Fluke 1742/INTL Three-Phase Power Quality Logger – Choice of Kit
The Fluke 1742/INTL Three-Phase Power Quality Logger can be used to assess power quality in accordance with the standards EN 50160 and IEEE 519. This instrument is fully compliant with IEC 61000-4-30 Class A Edition 3 and is capable of measuring and recording the following power parameters:
- Voltage
- Current
- Power
- Power Factor
- Frequency
- Energy forward/ reverse
- Peak demand
- THD
- Flicker
When used with three-phase and neutral voltage test leads and up to four flexible current probes (NOT included with the Fluke 1742/B model), the Fluke 1742/INTL Three-Phase Power Quality Logger can be used to measure all three voltage and current phases as well as neutral current.
It is capable of performing measurements anywhere on the power installation and can be placed at the service entrance, the substation or the load. It is suitable for troubleshooting and analysing power distribution systems as well as quantifying energy usage.
Ergonomic, Rugged Design
To ensure that the Power Quality Logger’s ports (including USB, Ethernet, AUX and I/O ports) are protected from dust and water ingress when not in use they have been constructed in compliance with IP65. The body of the Fluke 1742/INTL is also IP65-certified (when used with an IP65 voltage adapter).
Additionally, the Fluke 1742/INTL Three-Phase Power Quality Logger features the highest safety rating in the industry (600V CAT IV/ 1000V CAT III), expanding its scope-for-use: it can be used downstream and at service entrances.
Furthermore, the logger’s wide power range (it will go from 100V to 500V automatically) means that it can derive a power source from the circuit-under-investigation. Nevertheless, this instrument is also supplied with a lithium-ion battery capable of powering the unit for up to four hours. The inclusion of this battery means that it will remain operational despite temporary power disruptions to the circuit-under-investigation. It is also possible to power the Power Quality Logger using a wall line cord.
Also expanding the Fluke 1742/INTL Three-Phase Power Quality Logger’s scope-for-use and improving its practicality is its small dimensions: 23cm x 18cm x 5.4cm. Its compact construction means that it is able to be used in tight spaces. Moreover, as this instrument can be secured using a standard chain or another security instrument, protecting it against theft, it can be left safely in the field.
Accessories
In addition to its compact size, the Fluke 1742/INTL Three-Phase Power Quality Logger is also supplied with accessories that allow it to access conductors in remote and difficult-to-reach locations.
It is equipped with a 2m test lead and thin, IP65, flexible iFlex current probes (NOT included with the Fluke 1742/B model) enabling access to tight spaces and awkwardly located conductors. Up to four iFlex current probes can be connected to the Three-Phase Power Quality Logger, each probe is connected separately to ensure maximum measurement flexibility. Furthermore, the wide ranges of the probes (probe dependent) ensure that a high level of accuracy is maintained regardless of the application.
System Interface
Also working to maintain a high level of measurement accuracy is the Fluke 1742/INTL Three-Phase Power Quality Logger’s automatic recognition, scaling and powering of the connected probes and/or clamps. Furthermore, its intelligent verification feature automatically checks that probes, clamps and test leads are connected correctly and will digitally adjust faulty connections without the user having to disconnect or reconnect additional components. Incorrect connections are indicated by an amber light visible through the power button; this light changes to green when connections are correct or have been corrected.
In addition to this, the quick, graphical and guided PC-application setup provides a simple and easy method by which to configure the instrument for various applications.
Memory and Data Download
The Fluke 1742/INTL Three-Phase Power Quality Logger also includes internal memory. This tool will measure and save a number of power parameters automatically in order to ensure that measurement trends are complete.
As mentioned above, it includes a number of ports via which data can be downloaded. It is possible to transfer data to a PC via an Ethernet or USB interface. TIt features two USB ports enabling the simultaneous transfer of data to a PC via a USB interface and directly to a USB memory stick. This allows the user to leave the Fluke logger in the field, saving data to a removable memory stick, whilst he/she views the measurements from a safer distance via a PC.
Alternatively, data may be transferred to a PC via a Wi-Fi connection allowing the user to view data outside of the dangerous area, removing the need for PPE. Moreover, as data can be viewed in real-time, critical power quality and energy decisions may be made quickly.
Analysis and Reporting
Data transferred to a PC via a wired or wireless connection can be viewed, analysed and/or organised into reports using the included Fluke Energy Analyse Plus Software. At the touch of a button, the Fluke Energy Analyse Plus Software can create EN 50160, IEEE 519 and GOST 33073 reports. Report templates can be altered in order to accommodate evolving standards.
Moreover, the Fluke Energy Analyse Plus Software include a number of analysis features that allow the user to inspect and evaluate every detail of the energy consumption and power quality state-of-health. The user can perform advanced data correlation by selecting particular parameters to create a customised view. It is also possible to see hour/hour, day/day and week/week data comparisons using the Fluke Energy Analyse Plus Software.
Finally, if required, data can be exported for use with third-party software programs. The Fluke Energy Analyse Plus Software is able to export data in NeQual and PQDIF formats.
The Fluke 1742/INTL Three-Phase Power Quality Logger is an effective diagnostic, inspection and maintenance tool with an eclectic array of measurement functions optimised for simple load and energy studies.
Probe Options
The Fluke 1742/INTL Three-Phase Power Quality Logger is optimised for simple load and energy studies; it is suitable for engineers and technicians working in the UK, US, Europe, Australia, Brazil and China. The Fluke 1742/INTL Three-Phase Power Quality Logger is available in three kits that vary in regards to their iFlex current probes:
SKU | Accessories |
FLUKE 1742/B/INTL | WITHOUT Probe |
FLUKE 1742/15/INTL | with 1500A iFlex Probes |
FLUKE 1742/30/INTL | with 3000A iFlex Probes |
Key Features
- Optimised for simple load and energy studies
- Suitable for engineers and technicians working in the UK, US, Europe, Australia, Brazil and China
- Available in three kits that vary in regards to their included iFlex current probes
- Assess power quality in accordance with EN 50160 and IEEE 519 standards
- Compliant with IEC 61000-4-30 Class A Edition 3
- Measures and logs a variety of power parameters
- Voltage
- Current
- Power
- Power Factor
- Frequency
- Energy forward/ reverse
- Peak demand
- THD
- Flicker
- Measure all three voltage and current phases as well as neutral current using three-phase and neutral voltage test leads and up to four flexible current probes (NOT included with the Fluke 1742/B)
- Can perform measurements at any point on the power installation, from the service entrance to the substation to the load
- Troubleshoot and analyse power distribution systems
- Quantify energy usage
- IP65 ports
- IP65 body (when used with an IP65 voltage adapter)
- Highest safety rating in the industry: 600V CAT IV/ 1000V CAT III
- Wide power range: automatically goes from 100V to 500V
- Can be powered by the circuit-under-investigation
- Supplied with a lithium-ion battery capable of providing up to four hours of power
- Can be powered using a wall line cord
- Small dimensions: 23cm x 18cm x 5.4cm
- Suitable for use in tight spaces
- Can be secured using a standard chain or another security instrument
- Supplied with a 2m test lead for accessing awkwardly placed conductors
- Thin, IP65, flexible iFlex current probes (NOT included with the Fluke 1742/B) for accessing tight spaces
- The wide ranges of the iFlex current probes ensure that they can provide a high level of accuracy regardless of the application
- Automatically recognises, scales and powers the connected probes and/or clamps
- Intelligent verification feature automatically checks that probes, clamps and test leads are connected correctly
- The intelligent verification feature digitally corrects faulty connections
- An amber light indicates incorrect connections
- A green light indicates correct connections
- Quick, graphical and guided PC-application setup
- Internal memory
- A number of power parameters are saved automatically to ensure measurement trends are complete
- Transfer data to a PC via a USB, Ethernet or Wi-Fi connection
- Two USB ports
- Download data directly to a USB stick
- View data remotely via a PC and Wi-Fi connection
- Supplied with Fluke Energy Analyse Plus Software
- Create EN 50160, IEEE 519 and GOST 33073 reports using the supplied software
- Alter report templates to accommodate for evolving standards
- Analyse every aspect of the energy consumption and power quality state-of-health using the Fluke Energy Analyse Plus Software
- Select particular parameters to create a customised view and perform advanced data correlation
- View day/day, week/week and hour/hour data comparisons
- Export data in NeQual and PQDIF formats for use with third party software
- An effective diagnostic, inspection and maintenance tool optimised for simple load and energy studies
What’s Included?
- Your Choice of Fluke 1742/INTL Three-Phase Power Quality Logger Kit (see below)
Items | FLUKE1742/B/INTL | FLUKE1742/15/INTL | FLUKE1742/30/INTL |
Fluke 1742/INTL Three-Phase Power Quality Logger | • | • | • |
1500A iFlex Current Probes (60cm) | - | • | - |
3000A iFlex Current Probes (60cm) | - | - | • |
USB Stick | • | • | • |
USB Cable | • | • | • |
3PHVL-1730 3-Phase + neutral voltage test lead | • | • | • |
Test lead set red/black 0.18 m | • | • | • |
Test lead set red/black 1.5 m | • | • | • |
Alligator clips | 4 | 4 | 4 |
173x/174x Soft Case | • | • | • |
Cable marker kit | • | • | • |
The Fluke 1742/INTL Three-Phase Power Quality Logger can be upgraded to the Fluke 1746/INTL or 1748/INTL Three-Phase Power Quality Logger; please contact our sales team for further information.
- PASS Power Bank & Magnetic Wireless Charger (10 000mAh 15W) - PASSPOWER-PLUS, typically £49.00
Fluke 174X Three-Phase Power Quality Loggers Technical Specifications
Please note that the Fluke 1742/INTL Three-Phase Power Quality Loggers are part of Fluke's range of 174X Three-Phase Power Quality Loggers; the table below details the technical specifications for all the models included in this range.
Specifications | |||||
Accuracy | |||||
Parameter | Range | Maximum Resolution | Intrinsic Accuracy at Reference Conditions (% of Reading +% of Range) | ||
Voltage | 1000 V | 0.1 V | ±0.1 % of nominal voltage 1, 2 | ||
Current: Direct input | i17xx-flex 1500IP 24 1500 A | 150 A | 0.01 A (min. 1.5A)3 | ±(1% + 0.02%) | |
1500 A | 0.1 A | ||||
i17xx-flex 3000IP 24 3000 A | 300 A | 0.01 A (min. 3.0 A)3 | ±(1% + 0.03%) | ||
3000 A | 0.1 A | ||||
i17xx-flex 6000IP 36 6000 A | 600 A | 0.01 A (min. 6.0 A)3 | ±(1.5% + 0.03%) | ||
6000 A | 0.1 A | ||||
i40s-EL clamp | 4 A | 1 mA | ±(0.7% + 0.02%) | ||
40 A | 10 mA | ||||
Frequency | 42.5 Hz to 69 Hz | 0.01 Hz | ±(0.1%)2 | ||
Auxiliary input | ±10 V dc | 0.1 mV | ±(0.2% + 0.02%) | ||
Voltage min/max | 1000 V | 0.1 V | ±0.2 % of nominal input voltage1 | ||
Current min/max | Defined by accessory | Defined by accessory | ±(5% + 0.2%) | ||
THD on voltage | 1000% | 0.10% | ± 2.5% | ||
THD on current | 1000% | 0.10% | ± 2.5% | ||
Voltage harmonics 2nd to 50th | 1000 V | 0.1 V | ≥ 1 V: ±5% of reading | ||
< 1 V: ±0.05V | |||||
Current harmonics 2nd to 50th | Defined by accessory | Defined by accessory | ≥ 3% of current range: ±5% of reading | ||
< 3% of current range: ±0.15% of range | |||||
Flicker PLT, PST | 0 to 20 | 0.01 | 5% | ||
Current probe accuracy | |||||
Parameter | Influence quantity/ | iFlex1500IP-24 | iFlex3000IP-24 | iFlex6000IP-36 | i40S-EL |
150 A / 1500 A | 300 A / 3000 A | 600 A / 6000A | 4 A / 40 A | ||
Active Power P | PF ≥ 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Active Energy Ea | |||||
Apparent power S | 0 ≤ PF ≤ 1 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Apparent Energy Eap | |||||
Reactive power Q | 0 ≤ PF ≤ 1 | 2.5% of measured apparent power | |||
Reactive Energy Er | |||||
Power Factor PF | - | ±0.025 | |||
Displacement Power | |||||
Factor DPF/cosΦ | |||||
Additional uncertainty in% of range | VP-N>250 V | 0.015% | 0.023% | 0.023% | 0.015% |
1 In the range of 100 V … 500 V; also known as Udin 2 0 °C … 45 °C: Intrinsic accuracy x 2, outside of 0 °C … 45 °C: Intrinsic accuracy x 3 3 Consult operators manual for details Reference conditions: Environmental: 23 °C ± 5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65 % Input conditions: Cosφ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10 %. Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V Input current: I > 10 % of I range Primary conductor of clamps or Rogowski coil in center position Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C |
|||||
Electrical Specifications | |||||
Power Supply | |||||
Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit | ||||
100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7) | |||||
Power consumption | Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter) | ||||
Efficiency | ≥ 68.2% (in accordance with energy efficiency regulations) | ||||
Maximum no-load consumption | < 0.3 W only when powered using IEC 60320 input | ||||
Mains power frequency | 50/60 Hz ±15% | ||||
Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable | ||||
On-battery runtime | Typically 4 hours | ||||
Charging time | < 6 hours | ||||
Data Acquisition | |||||
Resolution | 16-bit synchronous sampling | ||||
Sampling frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency | ||||
Input signal frequency | 50/60 Hz (42.5 to 69 Hz) | ||||
Circuit types | 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies) | ||||
Data storage | Internal flash memory (not user replaceable) | ||||
Memory size | Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events | ||||
Basic Interval | |||||
Measured parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy | ||||
Averaging interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min | ||||
Averaging time min/max values | Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms) | ||||
Demand Interval (Energy Meter Mode) | |||||
Measured parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy | ||||
Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off | ||||
Power Quality Measurements | |||||
Measured parameter | Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation | ||||
Averaging interval | 10 min for all parameters 2 hrs (long term Flicker PLT) 150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT) |
||||
Individual harmonics | 2nd to 50th harmonic Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only |
||||
Interharmonics | 1st to the 50th interharmonic | ||||
Total harmonic distortion | Calculated on 50 voltage harmonics | ||||
Events | Voltage: dips, swells, interruptions, current: inrush current 1748: mains signaling, transients (low frequency) |
||||
Triggered recordings | RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30) | ||||
Waveform of voltage and current up to 200 ms, 10/12 cycles | |||||
Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s | |||||
Inrush | RMS profile based on 1/2 cycle RMS steady state triggering | ||||
Flicker | In accordance with IEC 61000-4-15 and IEEE 1453 | ||||
Mains signaling | Two user defined frequencies up to 3 kHz | ||||
PQ Health | Summarizes power quality measurements in one table. Detailed data available for each parameter | ||||
EN 50160 | Compliance with standard | ||||
Programmable PQ limits | Enables user defined limits for local standards compliance | ||||
Standards Compliance | |||||
Harmonics | IEC 61000-4-7: Class 1 | ||||
IEEE 519 (short time and very short time harmonics) | |||||
Power quality | IEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device) | ||||
Power | IEEE 1459 | ||||
Power quality compliance | EN 50160 | ||||
Safety | General: IEC 61010-1: Pollution Degree 2 | ||||
Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V | |||||
Power Supply: Overvoltage Category IV, Pollution Degree 2 | |||||
Li-ion Battery: IEC 62133 | |||||
Interfaces | |||||
USB-A | File transfer via USB flash drive, firmware updates, max. supply current: 120 mA | ||||
WiFi | File transfer and remote control via direct connection or WiFi infrastructure | ||||
Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or WiFi/BLE adapter, check for availability) | ||||
USB-mini | Data download device to PC | ||||
Current Inputs | |||||
Number of inputs | 4 (3 phases and neutral), mode selected automatically for attached sensor | ||||
Input voltage | Clamp input: 500 mVrms/50 mVrms; CF 2.8 | ||||
Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range | |||||
Range | 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 IP 24 | ||||
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 IP 24 | |||||
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 IP 36 | |||||
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL | |||||
Bandwidth | 42.5 Hz - 3.5 kHz | ||||
Scaling | 1:1 and variable | ||||
Auxiliary Inputs | |||||
Number of inputs | 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously) | ||||
Input range | 0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s | ||||
Scale factor | Format: mx + b (gain and offset) user configurable | ||||
Displayed units | User configurable (7 characters, for example, °C, psi, or m/s) | ||||
Wireless Bluetooth connection (check for availability) | |||||
Number of inputs | 2 | ||||
Supported modules | Fluke Connect® 3000 series | ||||
Acquisition | 1 reading/s | ||||
Environmental Specifications | |||||
Operating temperature | -25 °C to +50 °C (-13 °F to 122 °F)1 | ||||
Storage temperature | Without battery: -25 °C to +60 °C (-13 °F to 140 °F), with battery: -20 °C to +50 °C (−4 °F to 122 °F) | ||||
Operating humidity | IEC 60721-3-3: 3K6: | ||||
-25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 % | |||||
40 °C (104 °F): 55 % | |||||
50 °C (122 °F): 35 % | |||||
Operating Altitude | 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) | ||||
Storage altitude | 12,000 m | ||||
Enclosure | IEC 60529: IP50 | ||||
IEC 60529: IP65 with IP65 rated voltage connector | |||||
Vibration | IEC 60721-3-3 / 3M2 | ||||
Electromagnetic compatibility (EMC) | EN 61326-1: Industrial CISPR 11: Group 1, Class A | ||||
IEC 61000-6-5 Power station environment | |||||
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) | |||||
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 | |||||
General Specifications | |||||
Warranty | Two-years (battery not included) | ||||
Accessories: one-year | |||||
Calibration cycle: two-years | |||||
Dimensions | 23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in) | ||||
Weight | Instrument: 1 kg (2.2 lb) | ||||
Tamper protection | Accept securing cables (max. Φ 6mm) | ||||
1Warm up the product to -10 °C (+14 °F) before you power the unit on | |||||
Flexible Current Probe Specifications | |||||
Specifications | i17XX-FLEX1.5KIP | i17XX-FLEX3KIP | |||
Measuring range | 1 to 150 A ac/10 to 1500 A ac | 1 to 300 A ac 10 to 3000 A ac | |||
Probe cable length | 610 mm (24 in) | 610 mm (24 in) | |||
Probe cable diameter | 7.5 mm (0.3 in) | 7.5 mm (0.3 in) | |||
Weight | 170 g (0.38 lb) | 170 g (0.38 lb) | |||
Minimum bending radius | 38 mm (1.5 in) | ||||
Nondestructive current | 100 kA (50/60 Hz) | ||||
Temperature coefficient over operating temperature range |
0.05 % of reading/°C (0.028 % of reading/°F) | ||||
Working voltage | 1000 V CAT III, 600 V CAT IV | ||||
Output cable length | 2.0 m (6.5 ft) | ||||
Probe cable material | TPR | ||||
Weight | 115 g | ||||
Probe cable material | TPR | ||||
Coupling material | POM + ABS/PC | ||||
Output cable | TPR/PVC | ||||
Operating temperature | -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F) | ||||
Temperature, non-operating | -40 °C to +80 °C (-40 °F to 176 °F) | ||||
Relative humidity, operating | 15% to 85% non-condensing | ||||
IP rating | IEC 60529: IP65 | ||||
Warranty | One-year |
Fluke 174X Three-Phase Power Quality Loggers Comparison Table
Functions | 1742 Power Quality Loggers | 1746 Power Quality Loggers | 1748 Power Quality Loggers |
Voltage, current, power, power factor, frequency | X | X | X |
Energy forward/reverse | X | X | X |
Peak Demand | X | X | X |
THD | X | X | X |
Voltage and current harmonics (to 50th)1 | X | X | |
Flicker | X | X | X |
Unbalance1 | X | X | |
Rapid voltage change events1 | X | X | |
Interharmonics (to 50th)1 | X | X | |
Dips, swells, interruption and transient events tables1 | X | X | |
Mains signaling | X | X | |
Inrush current1 | X | X | |
Transients (low frequency)/Waveform deviation events2 | X | ||
Recording | 1742 Power Quality Loggers | 1746 Power Quality Loggers | 1748 Power Quality Loggers |
Trend | X | X | X |
Waveform snapshots2 | X | ||
RMS profile2 | X | ||
Communication | 1742 Power Quality Loggers | 1746 Power Quality Loggers | 1748 Power Quality Loggers |
Ethernet | X | X | X |
USB (mini B) | X | X | X |
WiFi download Instrument to device | X | X | X |
Wifi download via WiFi hub (requires registration) | Opt | Opt | Opt |
Included accessories | 1742 Power Quality Loggers | 1746 Power Quality Loggers | 1748 Power Quality Loggers |
Flexible current probe | not /B version | not /B version | not /B version |
USB stick | X | X | X |
USB cable | X | X | X |
3PHVL-1730 3-Phase + neutral voltage test lead | X | X | X |
Test lead set red/black 0.18 m | X | X | X |
Test lead set red/black 1.5 m | X | X | X |
Alligator clips | 4 | 4 | 4 |
173x/174x Soft Case | X | X | X |
Cable marker kit | X | X | X |
MP1-3R/1B-Magnet Probe 1 set (3 red, 1 black) | Opt | 1 | 1 |
174x-Hanger Kit | Opt | Opt | X |