Fluke 1748/INTL Three-Phase Power Quality Logger – Choice of Kit

SKU
Fluke/1748/INTL
Rating:
0%
(0)
Reward Points
:
8268
£8,268.00 £6,890.00
Free UK Delivery*
Choose a Special Offer
  • PASS Power Bank & Magnetic Wireless Charger
    PASS Power Bank & Magnetic Wireless Charger (10 000mAh 15W)
    FREE
    £49.00
  • PASS Power Bank & Magnetic Wireless Charger (10 000mAh 15W) SKU: (PASSPOWER-PLUS)
    FREE
    £49.00
    PASS Power Bank & Magnetic Wireless Charger
    • Supports magnetic wireless charging
    • Supports wired charging
    • 10 000mAh 15W
Advice & Support Call 01642 931329 or contact us
Price Match We won't be beaten, let us know
FREE Powerbank / Wireless Charger
Fluke 1748/INTL Three-Phase Power Quality Logger - Angled

The Fluke 1748/INTL Three-Phase Power Quality Logger is a useful diagnostic, inspection and maintenance tool; it can be used to aid engineers and technicians with making critical power quality and energy decisions in real-time.

The Fluke 1748/INTL Three-Phase Power Quality Logger is the most sophisticated model in Fluke’s series of 174X Three-Phase Power Quality Loggers and differs from its sister product, the Fluke 1748/EUS Three-Phase Power Quality Logger, in that it is suitable for use in Australia, China and Brazil as well as Europe, the UK and the US.

The Fluke 1748/INTL Three-Phase Power Quality Logger is available in three kits that vary in regards to their included flexible current probes:

  • FLUKE 1748/B/INTL - Fluke 1748/INTL Three-Phase Power Quality Logger WITHOUT Probes
  • FLUKE 1748/15/INTL - Fluke 1748/INTL Three-Phase Power Quality Logger with 1500A iFlex Probes
  • FLUKE 1748/30/INTL -  Fluke 1748/INTL Three-Phase Power Quality Logger with 3000A iFlex Probes  

Measurement Functions

This diagnostic, maintenance and inspection tool is suitable for carrying out quality-of-service surveys, quantifying energy usage, and troubleshooting power distribution systems. To this end, it is able to monitor and log up to five-hundred power parameters simultaneously, including the following:

  • Harmonics for voltage and current
  • Interharmonics for voltage and current
  • Unbalance
  • Flicker
  • Rapid voltage changes

When used with three-phase and neutral voltage test leads and up to four current probes, the Fluke 1748/INTL Three-Phase Power Quality Logger can also be used to measure all three voltage and current phases as well as neutral current. Moreover; the Fluke 1748/INTL Three-Phase Power Quality Logger’s ability to record event waveforms and determine RMS event profiles, detailing the date, time and relevant severity information, makes this unit particularly well suited to identifying the root causes of power quality issues.

As a result of the Fluke 1748/INTL Three-Phase Power Quality Logger’s ability to log over five-hundred power parameters and capture events simultaneously, it can be used to assess power quality in accordance with EN 50160 and IEEE 519 standards. The versatility, accuracy and IEC 61000-4-30 Class A Edition 3-compliance of the Fluke 1748/INTL Three-Phase Power Quality Logger ensures that its precision is maintained regardless as to which part of the power system it is testing; this instrument can be used to perform tests at service entrances, substations or at the load.

Ergonomic, Rugged Design

System Interface

Also working to ensure the accuracy and reliability of results is the Fluke 1748/INTL Three-Phase Power Quality Logger’s intelligent verification feature which will alert the user via an amber light (visible through the power button) when test leads, clamps and/or probes are not connected correctly; when connections are correct, the amber light will change to green. If the Fluke 1748/INTL Three-Phase Power Quality Logger identifies an incorrect connection it will alter it digitally without the user having to remove connected test leads or clamps.

Further to this, the Fluke 1748/INTL Three-Phase Power Quality Logger automatically detects, scales and powers connected clamps and/ or probes thereby ensuring that the instruments can be depended upon to acquire accurate, reliable and relevant data. Up to four current probes can be connected separately, allowing the user to tailor the Fluke 1748/INTL Three-Phase Power Quality Logger to the application and ensuring maximum flexibility.

Finally, the Fluke 1748/INTL Three-Phase Power Quality Logger is equipped with a quick, guided and graphical PC-application setup that enables the user to configure the instrument so that it is able to gather the relevant data correctly, accurately and reliably.

Accessories

As mentioned above, up to four flexible current probes (NOT supplied in the Fluke 1748/B/INTL kit) can be connected to the Fluke 1748/INTL Three-Phase Power Quality Logger. These thin, IP65, flexible probes can be used to inspect most installations and allow the user to access tight spaces and difficult-to-reach conductors and systems. Their wide ranges (probe dependent) ensure high accuracy for each application.

Additionally, the Fluke 1748/INTL Three-Phase Power Quality Logger is supplied with 2m test leads allowing the user to access difficult-to-reach conductors.

Physical Design

Like the aforementioned probes, the Fluke 1748/INTL Three-Phase Power Quality Logger is IP65-compliant (when used with an IP65 voltage input adapter); all of the instrument’s ports, including its AUX, I/O, USB and Ethernet ports, are IP65 rated ensuring that they are unaffected by dust and water ingress when not in use.

Additionally, the Fluke 1748/INTL Three-Phase Power Quality Logger is safety rated to 600V CAT IV/ 1000V CAT III: the highest safety rating in the industry. This expands the Fluke 1748/INTL Three-Phase Power Quality Logger’s scope-for-use and makes it suitable for applications at service entrances and downstream.

The rugged, safety-optimised construction of the Fluke 1748/INTL Three-Phase Power Quality Logger protects it from physical damage when in the field, whilst its ability to be secured using a standard chain or another security instrument protects the unit from theft.

Using the supplied magnetic hanger, the Fluke 1748/INTL Three-Phase Power Quality Logger can be stored securely inside or outside the panel. Its small size also makes it suitable for applications in tight spaces; it has the following dimensions: 23cm x 18cm x 5.4cm.

The Fluke 1748/INTL Three-Phase Power Quality Logger is also supplied with a lithium-ion battery capable of powering the instrument for four hours per charge; it is able to withstand temporary power disruptions.

Alternatively, the Fluke 1748/INTL Three-Phase Power Quality Logger can be powered using a wall line cord or is able to derive a power source from the circuit-under-test, thereby improving its practicality as the user does not need to rely on the instrument's battery life or a mains supply in order to conduct relevant tests over prolonged periods. The Fluke 1748/INTL Three-Phase Power Quality Logger features a wide power range and will go from 100V to 500V automatically.

Memory and Data Download

As mentioned above, the Fluke 1748/INTL Three-Phase Power Quality Logger is equipped with a number of ports that can facilitate the transfer of recorded data. Results can be sent to a PC via a USB interface, an Ethernet connection or via Wi-Fi; the transfer of data via Wi-Fi allows the user to view measurements remotely outside of dangerous environments and in real-time, enabling real-time analysis and decision-making whilst reducing the need for expensive PPE.

Further to this, data can be logged directly to a USB drive. The Fluke 1748/INTL Three-Phase Power Quality Logger features two USB ports allowing it to be connected to a PC and USB drive at the same time.

The Fluke 1748/INTL Three-Phase Power Quality Logger’s internal memory is able to store in excess of twenty data-logging sessions. This inspection and diagnostics tool will automatically log a variety of power quality and power variables thereby ensuring that measurement trends are always complete.

Analysis and Reporting

The Fluke 1748/INTL Three-Phase Power Quality Logger is supplied with Fluke’s Energy Analyse Plus Software which can be used to analyse data and create relevant reports; it can also be used to view data remotely when it is transferred to a PC via a wired or wireless connection.

When data is downloaded to the user’s PC, and subsequently the Fluke Energy Analyse Plus Software, the program will automatically calculate the limits of the current harmonics using the installation parameters and thereby predict grid overload in accordance with a variety of international standards. Using this data, the engineer/ technician can monitor harmonics before distortion appears in the voltage enabling him/her to increase the system’s uptime by preventing unexpected failures and non-compliance situations.  

Data imported to Fluke’s Energy Analyse Plus Software may be exported in PQDIF and NeQual formats for use with third-party software. The operator is also to select a particular parameter to create a customised view of logged measurements for advanced data correlation. He/she can view hour/hour, day/day and week/week comparisons. Using this software the engineer or technician is able to analyse every detail of the energy consumption and power quality state-of-health.

Finally, at the touch of a button, the user is able to create EN 50160, IEEE 519, GOST 33073 reports. The templates of these reports can be altered as necessary in order to accommodate evolving standards.

The Fluke 1748/INTL Three-Phase Power Quality Logger is a sophisticated, small and safety-optimised three-phase power quality analyser and data logger.

Fluke 1748/INTL Three-Phase Power Quality Logger Key Features

  • A useful diagnostic, inspection and maintenance tool
  • Aids engineers and technicians with making critical power quality and energy decisions in real-time
  • The most sophisticated model in Fluke’s series of 174X Three-Phase Power Quality Loggers
  • Suitable for use in Australia, China and Brazil as well as Europe, the UK and the US
  • Available in three kits that vary in regards to their included current probes
  • Carry out quality-of-service surveys, quantify energy usage, and troubleshoot power distribution systems
  • Monitor and log up to five-hundred power parameters
  • Harmonics for voltage and current
  • Interharmonics for voltage and current
  • Unbalance
  • Flicker
  • Rapid voltage changes
  • Use three-phase and neutral voltage test leads and up to four current clamps to measure all three voltage and current phases and neural current
  • Record event waveforms
  • Determine RMS event profiles with the date, time and relevant security information
  • Suited to identifying the root causes of power quality issues
  • Log parameters and record events simultaneously
  • Assess power quality in accordance with EN 50160 and IEEE 519 standards
  • Complaint with IEC 61000-4-30 Class A Edition 3 
  • Can be used to perform tests at service entrances, substations and at the load
  • Intelligent verification feature checks that connections are correct
  • An amber light indicates an incorrect connection
  • A green light indicates that the connection is correct
  • The intelligent verification feature digitally corrects connections without the user having to remove test leads, probes or clamps
  • Automatically detects, scales and powers connected clamps and probes
  • Up to four current probes can be connected separately ensuring maximum flexibility
  • Features a quick, guided and graphical PC-based application setup for simple and correct configuration
  • IP65, flexible, thin current probes (NOT supplied with the Fluke 1748/B/INTL model)
  • The probes’ wide ranges ensure high accuracy regardless of the application
  • 2m test leads for accessing awkwardly placed conductors
  • Rugged, IP65 design (when used with an IP65 voltage input adapter)
  • IP65 ports are protected against dust and moisture ingress when not in use
  • Highest safety rating in the industry: 600V CAT IV/ 1000V CAT III
  • Suitable for use at service entrances and downstream
  • Can be secured using a standard chain or another security instrument
  • Compact for use in tight spaces: 23cm x 18cm x 5.4cm
  • Supplied with a magnetic hanger
  • Supplied with a lithium-ion battery capable of powering the instrument for four hours per charge
  • Able to withstand temporary power disruptions
  • Can be powered using a wall line cord
  • Can be powered by the circuit-under-test
  • Wide power range: automatically goes from 100V to 500V
  • Transfer data to a PC via a USB interface, Ethernet connection or Wi-Fi
  • Wi-Fi transfer allows the user to view data remotely outside of dangerous locations and in real-time
  • Two USB ports
  • Data can be downloaded directly to a USB drive
  • Internal memory can store in excess of twenty data-logging sessions
  • Automatically logs a variety of power quality and power variables ensuring that measurement trends are complete
  • Supplied with Fluke’s Energy Analyse Plus Software
  • Fluke’s Energy Analyse Plus Software can be used to analyse data, create relevant reports and view data remotely via a Wi-Fi connection
  • The Fluke Energy Analyse Plus Software calculates the limits of the current harmonics allowing it to predict grid overload in accordance with a variety of international standards
  • Export data in PQDIF and NeQual formats using the Flukes Energy Analyse Plus Software
  • Select a particular parameter to see a customised view of logged measurements for advanced data correlation
  • View hour/hour, day/day and week/week comparisons
  • Use the Fluke Energy Analyse Plus Software to analyse every detail of energy consumption and power quality state-of-health
  • Use the supplied software to create EN 50160, IEEE 519, GOST 33073 reports
  • Alter report templates to accommodate for evolving standards
  • A sophisticated, small and safety-optimised three-phase power quality analyser and data logger

What’s Included?

  • Your Choice of Fluke 1748/ INTL Three-Phase Power Quality Logger Kit (see below)
Items FLUKE1748/B/INTL FLUKE1748/15/INTL FLUKE1748/30/INTL
Fluke 1748/EUS Three-Phase Power Quality Logger  X X X
1500A iFlex Current Probes (60cm) - X -
3000A iFlex Current Probes (60cm) - - X
USB Stick X X X
USB Cable X X X
3PHVL-1730 3-Phase + neutral voltage test lead X X X
Test lead set red/black 0.18 m X X X
Test lead set red/black 1.5 m X X X
Alligator clips 4 4 4
173x/174x Soft Case X X X
Cable marker kit X X X
MP1-3R/1B-Magnet Probe 1 set (3 red, 1 black) 1 1 1
174x-Hanger Kit X X X
FREE Powerbank / Wireless Charger
  • PASS Power Bank & Magnetic Wireless Charger (10 000mAh 15W) - PASSPOWER-PLUS, typically £49.00

Fluke 174X Three-Phase Power Quality Loggers Technical Specifications 

Please note that the Fluke 1748/INTL Three-Phase Power Quality Loggers are part of Fluke's range of 174X Three-Phase Power Quality Loggers; the table below details the technical specifications for all the models included in this range. 

Specifications
Accuracy
Parameter Range Maximum Resolution Intrinsic Accuracy at Reference Conditions (% of Reading +% of Range)
Voltage 1000 V 0.1 V ±0.1 % of nominal voltage 1, 2
Current: Direct input i17xx-flex 1500IP 24 1500 A 150 A 0.01 A (min. 1.5A)3 ±(1% + 0.02%)
1500 A 0.1 A
i17xx-flex 3000IP 24 3000 A 300 A 0.01 A (min. 3.0 A)3 ±(1% + 0.03%)
3000 A 0.1 A
i17xx-flex 6000IP 36 6000 A 600 A 0.01 A (min. 6.0 A)3 ±(1.5% + 0.03%)
6000 A 0.1 A
i40s-EL clamp 4 A 1 mA ±(0.7% + 0.02%)
40 A 10 mA
Frequency 42.5 Hz to 69 Hz 0.01 Hz ±(0.1%)2
Auxiliary input ±10 V dc 0.1 mV ±(0.2% + 0.02%)
Voltage min/max 1000 V 0.1 V ±0.2 % of nominal input voltage1
Current min/max Defined by accessory Defined by accessory ±(5% + 0.2%)
THD on voltage 1000% 0.10% ± 2.5%
THD on current 1000% 0.10% ± 2.5%
Voltage harmonics 2nd to 50th 1000 V 0.1 V ≥ 1 V: ±5% of reading
< 1 V: ±0.05V
Current harmonics 2nd to 50th Defined by accessory Defined by accessory ≥ 3% of current range: ±5% of reading
< 3% of current range: ±0.15% of range
Flicker PLT, PST 0 to 20 0.01 5%
Current probe accuracy
Parameter Influence quantity/ iFlex1500IP-24 iFlex3000IP-24  iFlex6000IP-36 i40S-EL
150 A / 1500 A 300 A / 3000 A 600 A / 6000A 4 A / 40 A
Active Power P PF ≥ 0.99 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Active Energy Ea
Apparent power S 0 ≤ PF ≤ 1 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Apparent Energy Eap
Reactive power Q 0 ≤ PF ≤ 1 2.5% of measured apparent power
Reactive Energy Er
Power Factor PF - ±0.025
Displacement Power
Factor DPF/cosΦ
Additional uncertainty in% of range VP-N>250 V 0.015% 0.023% 0.023% 0.015%
1 In the range of 100 V … 500 V; also known as Udin
2 0 °C … 45 °C: Intrinsic accuracy x 2, outside of 0 °C … 45 °C: Intrinsic accuracy x 3
3 Consult operators manual for details

Reference conditions:
Environmental: 23 °C ± 5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65 %
Input conditions: Cosφ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10 %.
Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V
Input current: I > 10 % of I range
Primary conductor of clamps or Rogowski coil in center position
Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
Electrical Specifications
Power Supply
Voltage range 100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7)
Power consumption Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter)
Efficiency ≥ 68.2% (in accordance with energy efficiency regulations)
Maximum no-load consumption < 0.3 W only when powered using IEC 60320 input
Mains power frequency 50/60 Hz ±15%
Battery Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-battery runtime Typically 4 hours
Charging time < 6 hours
Data Acquisition
Resolution 16-bit synchronous sampling
Sampling frequency 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency 50/60 Hz (42.5 to 69 Hz)
Circuit types 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies)
Data storage Internal flash memory (not user replaceable)
Memory size Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events
Basic Interval
Measured parameters Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging interval User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max values Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms)
Demand Interval (Energy Meter Mode)
Measured parameters Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Power Quality Measurements
Measured parameter Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation
Averaging interval 10 min for all parameters
2 hrs (long term Flicker PLT)
150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT)
Individual harmonics 2nd to 50th harmonic
Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only
Interharmonics 1st to the 50th interharmonic
Total harmonic distortion Calculated on 50 voltage harmonics
Events Voltage: dips, swells, interruptions, current: inrush current
1748: mains signaling, transients (low frequency)
Triggered recordings RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30)
Waveform of voltage and current up to 200 ms, 10/12 cycles
Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s
Inrush RMS profile based on 1/2 cycle RMS steady state triggering
Flicker In accordance with IEC 61000-4-15 and IEEE 1453
Mains signaling Two user defined frequencies up to 3 kHz
PQ Health Summarizes power quality measurements in one table. Detailed data available for each parameter
EN 50160 Compliance with standard
Programmable PQ limits Enables user defined limits for local standards compliance
Standards Compliance
Harmonics IEC 61000-4-7: Class 1
IEEE 519 (short time and very short time harmonics)
Power quality IEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device)
Power IEEE 1459
Power quality compliance EN 50160
Safety General: IEC 61010-1: Pollution Degree 2
Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V
Power Supply: Overvoltage Category IV, Pollution Degree 2
Li-ion Battery: IEC 62133
Interfaces
USB-A File transfer via USB flash drive, firmware updates, max. supply current: 120 mA
WiFi File transfer and remote control via direct connection or WiFi infrastructure
Bluetooth Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or WiFi/BLE adapter, check for availability)
USB-mini Data download device to PC
Current Inputs
Number of inputs 4 (3 phases and neutral), mode selected automatically for attached sensor
Input voltage Clamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range
Range 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 IP 24
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 IP 24
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 IP 36
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth 42.5 Hz - 3.5 kHz
Scaling 1:1 and variable
Auxiliary Inputs
Number of inputs 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously)
Input range 0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s
Scale factor Format: mx + b (gain and offset) user configurable
Displayed units User configurable (7 characters, for example, °C, psi, or m/s)
Wireless Bluetooth connection (check for availability)
Number of inputs 2
Supported modules Fluke Connect® 3000 series
Acquisition 1 reading/s
Environmental Specifications
Operating temperature -25 °C to +50 °C (-13 °F to 122 °F)1
Storage temperature Without battery: -25 °C to +60 °C (-13 °F to 140 °F), with battery: -20 °C to +50 °C (−4 °F to 122 °F)
Operating humidity IEC 60721-3-3: 3K6:
-25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 %
40 °C (104 °F): 55 %
50 °C (122 °F): 35 %
Operating Altitude 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude 12,000 m
Enclosure IEC 60529: IP50
IEC 60529: IP65 with IP65 rated voltage connector
Vibration IEC 60721-3-3 / 3M2
Electromagnetic compatibility (EMC) EN 61326-1: Industrial CISPR 11: Group 1, Class A
IEC 61000-6-5 Power station environment
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
General Specifications
Warranty Two-years (battery not included)
Accessories: one-year
Calibration cycle: two-years
Dimensions 23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in)
Weight Instrument: 1 kg (2.2 lb)
Tamper protection Accept securing cables (max. Φ 6mm)
1Warm up the product to -10 °C (+14 °F) before you power the unit on
Flexible Current Probe Specifications
Specifications  i17XX-FLEX1.5KIP i17XX-FLEX3KIP
Measuring range 1 to 150 A ac/10 to 1500 A ac 1 to 300 A ac 10 to 3000 A ac
Probe cable length 610 mm (24 in) 610 mm (24 in)
Probe cable diameter 7.5 mm (0.3 in) 7.5 mm (0.3 in)
Weight 170 g (0.38 lb) 170 g (0.38 lb)
Minimum bending radius 38 mm (1.5 in)
Nondestructive current 100 kA (50/60 Hz)
Temperature coefficient over
operating temperature range
0.05 % of reading/°C (0.028 % of reading/°F)
Working voltage 1000 V CAT III, 600 V CAT IV
Output cable length 2.0 m (6.5 ft)
Probe cable material TPR
Weight 115 g
Probe cable material TPR
Coupling material POM + ABS/PC
Output cable TPR/PVC
Operating temperature -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Temperature, non-operating -40 °C to +80 °C (-40 °F to 176 °F)
Relative humidity, operating 15% to 85% non-condensing
IP rating IEC 60529: IP65
Warranty One-year

Fluke 174X Three-Phase Power Quality Loggers Comparison Table

Functions  1742 Power Quality Loggers 1746 Power Quality Loggers 1748 Power Quality Loggers
Voltage, current, power, power factor, frequency X X X
Energy forward/reverse X X X
Peak Demand X X X
THD X X X
Voltage and current harmonics (to 50th)1 X X
Flicker X X X
Unbalance1 X X
Rapid voltage change events1 X X
Interharmonics (to 50th)1 X X
Dips, swells, interruption and transient events tables1 X X
Mains signaling X X
Inrush current1  X X
Transients (low frequency)/Waveform deviation events2 X
Recording  1742 Power Quality Loggers 1746 Power Quality Loggers 1748 Power Quality Loggers
Trend X X X
Waveform snapshots2 X
RMS profile2 X
Communication  1742 Power Quality Loggers 1746 Power Quality Loggers 1748 Power Quality Loggers
Ethernet X X X
USB (mini B) X X X
WiFi download Instrument to device X X X
Wifi download via WiFi hub (requires registration) Opt Opt Opt
Included accessories 1742 Power Quality Loggers 1746 Power Quality Loggers 1748 Power Quality Loggers
Flexible current probe not /B version not /B version not /B version
USB stick X X X
USB cable X X X
3PHVL-1730 3-Phase + neutral voltage test lead X X X
Test lead set red/black 0.18 m X X X
Test lead set red/black 1.5 m X X X
Alligator clips 4 4 4
173x/174x Soft Case X X X
Cable marker kit X X X
MP1-3R/1B-Magnet Probe 1 set (3 red, 1 black) Opt 1 1
174x-Hanger Kit Opt Opt X

Fluke 174X Three-Phase Power Quality Logger - Datasheet Datasheets Fluke 174X Three-Phase Power Quality Logger - User Manual Manuals & Guides Fluke 174X Three-Phase Power Quality Logger - Quick Reference Guide Manuals & Guides Fluke 174X Three-Phase Power Quality Logger - IEC 61000-4-30 Class A Standard Explained Manuals & Guides Fluke 174X Three-Phase Power Quality Logger - Fluke Connect and Wi-Fi Instructions Manuals & Guides Fluke 174X Three-Phase Power Quality Logger - User Manual Supplement Manuals & Guides Fluke 174X Three-Phase Power Quality Logger - Calibration Manual Manuals & Guides Fluke 174X Three-Phase Power Quality Logger - Overhead Lines Application Note Case Studies & Applications Fluke 174X Three-Phase Power Quality Logger - Downloading, Analysing and Reporting Application Note Case Studies & Applications Fluke 174X Three-Phase Power Quality Logger - Safety Information Notes & Other Fluke 174X Three-Phase Power Quality Logger - Statement of Memory Volatility Notes & Other