Fluke 1748/ EUS Three-Phase Power Quality Logger - Choice of Kit
The Fluke 1748/ EUS Power Quality Logger can be used to perform quality of service surveys, quantify energy usage and troubleshoot power distribution systems, allowing the technician/ engineer to make critical power quality and energy decisions in real-time.
This power quality logger is optimised for European, UK and US markets and is available in three kits that vary in regards to the included flexible current probes:
- FLUKE 1748/B/EUS - WITHOUT Probes
- FLUKE 1748/15/EUS - with 1500A iFlex Probes
- FLUKE 1748/30/EUS - with 3000A iFlex Probes
Measurement Features
The Fluke 1748/ EUS Three-Phase Power Quality Logger is compliant with IEC 61000-4-30 Class A Edition 3 standards and can be used to log up to five-hundred parameters simultaneously. The highly accurate Fluke Power Quality Logger can monitor and log the following parameters (amongst others):
- Harmonics for voltage and current
- Interharmonics for voltage and current
- Unbalance
- Flicker
- Rapid voltage changes
This instrument can also be used to measure neutral current and all three current and voltage phases (when used with three-phase and neutral voltage test leads, and flexible current probes). In addition to monitoring up to five-hundred power parameters, the Fluke 1748/ EUS can capture events. It can be used to record event waveforms as well as determine an RMS event profile which includes the date, time and any severity information. These additional features mean it can be used to identify root causes of power quality issues.
The comprehensive measurement and event capture capabilities make is suited to assessing power quality in accordance with EN 50160 and IEEE 519 standards, whether testing at the service entrance, substation or at the load.
Memory and Data Download
The Fluke 1748/ EUS ensures that measurement trends are complete by automatically logging a variety of power quality and power variables. It is possible to save in excess of twenty separate logging sessions to the logger.
Recorded measurements may be downloaded to a USB drive and/or communicated to PC via a wired or Wi-Fi connection. It is also possible to transfer data via an Ethernet connection. It includes two USB ports allowing the user to connect the instrument to a PC and a USB drive, enabling him/her to log data continuously and without having to remove the Power Quality Logger from the field. Wi-Fi connectivity also allows the user to view data remotely outside of dangerous environments, reducing the need for expensive PPE.
Analysis and Reporting
The Fluke 1748/ EUS Three-Phase Power Quality Logger is supplied with Fluke’s Energy Analyse Plus Software. This program can be used to view data remotely and in real-time using a Wi-Fi connection, analyse logged data, and create standardised reports. At the touch of a button, the Energy Analyse Plus Software is able to create EN 50160, IEEE 519, GOST 33073 reports. The user may adjust the report templates to remain in-line with standards as they evolve.
This software program can also be used to export data in PQDIF or NeQual formats allowing it to be used with third-party software.
Furthermore, the Energy Analyse Plus Software can be used to analyse every detail of energy consumption and power-quality state-of-health. The user is able to select a particular parameter to create a customised view of logged measurements and facilitates advanced data correlation. It is possible to view hour/hour, day/day and week/week comparisons by selecting the relevant thumbnail.
Moreover, this software program will calculate the limits of current harmonics based on the installation parameters thereby enabling the user to predict grid overload according to a range of international standards. This, in turn, allows the technician or engineer to prevent unexpected failures or non-compliance situations by monitoring harmonics before distortion appears in the voltage, thereby increasing the system’s uptime.
Ergonomic, Rugged Design
System Interface
Equipped with a quick, guided and graphical PC-based application setup ensuring that the user is always able to capture the desired data. Further to this, the intelligent verification feature ensures that the necessary test leads and clamps are connected correctly. If a connection error is detected the power button will display an amber light, this changes to green when the connection is corrected. The Fluke 1748/ EUS is capable of correcting connections digitally without the user having to remove connected leads or clamps.
Also improving this instrument’s ease-of-operation is its automatic detection, scaling and powering of the connected probes, thereby ensuring the accuracy of detected measurements. Moreover, up to four current probes can be connected separately to the Three-Phase Power Quality Logger thereby allowing for greater flexibility.
Physical Design
Similarly improving the Fluke Power Quality Logger’s flexibility is its ability to be powered by the circuit it is testing; this instrument has a wide power range and will automatically go from 100V to 500V. Alternatively; it may be powered by a wall line cord. Its wide power range and ability to be powered using various methods expand the Power Quality Logger’s scope-for-use.
It is equipped with a lithium-ion battery with an operating time of four hours per charge ensuring that it is able to withstand temporary power disruptions.
Additionally, the Fluke 1748/ EUS Three-Phase Power Quality Logger has the highest safety rating in the industry, again expanding its scope-for-use. With a rating of 600V CAT IV/ 1000V CAT III, it can be used at service entrances and downstream.
Its small size also adds to the versatility as it can be placed in tight spaces; it has the following dimensions 23cm x 18cm x 5.4cm. The supplied magnetic hanger ensures that the Three-Phase Power Quality Logger can be stored safely inside or outside the panel.
When left on-site, the logger may be safeguarded against theft using a standard chain or another security instrument, whilst its rugged, IP65 design (when used with an IP65 voltage input adapter) ensures that it is protected against physical damage when used or left on-site. All of the Fluke 1748/ EUS Three-Phase Power Quality Logger’s ports (AUX, I/O, USB and Ethernet) are compliant with IP65 ensuring that they are resistant to dust and moisture ingress when not in use.
Accessories
The supplied flexible current probes (NOT supplied with the Fluke 1748/ B/EUS version) are also IP65 certified, making them suitable for most installations. They are thin in design ensuring that they can be used to access tight spaces and include a wide range (probe dependent) for high accuracy in each application. Moreover, the included 2m leads allow the user to access awkwardly located conductors.
The Fluke 1748/ EUS Three-Phase Power Quality Logger is a practical, portable and precise three-phase power quality logger.
Key Features
- Perform quality of service surveys, quantify energy usage and troubleshoot power distribution systems
- Allows the engineer/ technician to make critical power quality and energy decisions in real-time
- Optimised for European, UK and US markets
- Available in three kits with different current probes
- Compliant with IEC 61000-4-30 Class A Edition 3 standards
- Log up to five-hundred parameters simultaneously and to a high accuracy
- Harmonics for voltage and current
- Interharmonics for voltage and current
- Unbalance
- Flicker
- Rapid voltage changes
- Measure neutral current and all three current and voltage phases (using three-phase and neutral voltage test leads, and flexible current probes)
- Can capture events whilst logging parameters
- Record event waveforms
- Determine an RMS event profile including the date, time and severity information
- Identify root causes of power quality issues
- Assess power quality in accordance with EN 50160 and IEEE 519 whether testing at the service entrance, substation or at the load
- Ensures that measurement trends are complete by automatically logging a variety of power quality and power variables
- Download data to a USB drive
- Transfer data via a wired, Wi-Fi or Ethernet connection
- Two USB ports
- Wi-Fi connectivity allows the user to view data remotely and in real-time outside of hazardous areas
- Supplied with Fluke’s Energy Analyse Plus Software
- View data remotely and in real-time using the supplied software and a Wi-Fi connection
- Create EN 50160, IEEE 519, GOST 33073 reports using the Fluke Energy Analyse Plus Software
- Adjust report templates as standards evolve
- Export data in PQDIF or NeQual formats using the Fluke Energy Analyse Plus Software
- Analyse every detail of the energy consumption and power-quality state of health
- Customise the data view as necessary when using the Fluke Analyse Plus Software
- The Fluke Energy Plus Software calculates the limits of the current harmonics allowing it to predict grid overload in accordance with a variety of international standards
- Quick, guided, graphical PC-based application setup
- Intelligent verification feature ensures the connections are correct
- Intelligent verification feature digitally corrects connections without the user having to disconnect test leads and/or clamps
- A connection error is indicated by an amber light
- A green light indicates a good connection
- Automatically detects, scales and powers the connected probe
- Current probes are connected separately for maximum flexibility
- Can be powered by the circuit-under-investigation
- Wide power range
- Automatically goes from 100V to 500V
- Lithium-ion battery with an operating time of four hours per charge
- Safety rating: 600V CAT IV/ 1000V CAT III
- Can be used at the service entrance and downstream
- Small size: 23cm x 18cm x 5.4cm
- Suitable for use in tight spaces
- Supplied with a magnetic hanger
- Rugged
- IP65 ports
- Can be secured using a chain or other security device
- IP65, flexible, thin current probes (NOT supplied with the Fluke 1748/B/EUS model)
- 2m test leads for accessing awkwardly placed conductors
- Practical, portable and precise three-phase power logger
What’s Included
- Your Choice of Fluke 1748/ EUS Three-Phase Power Quality Logger Kit (see below)
Items | FLUKE1748/B/EUS | FLUKE1748/15/EUS | FLUKE1748/30/EUS |
Fluke 1748/EUS Three-Phase Power Quality Logger | • | • | • |
1500A iFlex Current Probes (60cm) | - | • | - |
3000A iFlex Current Probes (60cm) | - | - | • |
USB Stick | • | • | • |
USB Cable | • | • | • |
3PHVL-1730 3-Phase + neutral voltage test lead | • | • | • |
Test lead set red/black 0.18 m | • | • | • |
Test lead set red/black 1.5 m | • | • | • |
Alligator clips | 4 | 4 | 4 |
173x/174x Soft Case | • | • | • |
Cable marker kit | • | • | • |
MP1-3R/1B-Magnet Probe 1 set (3 red, 1 black) | 1 | 1 | 1 |
174x-Hanger Kit | • | • | • |
- PASS Power Bank & Magnetic Wireless Charger (10 000mAh 15W) - PASSPOWER-PLUS, typically £49.00
Fluke 174X Three-Phase Power Quality Loggers Technical Specifications
Please note that the Fluke 1748/ EUS Three-Phase Power Quality Loggers are part of Fluke's range of 174X Three-Phase Power Quality Loggers; the table below details the technical specifications for all the models included in this range.
Specifications | |||||
Accuracy | |||||
Parameter | Range | Maximum Resolution | Intrinsic Accuracy at Reference Conditions (% of Reading +% of Range) | ||
Voltage | 1000 V | 0.1 V | ±0.1 % of nominal voltage 1, 2 | ||
Current: Direct input | i17xx-flex 1500IP 24 1500 A | 150 A | 0.01 A (min. 1.5A)3 | ±(1% + 0.02%) | |
1500 A | 0.1 A | ||||
i17xx-flex 3000IP 24 3000 A | 300 A | 0.01 A (min. 3.0 A)3 | ±(1% + 0.03%) | ||
3000 A | 0.1 A | ||||
i17xx-flex 6000IP 36 6000 A | 600 A | 0.01 A (min. 6.0 A)3 | ±(1.5% + 0.03%) | ||
6000 A | 0.1 A | ||||
i40s-EL clamp | 4 A | 1 mA | ±(0.7% + 0.02%) | ||
40 A | 10 mA | ||||
Frequency | 42.5 Hz to 69 Hz | 0.01 Hz | ±(0.1%)2 | ||
Auxiliary input | ±10 V dc | 0.1 mV | ±(0.2% + 0.02%) | ||
Voltage min/max | 1000 V | 0.1 V | ±0.2 % of nominal input voltage1 | ||
Current min/max | Defined by accessory | Defined by accessory | ±(5% + 0.2%) | ||
THD on voltage | 1000% | 0.10% | ± 2.5% | ||
THD on current | 1000% | 0.10% | ± 2.5% | ||
Voltage harmonics 2nd to 50th | 1000 V | 0.1 V | ≥ 1 V: ±5% of reading | ||
< 1 V: ±0.05V | |||||
Current harmonics 2nd to 50th | Defined by accessory | Defined by accessory | ≥ 3% of current range: ±5% of reading | ||
< 3% of current range: ±0.15% of range | |||||
Flicker PLT, PST | 0 to 20 | 0.01 | 5% | ||
Current probe accuracy | |||||
Parameter | Influence quantity/ | iFlex1500IP-24 | iFlex3000IP-24 | iFlex6000IP-36 | i40S-EL |
150 A / 1500 A | 300 A / 3000 A | 600 A / 6000A | 4 A / 40 A | ||
Active Power P | PF ≥ 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Active Energy Ea | |||||
Apparent power S | 0 ≤ PF ≤ 1 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Apparent Energy Eap | |||||
Reactive power Q | 0 ≤ PF ≤ 1 | 2.5% of measured apparent power | |||
Reactive Energy Er | |||||
Power Factor PF | - | ±0.025 | |||
Displacement Power | |||||
Factor DPF/cosΦ | |||||
Additional uncertainty in% of range | VP-N>250 V | 0.015% | 0.023% | 0.023% | 0.015% |
1 In the range of 100 V … 500 V; also known as Udin 2 0 °C … 45 °C: Intrinsic accuracy x 2, outside of 0 °C … 45 °C: Intrinsic accuracy x 3 3 Consult operators manual for details Reference conditions: Environmental: 23 °C ± 5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65 % Input conditions: Cosφ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10 %. Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V Input current: I > 10 % of I range Primary conductor of clamps or Rogowski coil in center position Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C |
|||||
Electrical Specifications | |||||
Power Supply | |||||
Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit | ||||
100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7) | |||||
Power consumption | Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter) | ||||
Efficiency | ≥ 68.2% (in accordance with energy efficiency regulations) | ||||
Maximum no-load consumption | < 0.3 W only when powered using IEC 60320 input | ||||
Mains power frequency | 50/60 Hz ±15% | ||||
Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable | ||||
On-battery runtime | Typically 4 hours | ||||
Charging time | < 6 hours | ||||
Data Acquisition | |||||
Resolution | 16-bit synchronous sampling | ||||
Sampling frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency | ||||
Input signal frequency | 50/60 Hz (42.5 to 69 Hz) | ||||
Circuit types | 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies) | ||||
Data storage | Internal flash memory (not user replaceable) | ||||
Memory size | Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events | ||||
Basic Interval | |||||
Measured parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy | ||||
Averaging interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min | ||||
Averaging time min/max values | Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms) | ||||
Demand Interval (Energy Meter Mode) | |||||
Measured parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy | ||||
Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off | ||||
Power Quality Measurements | |||||
Measured parameter | Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation | ||||
Averaging interval | 10 min for all parameters 2 hrs (long term Flicker PLT) 150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT) |
||||
Individual harmonics | 2nd to 50th harmonic Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only |
||||
Interharmonics | 1st to the 50th interharmonic | ||||
Total harmonic distortion | Calculated on 50 voltage harmonics | ||||
Events | Voltage: dips, swells, interruptions, current: inrush current 1748: mains signaling, transients (low frequency) |
||||
Triggered recordings | RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30) | ||||
Waveform of voltage and current up to 200 ms, 10/12 cycles | |||||
Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s | |||||
Inrush | RMS profile based on 1/2 cycle RMS steady state triggering | ||||
Flicker | In accordance with IEC 61000-4-15 and IEEE 1453 | ||||
Mains signaling | Two user defined frequencies up to 3 kHz | ||||
PQ Health | Summarizes power quality measurements in one table. Detailed data available for each parameter | ||||
EN 50160 | Compliance with standard | ||||
Programmable PQ limits | Enables user defined limits for local standards compliance | ||||
Standards Compliance | |||||
Harmonics | IEC 61000-4-7: Class 1 | ||||
IEEE 519 (short time and very short time harmonics) | |||||
Power quality | IEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device) | ||||
Power | IEEE 1459 | ||||
Power quality compliance | EN 50160 | ||||
Safety | General: IEC 61010-1: Pollution Degree 2 | ||||
Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V | |||||
Power Supply: Overvoltage Category IV, Pollution Degree 2 | |||||
Li-ion Battery: IEC 62133 | |||||
Interfaces | |||||
USB-A | File transfer via USB flash drive, firmware updates, max. supply current: 120 mA | ||||
WiFi | File transfer and remote control via direct connection or WiFi infrastructure | ||||
Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or WiFi/BLE adapter, check for availability) | ||||
USB-mini | Data download device to PC | ||||
Current Inputs | |||||
Number of inputs | 4 (3 phases and neutral), mode selected automatically for attached sensor | ||||
Input voltage | Clamp input: 500 mVrms/50 mVrms; CF 2.8 | ||||
Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range | |||||
Range | 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 IP 24 | ||||
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 IP 24 | |||||
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 IP 36 | |||||
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL | |||||
Bandwidth | 42.5 Hz - 3.5 kHz | ||||
Scaling | 1:1 and variable | ||||
Auxiliary Inputs | |||||
Number of inputs | 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously) | ||||
Input range | 0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s | ||||
Scale factor | Format: mx + b (gain and offset) user configurable | ||||
Displayed units | User configurable (7 characters, for example, °C, psi, or m/s) | ||||
Wireless Bluetooth connection (check for availability) | |||||
Number of inputs | 2 | ||||
Supported modules | Fluke Connect® 3000 series | ||||
Acquisition | 1 reading/s | ||||
Environmental Specifications | |||||
Operating temperature | -25 °C to +50 °C (-13 °F to 122 °F)1 | ||||
Storage temperature | Without battery: -25 °C to +60 °C (-13 °F to 140 °F), with battery: -20 °C to +50 °C (−4 °F to 122 °F) | ||||
Operating humidity | IEC 60721-3-3: 3K6: | ||||
-25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 % | |||||
40 °C (104 °F): 55 % | |||||
50 °C (122 °F): 35 % | |||||
Operating Altitude | 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) | ||||
Storage altitude | 12,000 m | ||||
Enclosure | IEC 60529: IP50 | ||||
IEC 60529: IP65 with IP65 rated voltage connector | |||||
Vibration | IEC 60721-3-3 / 3M2 | ||||
Electromagnetic compatibility (EMC) | EN 61326-1: Industrial CISPR 11: Group 1, Class A | ||||
IEC 61000-6-5 Power station environment | |||||
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) | |||||
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 | |||||
General Specifications | |||||
Warranty | Two-years (battery not included) | ||||
Accessories: one-year | |||||
Calibration cycle: two-years | |||||
Dimensions | 23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in) | ||||
Weight | Instrument: 1 kg (2.2 lb) | ||||
Tamper protection | Accept securing cables (max. Φ 6mm) | ||||
1Warm up the product to -10 °C (+14 °F) before you power the unit on | |||||
Flexible Current Probe Specifications | |||||
Specifications | i17XX-FLEX1.5KIP | i17XX-FLEX3KIP | |||
Measuring range | 1 to 150 A ac/10 to 1500 A ac | 1 to 300 A ac 10 to 3000 A ac | |||
Probe cable length | 610 mm (24 in) | 610 mm (24 in) | |||
Probe cable diameter | 7.5 mm (0.3 in) | 7.5 mm (0.3 in) | |||
Weight | 170 g (0.38 lb) | 170 g (0.38 lb) | |||
Minimum bending radius | 38 mm (1.5 in) | ||||
Nondestructive current | 100 kA (50/60 Hz) | ||||
Temperature coefficient over operating temperature range |
0.05 % of reading/°C (0.028 % of reading/°F) | ||||
Working voltage | 1000 V CAT III, 600 V CAT IV | ||||
Output cable length | 2.0 m (6.5 ft) | ||||
Probe cable material | TPR | ||||
Weight | 115 g | ||||
Probe cable material | TPR | ||||
Coupling material | POM + ABS/PC | ||||
Output cable | TPR/PVC | ||||
Operating temperature | -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F) | ||||
Temperature, non-operating | -40 °C to +80 °C (-40 °F to 176 °F) | ||||
Relative humidity, operating | 15% to 85% non-condensing | ||||
IP rating | IEC 60529: IP65 | ||||
Warranty | One-year |
Fluke 174X Three-Phase Power Quality Loggers Comparison Table
Functions | 1742 Power Quality Loggers | 1746 Power Quality Loggers | 1748 Power Quality Loggers |
Voltage, current, power, power factor, frequency | X | X | X |
Energy forward/reverse | X | X | X |
Peak Demand | X | X | X |
THD | X | X | X |
Voltage and current harmonics (to 50th)1 | X | X | |
Flicker | X | X | X |
Unbalance1 | X | X | |
Rapid voltage change events1 | X | X | |
Interharmonics (to 50th)1 | X | X | |
Dips, swells, interruption and transient events tables1 | X | X | |
Mains signaling | X | X | |
Inrush current1 | X | X | |
Transients (low frequency)/Waveform deviation events2 | X | ||
Recording | 1742 Power Quality Loggers | 1746 Power Quality Loggers | 1748 Power Quality Loggers |
Trend | X | X | X |
Waveform snapshots2 | X | ||
RMS profile2 | X | ||
Communication | 1742 Power Quality Loggers | 1746 Power Quality Loggers | 1748 Power Quality Loggers |
Ethernet | X | X | X |
USB (mini B) | X | X | X |
WiFi download Instrument to device | X | X | X |
Wifi download via WiFi hub (requires registration) | Opt | Opt | Opt |
Included accessories | 1742 Power Quality Loggers | 1746 Power Quality Loggers | 1748 Power Quality Loggers |
Flexible current probe | not /B version | not /B version | not /B version |
USB stick | X | X | X |
USB cable | X | X | X |
3PHVL-1730 3-Phase + neutral voltage test lead | X | X | X |
Test lead set red/black 0.18 m | X | X | X |
Test lead set red/black 1.5 m | X | X | X |
Alligator clips | 4 | 4 | 4 |
173x/174x Soft Case | X | X | X |
Cable marker kit | X | X | X |
MP1-3R/1B-Magnet Probe 1 set (3 red, 1 black) | Opt | 1 | 1 |
174x-Hanger Kit | Opt | Opt | X |
Reviews
SKU | Fluke/1748/EUS |
---|---|
Manufacturer Part Code | 4920780 |