Built specifically for the UK market, this two-pole voltage detection device includes GS38 compliant probe tips and is a great tool quickly and easily evaluating overall voltage levels.
The main body of this tester features oversided LED indicators that show the presence of voltage (both AC/DC) up to a high point of 690V. The device can also be used to carry out continuity testing with clear audible tone, single pole phase testing, polarity indication, phase rotation testing and also performs a self diagnostic test to ensure efficiency at all times.
The 1780 is also built to be compliant with IEC 61243-3, IEC 61010-1 and CAT IV 600.V
Kewtech KT1780 Two-Pole Voltage Detector Key Features
- Dual probe system with GS38 compliant probe tips
- Designed in line with international safety standards
- Clear, bright LED indicators of measurement parameters
- Measures AC and DC voltage from 12-690V
- Continuity testing
- Clear audible tone
- Single pole phase testing
- Polarity indication
- Phase rotation testing
- Self diagnostic testing
- Double moulded surface is designed to make holding the tester comfortable
- Auto power on/off
- Pen torch included for illuminating darkened environments
- IP65 protection
Full List of Products Included
- Kewtech 1780 Two-Pole Voltage Detector
- Built-In Test Leads
- Batteries
- Printed Instruction Manual with Certificate of Conformity
Kewtech 1780 Technical Specifications
Voltage Range | 12-690V AC/DC |
Peak Current | Is <3.5mA (at 690V) |
Internal Battery Consumption | Approx. 80mA (Battery 3V, measuring 690V AC) |
Battery Life | Approx 1000 Operations (30s ON/240s OFF duty) |
Nominal Voltage | 12/24/50/120/230/400/690V, AC (16-400Hz), DC (±) |
Tolerance (Threshold Voltage) | Light on at more than : 7 ± 3V (12V LED), : 18 ± 3V (24V LED), : 37.5 ± 4V (50V) 75%±5% of nominal voltage, (120/230/400/690V LED) |
Response Time | <0.6s at 100% of each nominal voltage |
Single Pole Phase Test Voltage Range | 100~690V AC (45~100Hz) |
Phase Rotation Test System | Three-phase 4-wire system 200~690V phase-to-phase (100~400V earth-to-phase) AC 50/60Hz |
Continuity Detection Range | 0~400K Ω + 50% (23 ± 5ºC) |
Continuity Test Current | Approx. 1.5μA (battery 3V, 0 Ω) |
Internal Battery Consumption | Approx. 80mA (battery 3V, 0 Ω) |