All Fluke Products

Fluke 393 FC CAT III 1500V DC True-RMS Clamp Meter with iFlex & Fluke Connect

SKU
FLUKE-393
Rating:
0%
(0)
Reward Points
:
534
£534.00 £445.00
Free UK Delivery*
Choose a Special Offer
  • Fluke PVLEAD3 - Set of black and red solar PV MC4 Solar Clamp Meter Test Leads
    Fluke PVLEAD3 - Set of Black and Red Solar PV MC4 Solar Clamp Meter Test Leads
    FREE
    £65.00
  • Fluke PVLEAD3 - Set of Black and Red Solar PV MC4 Solar Clamp Meter Test Leads SKU: (PVLEAD3)
    FREE
    £65.00
    Fluke PVLEAD3 - Set of black and red solar PV MC4 Solar Clamp Meter Test Leads
    • Designed for use with solar clamp meters that accept 4mm banana plugs
    • Ensures safe DC power measurements on Photovoltaic (PV) modules and systems
    • Creates a connection between solar panel and inverter for troubleshooting and maintenance of PV systems
Advice & Support Call 01642 931329 or contact us
Price Match We won't be beaten, let us know
Free MC4 Solar Clamp Test Leads
Fluke 393 FC CAT III 1500V DC True-RMS Clamp Meter with iFlex Clamp & Fluke Connect

Fluke 393 FC CAT III 1500V DC True-RMS Clamp Meter with iFlex & Fluke Connect

Fluke 393 FC Clamp Meter with iFlex | Electricians Ultimate Tool

The Fluke 393 FC CAT III 1500V True-RMS Clamp Meter is the only clamp meter designed to measure 1500V DC systems, making it ideal for checking solar arrays, wind power equipment, electric railways, data centres, and battery banks. To this end, it features a CAT III 1500V safety rating, 1500V CAT III insulated test leads, and can take the following measurements through its thin clamp jaw:

  • DC voltage: up to 1500V
  • AC voltage: up to 1000V
  • AC/DC current: 999.9A

Fluke 393 FC 1500 V Clamp Meter | Importance of CAT III Ratings

Furthermore, the supplied iFlex flexible current probe extends AC current measurements up to 2500A while providing access to tight spaces as it can be twisted through extremely small spots. The Fluke 393 FC CAT III 1500V True-RMS Clamp Meter’s thin jaw also enables access to cables in crowded combiner boxes.

Fluke 393 FC 1500 V Clamp Meter | Benefits Of A Thinner Jaw

Additionally, for safe, simple, and speedy working, the Fluke 393 FC CAT III 1500V True-RMS Clamp Meter measures DC power (displayed in kVA) and is equipped with audio polarity and visual continuity indicators. Audio polarity indication prevents accidental miswiring while the visual continuity indicator is particularly useful when working in dark and noisy environments as it turns the Fluke 393 FC CAT III 1500V True-RMS Clamp Meter’s digital display bright green.

Fluke 393 FC 1500 V Clamp Meter | Install PV Panels w/ Audio Polarity

Models with Fluke Connect technology offer even more convenience as results can be wirelessly logged to the Fluke Connect App, allowing you to analyse and share results, as well as create reports.

Fluke 393 FC 1500 V Clamp Meter | Features And Functions

The IP54-rated Fluke 393 FC CAT III 1500V True-RMS Clamp Meter is an ergonomic, easy-to-use, safety-optimised clamp meter ideal for technicians working inside or outside in high voltage DC environments.

Fluke 393 FC 1500 V Clamp Meter | What It Does And How It Works

Applications

Solar Industry

Fluke 393 FC 1500 V Clamp Meter | Why This Tool Matters To Solar

Fluke 393 FC CAT III 1500V True-RMS Clamp Meter Key Features

  • The only clamp meter designed to measure 1500V DC systems
  • Ideal for checking solar arrays, wind power equipment, electric railways, data centres, and battery banks
  • Safety rating: CAT III 1500V
  • 1500V CAT III insulated test leads
  • DC voltage: up to 1500V
  • AC voltage: up to 1000V
  • AC/DC current: 999.9A
  • iFlex probe extends AC current measurements to 2500A
  • iFlex probe can be twisted through tight spaces to provide access
  • Thin jaw enables access to cables in crowded combiner boxes
  • Measure DC power (readings displayed in kVA)
  • Audio polarity indicator prevents accidental miswiring
  • Visual continuity indicator turns the display bright green
  • Two models available: one with Fluke Connect and one without
  • Log, analyse, and share data using the Fluke Connect App
  • IP54-rated: suitable for outdoor use
  • An ergonomic, easy-to-use, safety-optimised clamp meter
  • Ideal for technicians working inside or outside in high voltage DC environments

What’s Included?

  • Your Choice of Fluke 393/E OR 393FC/E CAT III 1500V True-RMS Clamp Meter
  • CAT III 1500V Rated Test Leads with Right Angle Plugs and Safety Caps
  • 18-inch iFlex Flexible Current Probe
  • TPAK Hanging Strap
  • Premium Carrying Case

Fluke 393 FC 1500 V Clamp Meter | Product Unboxing

Free MC4 Solar Clamp Test Leads
  • Fluke PVLEAD3 - Set of Black and Red Solar PV MC4 Solar Clamp Meter Test Leads - PVLEAD3, typically £65.00

Fluke 393 FC CAT III 1500V True-RMS Clamp Meter with iFlex Technical Specifications 

General
Maximum voltage between any Terminal and Earth Ground
AC 1000 V
DC 1500 V
Batteries 2 AA IEC LR6 alkaline
Display Dual display with backlight
Automatic Power Off 20 minutes
Electrical 
Accuracy Accuracy is specified for 1 year after calibration, at operating temperatures of 18 °C to 28 °C, relative humidity at 0 % to 75 %. Accuracy specifications take the form of: ±([% of Reading] + [Number of Least Significant Digits]).
Temperature Coefficients Add 0.1 x specified accuracy for each °C > 28 °C or < 18 °C
AC Current: Jaw  
Range 999.9 A
Resolution 0.1 A
Accuracy 2 % + 5 digits (10 Hz to 100 Hz)
2.5 % + 5 digits (100 Hz to 500 Hz)
Crest Factor (50/60 Hz) 2.5 @600.0 A
3.0 @500.0 A
1.42 @999.9 A
Add 2 % for C.F. >2
AC Current: Flexible Current Probe
Range 999.9 A
  2500 A
Resolution 0.1 A (≤999.9 A)
1 A (≤2500 A)
Accuracy 3 % RD + 5 digits (10 Hz to 500 Hz)
Crest Factor (50/60Hz) 2.5 @1400 A
3.0 @1100 A
1.42@2500 A
Add 2 % for C.F. >2
DC Current
Range 999.9 A
Resolution 0.1 A
Accuracy 2 % RD + 5 digits[1]
Note [1] When using the ZERO (B) function to compensate for offsets.
AC Voltage 
Range 600.0 V
1000 V
Resolution 0.1 V (≤600.0 V)
1 V (≤1000 V)
Accuracy 1 % RD + 5 digits (20 Hz to 500 Hz)
DC Voltage 
Range 600.0 V
1500 V
Resolution 0.1 V (≤600.0 V)
1 V (≤1500 V)
Accuracy 1 % RD + 5 digits
mV DC
Range 500.0 mV
Resolution 0.1 mV
Accuracy 1 % RD + 5 digits
Amps Frequency: Jaw 
Range 5.0 Hz to 500.0 Hz
Resolution 0.1 Hz
Accuracy 0.5 % RD + 5 digits
Trigger Level 5 Hz to 10 Hz, ≥10 A
10 Hz to 100 Hz, ≥5 A
100 Hz to 500 Hz, ≥10 A
Amps Frequency: Flexible Current Probe
Range 5.0 Hz to 500.0 Hz
Resolution 0.1 Hz
Accuracy 0.5 % RD + 5 digits
Trigger Level 5 Hz to 20 Hz, ≥25 A
20 Hz to 100 Hz, ≥20 A
100 Hz to 500 Hz, ≥25 A
Voltage Frequency
Range 5.0 Hz to 500.0 Hz
Resolution 0.1 Hz
Accuracy 0.5 % RD + 5 digits
Trigger Level 5 Hz to 20 Hz, ≥5 V
20 Hz to 100 Hz, ≥5 V
100 Hz to 500 Hz, ≥10 V
DC Power 
Range 600.0 kVA (600.0 V dc range)
1500 kVA (1500 V dc range)
Resolution 0.1 kVA
1 kVA
Accuracy 2 % RD + 2.0 kVA
2 % RD + 20 kVA
Resistance 
Range 600.0 Ω
6000 Ω
60.00 kΩ
Resolution 0.1 Ω (≤600.0 Ω)
1 Ω (≤6000 Ω)
0.01 kΩ (≤60.00 kΩ)
Accuracy 1 % RD + 5 digits
Capacitance
Range 100.0 μF
1000 μF
Resolution 0.1 μF (≤100.0 μF)
1 μF (≤1000 μF)
Accuracy 1 % RD + 5 digits
Inrush Trigger Level 5 A
Mechanical
Size (L x W x H) 281 mm x 84 mm x 49 mm
Weight (with batteries) 520 g
Jaw Opening 34 mm
Flexible Current Probe Diameter 7.5 mm
Flexible Current Probe Cable Length (head to electronics connector) 1.8 m
Environmental 
Operating Temperature -10 °C to 50 °C
Storage Temperature -40 °C to 60 °C
Operating Humidity Non condensing (<10°C)
≤90 % RH (at 10 °C to 30 °C)
≤75 % RH (at 30 °C to 40 °C)
≤45 % RH (at 40 °C to 50 °C)
Operating Altitude 2000 m
Storage Altitude 12 000 m
Ingress Protection (IP) Rating IEC 60529: IP54 non-operating
Electromagnetic Compatibility (EMC)
International IEC 61326-1: Portable, Electromagnetic Environment, IEC 61326-2-2 CISPR 11: Group 1, Class A
Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself.
Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances.
Caution: This equipment is not intended for use in residential environments and may not provide adequate protection to radio reception in such environments.
Korea (KCC) Class A equipment (Industrial Broadcast & Communications Equipment)
Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes.
USA (FCC) 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
Safety 
General IEC 61010-1, Pollution Degree 2
Measurement IEC 61010-2-032: CAT III 1500 V / CAT IV 600 V
IEC 61010-2-033: CAT III 1500 V / CAT IV 600 V
Wireless Radio
Radiofrequency certification FCC ID: T68-FBLE, IC: 6627A-FBLE
Wireless Radio Frequency Range 2400 MHz to 2483.5 MHz
Output Power <100 mW
SIMPLIFIED EU DECLARATION OF CONFORMITY Hereby, Fluke declares that the radio equipment contained in this Product is in compliance with Directive 2014/53/EU.

Reviews

Additional Information
SKU FLUKE-393