This version of the Fluke Norma 5000 comes as standard with 3 x PP54 power phase input modules, an IEEE488/Ethernet interface and analogue/digital output channels.
Fluke's Norma 5000 is one of the most advanced power quality analysers on the market. With extremely high bandwidth, the latest measurement technology and several useful advanced features built-in, these power instruments are ideal for use on motors, inverters, lighting, power supplies, transformers, automotive components and wherever else power quality needs to be quantified.
The Fluke Norma 5000 is built with high bandwidth built-in, making it suitable for the development of frequency converters and lighting equipment. It can test all aspects of power, including voltage, current and power harmonics to the 40th, can perform FFT analysis with vector diagram display and even includes an integrated digital oscilloscope for simultaneous display of up to 3 measured values with quick view of waveform/distortion.
This power analyser can interface directly with a PC for further analysis of data using Fluke's included software package.
Spend £150+ (Ex VAT) on any qualified Fluke or Beha-Amprobe product(s) and claim a free tool of your choice from the list at Fluke Promotion. Valid February 17 2025 - July 31 2025.
Claims are made direct to Fluke. For more information and terms and conditions, visit Fluke Promotion.
General
Basic Functions
Ambient Conditions
Frequency and Synchronization
Standards and Safety
Power Phases
The Fluke Norma 4000 Power Analyzer can be equipped with up to three power phases and the Fluke Norma 5000 Power Analyzer can be equipped with up to six power phases. Users can select the power phase best suited for their application. Specifications vary depending on the model of the power phase. Each modular plug-in power phase consists of a voltage and a current measurement channel. Each measuring channel is available for each basic unit, however only one kind of channel can be used per unit. Check standard configurations.
Power Phase Channels
PP42 Accuracy: 0.2% (0.1% rd + 0.1 % rg) Current range: 20 A Sampling rate: 341 kHz Bandwidth: 3 MHz
PP50 Accuracy: 0.1% (0.05% rd + 0.05 % rg) Current range: 10 A Sampling rate: 1 MHz Bandwidth: 10 MHz
PP54 Accuracy: 0.1% (0.05% rd + 0.05 % rg) Current range: 10 A Sampling rate: 341 kHz Bandwidth: 3 MHz
PP64 Accuracy: 0.03% (0.02% rg + 0.01% rg) Current range: 10 A Sampling rate: 341 kHz Bandwidth: 3 MHz