The Fluke 710 mA Loop Valve Tester with HART can be used to test complex smart valves in order to verify correct functionality or identify and locate faults. The Fluke 710 mA Loop Valve Tester features a number of integrated and easy-to-run test procedures; this instrument will also quick-check the results of each test, providing the user with an indication as to whether the valve is in good, marginal or bad health. The quick-check feature allows the user to determine, in the field, whether further maintenance is required thereby increasing repair efficiency, reducing downtime and increasing productivity. For a quick introduction to the Fluke 710 mA Loop Valve Tester with HART, please see the following video.

Introducing the Fluke 710 mA Loop Valve Tester

Testing Valves

The Fluke 710 mA Loop Valve Tester verifies the functionality of valves by sourcing a current between 4 and 20mA to the smart valve in order to move the apparatus; it simultaneously interprets the valve’s HART feedback signal, using the HART communication function, allowing it to ascertain whether the valve is moving to the expected position.

Additionally, the Fluke 710 mA Loop Valve Tester’s HART communication protocol enables it to measure the pressure delivered from the valves internal I/P (the component that moves the valve).

The Fluke 710 mA Loop Valve Tester includes a number of integrated test procedures allowing the user to tailor the instrument to the application. These test procedures automatically increase and change the mA signal whilst monitoring the HART position and pressure feedback; the Fluke 710 mA Loop Valve Tester includes the following test procedures.

Step Test

Alters the mA signal in steps whilst monitoring and evaluating the valve’s response to the changes in the mA signal.

Fluke 710 mA Loop Valve Tester - Step Test Demo

Speed Test

This test can be used to check the length of time it takes for the valve to open and close.

Fluke 710 mA Loop Valve Tester - Speed Test Demo

Bump Test

Optimised for testing valves whilst they are in use; this procedure checks the valves over a portion of their range.

Fluke 710 mA Loop Valve Tester - Bump Test Demo

Signature Test

The Fluke 710 mA Loop Valve Tester ramps the mA signal from 4 to 20 mA and then back down to 4mA; it simultaneously records the position of the valve and/or the pressure that moves the valve.

Fluke 710 mA Loop Valve Tester - Signature Test Demo

Manual Testing

This function allows the user to alter the mA signal as required and view the HART position and/or pressure information.

Fluke 710 mA Loop Valve Tester - Manual Test Demo

HART Communication

Due to the inclusion of an integrated HART modem, the Fluke 710 mA Loop Valve Tester can also communicate a range of HART commands improving the ease, efficiency and effectiveness of testing. The Fluke 710 mA Loop Valve Tester with HART is able to issue the following commands:

  • Read sensor PV information
  • Read PV output information
  • Read and write the PV unit type, tag ID name, descriptor, and message
  • Read and write PV upper and lower ranges
  • Engage/ disengage fixed current mode
  • Set zero offset
  • Trim DAC zero (mA output 4 mA)
  • Trim DAC gain (mA output 20 mA)

The Fluke 710 mA Loop Valve Tester is also able to issue an ‘autotrim of valve controller’ command, which is unique to control valves.

Measurements

The Fluke 710 mA Loop Valve Tester is accurate to 0.01% of the measurement or source value and has a resolution of 1µA on mA ranges and 1mV on voltage ranges.

Furthermore, in addition to the aforementioned test procedures, the Fluke 710 mA Loop Valve Tester includes the following measurement features:

  • Integrated and user-selectable 250Ω resistor for HART communications
  • 24V DC loop power with an mA measurement mode (-25% to 125%)
  • mA loop calibrator functions: mA source, mA simulate, mA read, mA read/loop power, and volts read

HART data and mA loop measurements are logged to the Fluke 710 mA Loop Valve Tester’s integrated memory. It has the capacity to store up to 4910 records or 99 logging sessions. It can be set to log measurements at intervals ranging from once every second to once every sixty seconds.

When saving data, the Flike 710 Tester includes the mA measurement and all four process variables in each record. The data logging feature can be used to record HART and mA data from a particular transmitter, making this function especially useful for troubleshooting and loop tuning applications.

Results recorded to the Fluke 710 mA Loop Valve Tester may be uploaded to the included ValveTrack™ Analysis Software.

ValveTrack™ Analysis Software

The included ValveTrack™ Analysis Software allows the operator to upload data recorded to the Fluke 710 mA Loop Valve Tester to a PC. Once uploaded, he/she is able to conduct further analysis as well as export and compare data. The user is able to perform the following tasks:

  • Upload data
  • Print data
  • Plot the results of valve tests
  • Compare the uploaded results with recent test results
  • Export data in a CSV file for further analysis in Microsoft Excel
  • Data can also be outputted in a .txt format
  • View the test history of a valve using its HART Tag ID
  • Upload the HART configuration of up to twenty HART devices

Ergonomic and Intuitive Design

It is simple and quick to configure the Fluke 710 mA Loop Valve Tester to perform the correct tests. All measurements are conducted via a two-wire connection to the equipment-under-investigation and relevant procedures and/or measurement functions are accessible using the quick-set knob and intuitive user interface. Please see the video below for further information regarding how to program this tester.

Fluke 710 mA Loop Valve Tester - Product Configuration Demo

More practically, the Fluke 710 mA Loop Valve Tester features a compact design ensuring that it is easy to hold and carry, whilst its rugged casing protects it from harsh environments.

To preserve battery life and thereby reduce downtime, the Fluke 710 mA Loop Valve Tester includes an Auto Shutdown function.

The Fluke 710 mA Loop Valve Tester with HART is a comprehensive, easy-to-use, and durable diagnostic and calibration tool suitable for checking complicated smart control valves.

Fluke 710 mA Loop Valve Tester with HART Key Features

  • Test complex smart valves to verify correct functionality or identify faults
  • Includes a number of integrated and easy-to-run test procedures
  • Quick-checks the results of each test: good, marginal or bad
  • Quick-checks allow the user to determine in real-time whether further maintenance is required
  • Increase repair efficiency, decrease plant downtime, thereby improving productivity
  • Sources a 4 to 20mA current to the valve in order to move it
  • Interprets the valve’s HART feedback signal using the HART communication function
  • Able to determine whether the valve is moving to the expected position
  • HART communication protocol for measuring pressures delivered from the valve’s I/P
  • Test procedures automatically increase and change the mA signal whilst monitoring the HART position
  • Step Test: alters the mA signal in steps
  • Speed Test: checks the length of time it takes for the valve to open and close
  • Bump Test: tests the valve over a portion of its range
  • Signature Test: ramps the signal from 4 to 20mA and then back to 4mA
  • Manual Testing: alter the mA signal as required
  • Integrated HART modem allows the tester to communicate a range of HART commands
  • Read sensor PV information
  • Read PV output information
  • Read and write the PV unit type, tag ID name, descriptor, and message
  • Read and write PV upper and lower ranges
  • Engage/ disengage fixed current mode
  • Set zero offset
  • Trim DAC zero (mA output 4 mA)
  • Trim DAC gain (mA output 20 mA)
  • Autotrim of valve controller – unique to control valves
  • Accuracy: 0.01% of the measurement or source value
  • Resolution: 1µA on mA ranges and 1mV on voltage ranges
  • Integrated and user-selectable 250Ω resistor for HART communications
  • 24V DC loop power with an mA measurement mode (-25% to 125%)
  • mA loop calibrator functions: mA source, mA simulate, mA read, mA read/loop power and volts read
  • HART data and mA measurements are logged to the tester’s internal memory
  • Store up to 4910 records or 99 logging sessions
  • Programmable logging intervals ranging from every second to every minute
  • Records include the mA measurement and all four process variables
  • Data logging feature can be used to record HART and mA data from a particular transmitter
  • Data logging feature is particularly useful for troubleshooting and loop tuning applications
  • Logged results can be uploaded to the included ValveTrack™ Analysis Software
  • Use the ValveTrack™ Analysis Software to upload data to a PC
  • Analyse, plot, export, organise and print uploaded data using the ValveTrack™ Analysis Software
  • View the test history of a valve using its HART Tag ID and compare uploaded test results with recent test results via the software
  • Upload HART configurations of up to twenty HART devices using the included software
  • Export data in a CSV or txt file using the included software
  • Simple two-wire connection for performing tests
  • Quick-set knob
  • Intuitive user interface
  • Compact, rugged design
  • Auto Shutdown function for preserving battery life
  • A comprehensive, easy-to-use and durable diagnostic and calibration tool
  • Suitable for testing complicated smart control valves

What’s Included?

  • Fluke 710 mA Loop Valve Tester with HART
  • Stackable Test Lead Set
  • Extended Tooth Alligator Clip Set
  • TP220 Test Probes
  • AC280 SureGrip™ Hook Clips
  • Lemo to USB Cable
  • ValveTrack™ Analysis Software (free download)
  • Softcase
  • Six AAA Batteries (installed)
  • Product Manual CD-ROM
  • Quick Reference Guide
  • Safety Information

Fluke 710 mA Loop Valve Tester with HART Technical Specifications 

Functions mA source, mA simulate, mA read, mA read/loop power, and volts read.
Ranges mA (0 to 24 mA) and Volts (0 to 30 V DC)
Resolution 1 µA on mA ranges and 1 mV on voltage range
Accuracy 0.01% ± 2 counts, all ranges (@ 23 °C ± 5 °C [73.4 °F ± 41 °F])
Operating temperature range -10°C to 55°C (14°F to 131°F)
Humidity range 10 to 95% non-condensing
Stability 20 ppm of F.S. /°C from -10°C to 18°C and 28°C to 55°C
Display 128 x 64 pixels, LCD Graphic w/backlight, .34 high digits
Power 6 AAA alkaline
Battery life 40 hours continuous use (measure mode using)
Loop compliance voltage 24 V DC @ 20mA
Over-voltage protection 240 V AC
Overload current protection 28 mA DC
EMC EN61326 Annex A (Portable Instruments)
Dimensions (L x W x D) 15 x 9 x 3 cm (6 x 3.6 x 1.3 in)
Weight 0.3 kg (9.5 oz)
Warranty Three year
Accessories related to this product:
Fluke 710 mA Loop Valve Tester with HART - Datasheet Datasheets Fluke 710 mA Loop Valve Tester with HART - Calibration Manual Manuals & Guides Fluke 710 mA Loop Valve Tester with HART - User Manual Manuals & Guides Fluke 710 mA Loop Valve Tester with HART - Quick Start Guide Manuals & Guides Fluke 710 mA Loop Valve Tester with HART - Safety Information Notes & Other Fluke 710 mA Loop Valve Tester with HART - Security Procedures Notes & Other