All Fluke Products

Fluke i2000 flex AC Flexible Current Clamp (2000 A)

SKU
FLUCMA12
Rating:
0%
(0)
Reward Points
:
345
£414.00 £345.00
Free UK Delivery*
Advice & Support Call 01642 931329 or contact us
Price Match We won't be beaten, let us know
Fluke i2000 flex AC Flexible Current Clamp 2000 A

The i2000 flex is a flexible AC current probe recommended for current measurements on large and difficult to reach conductors.

It measures up to 2000A AC. For use with an oscilloscope, power analyser, scopemeter or digital multimeter, a BNC to Banana adaptor is included.

Fluke i2000 Flex AC Current Clamp Adaptor features:

mV Output
AC Current Max: 2000A
Max Conductor Diameter: 170mm

Specifications

  • Current ranges 20 A 200 A 2000 A AC rms
  • Output sensitivity (AC-coupled) 100 mV 10 mV 1 mV 1 mV per A
  • Load impedance 100 kΩ minimum
  • Accuracy at +25 °C ± 1 % of range (45 Hz to 65 Hz)
  • Linearity 10 % to 100 % of range ± 0.2 % of reading
  • Noise 8 mV ac rms (30 A) 2 mV ac rms (300 A, 3000 A)
  • Frequency range 10 Hz to 20 kHz (-3 dB)
  • Phase error < ± 1 º (45 Hz to 65 Hz) ± 10 º (at 20 kHz)
  • Position sensitivity with cable > 25 mm from the coupling ± 2 % of range
  • External field with cable > 200 mm from the head ± 1 % of range
  • Power supply 2 x AA/MN 1500/LR6 Alkaline, 200 hours, low battery indicator
  • Temperature Coefficient ± 0.08% of reading per°C
  • Working voltage see Safety standards section 600 V AC rms or DC
  • Head Circumference 610 mm (24 in)
  • Head cable diameter 14.3 mm (0.56 in)
  • Head bend radius 38.1 mm (1.5 in)
  • Cable length (head to electronics) 2 m (6.56 ft)
  • Output connection Molded 4 mm safety plugs (not integrated)
  • Operating temperature range 0 °C to +70 °C (32 °F to 158 °F) (head and electronics)
  • Storage temperature range -40 °C to +105 °C (-40 °F to 221 °F) (head) -20 °C to +85 °C (-4 °F to 185 °F) (electronics)
  • Operating humidity 15 % to 85 % (non-condensing) Weight 180 g (6.34 oz) (head) 190 g (6.70 oz) (electronics)
  • Safety standards EN 61010-1: 2001 EN 61010-2-032: 2002 EN 61010-031: 2002 600 Vrms, Category III, Pollution Degree 2 Use of the probe on uninsulated conductors is limited to 600 V ac rms or dc and frequencies below 1 kHz.
  • EMC standards EN 61326: 1998 +A1, A2, & A3
  • Dimensions HxWxD 116 mm x 68.5 mm x 30 mm (4.56 in x 2.69 in x 1.18 in)
Fluke i2000 Flexible Current Clamp - Datasheet Datasheets Fluke i2000 Flexible Current Clamp - User Manual Manuals & Guides

Reviews

Additional Information
SKU FLUCMA12
Manufacturer Part Code 2584912
Model Ref i2000 flex
Country of Origin China