Fluke VR1710 Single-Phase Voltage Quality Recorder
Suitable for use on single-phase systems, the Fluke VR1710 is connected directly to a system and monitors voltage trends, dropouts and overall levels of power quality. It's an ideal fault finding device and allows easy determination of what is causing problems with voltage in single-phase installations.
The VR1710 plugs directly into a mains power socket, making it extremely easy to use. It isn't just a single measurement instrument either; the VR1710 is designed to continuously monitor the voltage on a system with no gaps, allowing the user to get the full picture and accurate measurements of voltage over a time period. This recorder can be used to record voltage on a system from 1 day up to 339 days and is compatible with the included PowerLog software package for download and analysis of testing data captured over a time period.
When capturing, this voltage quality recorded will store MIN, MAX, and average RMS values as well as actual transient display with time stamps, allowing the user to easily determine what happened at exactly what time. It can also be used to record flicker to EN 61000-4-15 and can also store individual harmonic and THD values with trend data.
Key Features
- Plugs directly into a mains socket and monitors voltage quality
- Monitor trends, dropouts and power quality
- Easy to use
- Continuous recording
- Graphical summary of data and quick overview of problems
- Records for up to 339 days
- MIN/MAX/AVG value calculation
- Actual transient display
- Flicker recording
- Individual harmonics and THD value recording
- Statistical analysis of single phase voltage events
- Compatible with PowerLog software (included)
What Accessories are Included?
- Fluke VR1710 Single-Phase Voltage Quality Recorded
- USB Cable
- PowerLog Software Package on CD
- Universal Power Cord Adapters
Fluke VR1710 Technical Specifications
Operating Voltage | 70V to 300V |
MIN/MAX/AVG RMS Value | Resolution 0.125V |
Number of Events | 175000 |
Dips/Interruptions | Yes |
Time Resolution | 5ms |
Voltage Resolution | 0.125V |
Over-Voltages | Yes |
Frequency | Yes |
Harmonics Measurements | EN 61000-4-7 (up to 32nd) |
Flicker Measurement | EN 61000-4-15 |
Number of Recording Channels | 1 Phase to Neutral 2 Phase/Neutral to Ground |
Recording Time | 1 day to 339 days depending on average time from 1 second to 20 minutes |
Transients | Yes |
Frequency Range | 50Hz ± 1Hz and 60Hz ± 1Hz |
Safety Category Rating | CAT II 300V |
Reviews
SKU | Fluke VR1710 |
---|---|
Manufacturer Part Code | 3030923 |
Model Ref | Fluke VR1710 |
Country of Origin | United States |