation test | 170…1000V phase-to-phase, AC (40...70Hz) |
Continuity test | 0…500 kΩ + 50% |
Resistance measurement | 0…100 kΩ; accuracy: ±5%±10dgt@25°C; resolution: 1 Ω (1-2000 Ω) 1 kΩ (2-100 kΩ) |
Frequency measurement | 1…800 Hz ±5%±5dgt; resolution: 1Hz |
NCV Test | 100...1000V AC (50/60Hz) |
Battery | 3V (IEC LR03 1.5V x 2) |
Temperature | -15…55°C operation; -20…70°C storage; No condensation |
Humidity | max. 85% RH |
Altitude | up to 2000m |
Overvoltage | CAT IV/600V, CAT III/1000V |
Standard | EN/IEC 61243-3:2014 |
Protection | IP64 |
Output voltage | 180V in to 6.8 Ω , 720V - 820V in to 10M Ω |
Operating conditions | -10 to 40 C, 70% RH |
Dimensions | W65 x H120 x D45mm |