Free Beanie Hat. Spend £250+ (ex VAT) View
All HD Electric Company Products

HD Electric (FACT) Feeder Ammeter Clear Test

SKU
HD-FACT-1
Rating:
0%
(0)
Call For Pricing

We require additional information before you purchase this product

or Call 01642 931 329 to discuss product options

HD Electric (FACT) Feeder Ammeter Clear Test

The HD Electric Feeder Ammeter Clear Test (FACT) is used to detect ground connections prior to re-energising distribution feeder circuits.

It is a requirement that when distribution feeder circuits are taken out of work for maintenance bolted grounds are installed on all three phases at every location where work is being performed. Once this requirement has been fulfilled the engineer is able to replace cross-arms, insulators and/or transformers. When work has been completed the added grounds must be removed prior to circuit re-energisation; failure to remove grounds can cause damage at the location or at the connected substation. The HD Electric Feeder Ammeter Clear Test can be used to check that absolutely all of the added ground connections have been removed.

The HD Electric Feeder Ammeter Clear Test is applied before substation circuit breakers have been closed and can be connected along the feeder circuit or at the substation.

The HD Electric Feeder Ammeter Clear Test energises the feeder circuit at a low secondary voltage and measures the resulting current flow. This automatic test sequence steps through and tests all three phases in sequence; it also performs an automatic self-test prior to testing the circuit. Its internal diagnostics confirm correct operation.

Via the LCD display, the user can see the condition of each phase and any detected shorts. The HD Electric Feeder Ammeter Clear Test is able to differentiate between currents drawn by transformers and currents caused by remaining grounds. Detected ground connections are indicated on the LCD display. In addition to this, the HD Electric Feeder Ammeter Clear Test’s display indicates the ammeter’s current and shows instructions and messages, adding to its ease of use.

As well as detecting connected grounds, the HD Electric Feeder Ammeter Clear Test will automatically detect incorrect polarity.

As the HD Electric Feeder Ammeter Clear Test is able to differentiate between currents drawn by grounds and currents drawn by transformers, it is possible to use this instrument to test circuits with equipment such as transformers, capacitor banks and lightning arresters still installed. Furthermore, as the HD Electric Feeder Ammeter Clear Test only requires a 120V AC 60Hz power supply and has a limited current (5A output) it can be safely connected to any grounded or un-grounded circuit. Also adding to the HD Electric Feeder Ammeter Clear Test’s practicality is its portable, one-person design.

The HD Electric Feeder Ammeter Clear Test is an ergonomic, easy-to-use and effective instrument designed to facilitate the clear, simple and efficient detection of ground connections. It is ideal for preventing transformer damage, blown fuses and fault currents caused by re-energising grounded distribution feeder circuits.

HD Electric (FACT) Feeder Ammeter Clear Test Key Features

  • Detect ground connections prior to re-energising feeder circuits
  • Can be applied anywhere along the feeder circuit or at the substation
  • Energises the feeder circuit at a low secondary voltage
  • Measures the resultant current flow
  • Automatic test sequence steps through and tests all three phases in sequence
  • Performs a self-test as part of the automatic test sequence
  • Internal diagnostics confirm correct operation
  • See the condition of each phase and detected shorts via the LCD display
  • Able to differentiate between currents caused by remaining ground connections and currents drawn by transformers
  • Indicates detected grounds on the LCD display
  • The LCD display also indicates the ammeter’s current
  • View instructions and messages via the LCD display
  • Easy to use
  • Automatically detects incorrect polarity
  • No need to disconnect transformers, capacitor banks and lightning arresters 
  • Requires a 120V AC 60Hz power supply
  • Limited current: 5A output
  • Can be safely connected to any grounded or un-grounded circuit
  • Portable, one-person design
  • An ergonomic, easy-to-use and effective instrument designed to facilitate the clear, simple and efficient detection of ground connections
  • Prevent transformer damage, blown fuses and fault currents caused by re-energised grounded distribution feeder circuits

What’s Included?

  • HD Electric (FACT) Feeder Ammeter Clear Test
HD Electric (FACT) Feeder Ammeter Clear Test - Datasheet Datasheets HD Electric (FACT) Feeder Ammeter Clear Test - Instruction Manual Manuals & Guides

Reviews

Additional Information
SKU HD-FACT-1
Manufacturer Part Code FACT-1
Model Ref HD Electric FACT-1