Kewtech EZYPAT PAT Tester
The Kewtech EZYPAT PAT Tester is battery operated and capable of performing up to approximately 1400 tests before the batteries begin to expire. This PAT tester has been optimised to perform manual dead tests on Class I and Class II appliances as well as extension leads. The Kewtech EZYPAT is the simplest model in the range; for more information on the models within this range, please see the comparison table in the 'Technical Specifications'.
Testing Capabilities
- Appliance status pre-check (determines whether the appliance under investigation is on or off)
- Quick check continuity (1 second)
- 5-second continuity check
- Insulation tests (user selectable 250V DC or 500V DC)
- Substitute leakage test (user selectable limits)
- Extension lead test
- 200mA earth test
The Kewtech EZYPAT’s inclusion of a low current earth continuity test and 250V insulation test ensures that it is IT safe, whilst its Test Lead Null setting ensures that the user is able to attain accurate insulation measurements which are unaffected by the resistance of the test leads.
In addition to this, it features clearly labelled function buttons which allow the user to run automatic test sequences for Class I and Class II appliances, as well as extension cables. The results of all these tests are indicated via the EZYPAT's large, easy-to-read, backlit display, which turns green for PASS and red for FAIL.
This product’s convenience is further improved by its lightweight and ergonomic design; extension lead adapter and earth continuity test lead with probe and crocodile clip, these features and accessories ensure that the EZYPAT is suitable for use in a variety of environments and can be easily adapted to perform multiple tests.
Overall it is versatile, convenient and efficient, the ideal portable appliance tester for those who wish to perform manual dead tests on items that do NOT require a power supply to switch on, i.e. appliances WITHOUT electronic on/off switches.
(PLEASE NOTE that the EZYPAT PLUS, available here, is suited to testing items (such as computers and TVs) with electronic on/off switches and which do require a power supply to start up.)
Videos
Key Features
- Battery operated PAT Tester ideal for performing manual dead tests on appliances that do not require a power supply to switch on (WITHOUT electronic on/off switches)
- Can perform up to approximately 1400 tests before the batteries expire
- Appliance status pre-check (determines whether the appliance under investigation is on or off)
- Quick check continuity (1 second)
- 5-second continuity check
- Insulation tests (using either 250 or 500V DC)
- Substitute leakage test
- Extension lead test
- 200mA earth test
- Low current earth continuity and 250V insulation test make the EZYPAT IT safe
- Test Lead Null setting
- Automatic test sequences for Class I and Class II appliances and extension leads
- Large, easy-to-read, backlit display
- Red and green PASS/ FAIL screens
- Lightweight, ergonomic design
- Extension lead adapter
- Earth continuity test lead, probe and crocodile clip
- Selectable insulation test voltages: 250V DC and 500V DC
- Selectable substitute leakage test limits
- Can be used with Kewtech's KEWPAT App to collect data and create reports manually
- The Kewtech KEWPAT App is available for free download from the App Store (iOS) and Google Play (Android)
What’s Included?
- Kewtech EZYPAT PAT Tester – Battery Operated
- EZYLEAD Extension Lead Adapter
- EZYEARTH Earth Continuity Test Lead with Probe and Crocodile Clip
- Carry Bag with Strap
- Quick Start Guide
Kewtech PAT Tester Comparison
EZYPAT | EZYPAT Plus | SMARTPAT | |
---|---|---|---|
200mA continuity Test | Yes | ||
250V Insulation Test | Yes | ||
500V Insulation Test | Yes | ||
Substitute Leakage Measurement | Yes | ||
Polarity Check | Yes | ||
110V Load and Run Test | - | Yes | |
230V Load and Run Test | - | Yes | |
Portable RCD Test | - | - | Yes |
Compatible with KEWPAT App | - | Yes | |
Customisable Test Sequences | - | - | Yes |
Enjoy peace of mind with a Free PAT Card included with every purchase. Keep track of essential safety checks effortlessly!
- Essential Bundle (1,000 Labels & Logbook) - PAT-ESSENTIAL-BUNDLE, typically £77.98
- IT Bundle (3 x IEC Adaptors & Socket Tester) - PAT-IT-BUNDLE, typically £46.96
- Tolsen Tools 7-Piece Insulated Screwdriver Set - TS-9900012, typically £16.99
Kewtech EZYPAT/ SMARTPAT Comparision Table
Specification | EZYPAT | EZYPAT PLUS | SMARTPAT |
200mA Continuity Test | X | X | X |
250V Insulation Test | X | X | X |
500V Insulation Test | X | X | X |
Substitute Leakage Test | X | X | X |
Polarity Check | X | X | X |
110V Load and Run Test | X | X | |
230V Load and Run Test | X | X | |
Portable RCD Test | X | ||
Compatible with KEWPAT App | X | ||
Customisable Test Sequences | X |
Kewtech EZYPAT PAT Tester – Battery Operated Technical Specifications
Protective Conductor Resistance Test | |
Measuring Range | 0.00 - 20.00 Ω (NULL value inc)* |
Over-range Indication | > 20.00 Ω |
Resolution | 0.01Ω |
Open-circuit Voltage | 5 V ±0.4 V DC |
Measuring Current | 200 mA DC (nominal value) |
Accuracy | ±3%rdg ±5dgt |
* Resistances exceeding 3 Ω cannot be cancelled by NULL function. |
|
Insulation | |
Measuring Range | 0.00 - 20.00 MΩ |
Over-range Indication | > 20.00 MΩ |
Resolution | 0.01 MΩ |
No-load Voltage | 250V : 250 V DC +20%, -0% |
500V: 500 V DC +20%, -0% | |
Short-circuit Current | 1.5 mA DC or less |
Rated Current | 250V: 1 -1.2 mA with a load of 0.25 MΩ |
500V: 1 to 1.2 mA with a load of 0.5 MΩ | |
Accuracy | ±2%rdg±3dgt |
Substitute Leakage | |
Measuring Range | 0.10 - 12.00 mA rms |
Over-range Indication | > 12.00 mA |
Resolution | 0.01mA |
Open-circuit Voltage/ Frequency | 30 V ±5 V rms / 50 Hz ±5% |
Measuring Circuit | 1.2 mA AC ±0.5 mA (when measuring 12.00 mA) |
Accuracy | ±3%rdg±5dgt |
Insulation Testy Between L-N | |
Open-circuit Voltage | 4.5 V ±0.5 V DC |
Criteria of Judgement |
100 kΩ ±20 kΩ or less: LCD shows “<0.10 MΩ” and the measurement is halted. |
Physical Specifications | |
Safety |
IEC/EN61010-1 CAT II 300V-instrument |
EMC | EN61326-1, 2-2 |
Possible number of |
Approx. 1400 times |
Boxed Weight | 1.61Kg |
Boxed Dimensions (L x W x D) | 261 x 140 x 130mm |
Reviews
SKU | EZYPAT |
---|---|
Manufacturer Part Code | EZYPAT |
Model Ref | EZYPAT |