Kane 988 Industrial Flue Gas Analyser
The Kane 988 Industrial Flue Gas Analyser is a unique FGA featuring the latest technology. It can accommodate up to eight sensors. As standard, this flue gas analyser can measure oxygen (0-21%), hydrogen-compensated carbon monoxide (0-10 000ppm), carbon monoxide (0-10%), hydrocarbons (0-5000ppm), and carbon dioxide (0-20%). Optional nitric oxide, nitrogen dioxide, sulphur dioxide, and hydrogen sulphide sensors may be added to the Kane 988 Industrial Flue Gas Analyser.
Integrated wireless connectivity allows the Kane 988 Industrial Flue Gas Analyser to connect with other KANE-Link-enabled instruments. This is useful when balancing heating systems, checking air conditioning units or kitchen fans, and measuring CO levels.
The Kane 988 Industrial Flue Gas Analyser is a comprehensive flue gas analyser suitable for industrial applications.
Applications
- Install, commission & service any heating & hot water system using any fossil, biomass & HVO fuel
- Optional environmental sensors test to local regulations
- Accurate NO2 & SO2 measurements with optional KANE-GCU gas conditioning unit
- Safety checks - CO in rooms & around appliances
- Combustion performance & efficiency tests
- Flue draught & gas pressure / system tightness tests
- Flow & return, air flow & air quality tests
- Air conditioning & refrigeration superheat & subcool tests
Measuring Capabilities
- O2 to 21% ppm to 0.01% resolution
- CO to 10,000ppm H2compensated & 100,000ppm / 10%
- CO2 to 21% with 40% over range
- HC to 5,000ppm
- Temperature - inlet / flue gas / differential / ambient / flow & return
- High accuracy differential pressure meter +/- 160mbar
- Velocity measurement to 30m/s with optional pitot tube
- NO to 5,000ppm - option
- NO2 to 1,000ppm - option
- SO2 0-5,000ppm - option
- H2S to 200ppm - option
Calculates
- CO/CO2 ratio
- Combustion efficiency,
- Excess air / Lambda
- NOx - if NO fitted
- Superheat & Subcool
Fuel Types
- Natural Gas x2 & Town Gas
- LPG, Biogas & Kinsale Gas
- Butane, Propane & Gascor
- Light oil & Heavy oil
- Coke, Coal & Anthracite
- Up to 5 user fuels
What’s Included?
- Kane 988 Industrial Flue Gas Analyser
- CP2T Combustion Probe
- CU12VDCA21 Charger
- 14102/2 Large Carry Bag
- MSC00017 Handset Pouch
- 15mm + 22mm AutoCut Pipe Cutters & Flue Cleaning Brush Set - FGAPROMO2, typically £45.00
Range | Resolution | Accuracy | |
---|---|---|---|
Temperature Measurement | |||
Flue Temperature | 0 - 600°C | 0.1°C | ±0.5°C |
Inlet Temperature (Internal Sensor) | 0 - 50°C | 0.1°C | ±1°C |
Inlet Temperature (External Sensor) | 0 - 600°C | 0.1°C | ±0.5°C |
Flue Gas Measurement | |||
Oxygen | 0 - 25% | 0.01% | ±0.3% Volume |
Carbon Monoxide H2 Compensated | 0 - 10,000ppm | 1ppm | ±5ppm < 100ppm +20ppm <400ppm ±5% >400ppm - 2000ppm +10% >2000ppm - 10,000ppm |
Carbon Monoxide High Range | 0 - 10% | 0.01% | ±5% of reading |
Nitric Oxide (optional) | 0 - 5000ppm | 1ppm | ±5ppm < 100ppm +5% >100ppm |
Nitrogen Dioxide (optional) | 0 - 1000ppm | 1ppm | ±5ppm < 100ppm +5% >100ppm |
Sulphur Dioxide (optional) | 0 - 5000ppm | 1ppm | ±5ppm < 100ppm +5% >100ppm |
Hydrogen Sulphide (optional) | 0 - 200ppm | 1ppm | ±5ppm < 100ppm +5% >100ppm |
Carbon Dioxide | 0 - 40% | 0.10% | ±5% of reading |
Hydrocarbons | 0 - 5000ppm | 1ppm | ±5% of reading |
Pressure Measurement | |||
Pressure (Differential) | ±160mbar | 0.1mbar | ±0.5% FSD |
Velocity | 0-30m/s | 1m/s | ±0.5% FSD |
Calculations | |||
CO/CO2 Ratio | 0 - 0.9999 | 0.0001 | ±5% of reading |
Efficiency (Net or Gross) | 0 - 99.9% | 0.10% | ±1% of reading |
Efficiency High (C) | 0 - 119.9% | 0.10% | ±1% of reading |
Excess Air | 0 - 119.9% | 0.10% | ±0.2% of reading |
Pre-programmed Fuels | |||
UK, USA & France | Natural Gas, Propane, Butane, LPG, Light Oil, Digester Gas & Wood Pellets | ||
European | Natural Gas, Light Oil, Bio Oil, Coke, LPG, Wood, Town Gas, Butane & Propane | ||
Battery Life | >5 hours (continuous with pump on) | ||
Certification | The KANE988 is independently tested & certified to EN 50379 Parts 1-2 in accordance to the 1st German Federal Emission Control Ordinance (Bim5chV) Pending |
||
Operating Conditions | |||
Temperatures | 0 - 50°C | ||
Humidity | 15 to 90% RH, (non-condensing) | ||
Power Supply | Rechargeable batteries, 12v DC @ 2A Charging | ||
Physical Characteristics | |||
Weight | Approx. 1.2kg | ||
Dimensions | L: 240mm x H: 165mm x W: 65mm |
Reviews
SKU | KANE988 |
---|---|
Manufacturer Part Code | KANE988 |
Made to Order item: This item is made-to-order with a lead time once the order is placed. Once an order is placed it cannot be cancelled or returned unless the unit is found to be faulty.