All Fluke Products

Fluke 1630-2 Earth Ground Loop & Leakage Clamp

SKU
4829515
Rating:
0%
(0)
Reward Points
:
1289
£1,546.80 £1,289.00
Lead Time: 2-3 Weeks
Free UK Delivery*
Advice & Support Call 01642 931329 or contact us
Price Match We won't be beaten, let us know
Fluke 1630-2 Earth Ground Loop & Leakage Clamp

The Fluke 1630-2 Earth Ground Loop & Leakage Clamp is a stake-less earth ground loop and AC leakage current clamp for testing the grounding components of equipment in hard-to-reach places such as indoor spaces or fully paved areas. It can be used to measure earth ground resistance and AC leakage current quickly and safely. For instance, you can identify ground loop resistance without having to disconnect then reconnect the earth electrode from the system and identify AC leakage currents without disconnecting the earth ground stake from the grounding system. As a result, the Fluke 1630-2 Earth Ground Loop & Leakage Clamp is ideal for system troubleshooting.

A band-pass filter removes unwanted noise from the AC leakage current measurement while user-configurable high and low alarm limits provide instantons measurement evaluation. Additionally, data is automatically recorded at preset intervals; the Fluke 1630-2 Earth Ground Loop & Leakage Clamp’s internal memory has the capacity to store up to 32 760 measurements.

Finally, this rugged clamp meter’s heavy-duty jaws remain in alignment and in calibration even in challenging industrial environments. The Fluke 1630-2 Earth Ground Loop & Leakage Clamp is a durable, dependable, data logging clamp meter.

Fluke 1630-2 Earth Ground Loop & Leakage Clamp Key Features

  • A stake-less earth ground loop and AC leakage current clamp
  • Test the grounding components of equipment that is hard-to-reach
  • Measure earth ground resistance and AC leakage quickly and safely
  • Identify ground loop resistance without having to disconnect the earth ground stake from the grounding system
  • Ideal for system troubleshooting
  • The band-pass filter removes unwanted noise from the AC leakage current measurement
  • User-configurable high and low alarm limits
  • Data is automatically recorded at preset intervals
  • Memory capacity: 32 760 data points
  • Rugged
  • Heavy-duty clamp jaws remain in alignment and in calibration even in challenging industrial environments
  • A durable, dependable, data logging clamp meter

What’s Included?

  • Fluke 1630-2 Earth Ground Loop & Leakage Clamp
  • Hard Case
  • 4x AA Batteries
  • Safety Information Guide
  • Quick Reference Guide

Please note that this model does not include Fluke Connect software; please click here for a Fluke Connect-enabled version.

Fluke 1630-2 Earth Ground Loop & Leakage Clamp Technical Specifications 

Electrical Specifications 
Maximum voltage to earth ground 1000 V
Battery type 4 x 1.5 V AA alkaline IEC/EN LR6
Battery life More than 15 hours*
Frequency range 40 Hz to 1 kHz
Ingress protection IEC/EN 60529: IP30 with jaw closed
LCD Digital reading 9999 counts
Refresh rate 4/s
Temperature Operating -10 °C to +50 °C (14 °F to +122 °F)
  Storage -20 °C to +60 °C (-4 °F to +140 °F)
Operating humidity Non condensing (<10 °C) (< 50 °F)
≤90 % RH (at 10 °C to 30 °C [50 °F to 86 °F])
≤75 % RH (at 30 °C to 40 °C [86 °F to 104 °F])
≤45 % RH (at 40 °C to 50 °C [104 °F to 122 °F])
(Non condensing)
Altitude Operating 2000 m (6561 ft.)
Storage 12,000 m (39370 ft.)
Reference temperature 23 °C ±5 °C (73 °F ±9 °F)
Temperature coefficient 0.15 % X (specified accuracy)/ °C (<18 °C or >28 °C ([<64.4 °F or >82.4 °F])
Overload indication OL
Display Reading Specification with
Loop Resistance Standard
Input (Ω) Minimum Maximum
0.474 0.417 0.531
0.5 0.443 0.558
10 9.55 10.45
100 96 104.0
Data logging capacity Minimum of 32,760 measurements
Data logging interval 1 second to 59 minutes and 59 seconds
Safety General IEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1
Measurement IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V
Current clamp for leakage current measurements IEC/EN 61557-13: Class 2, ≤30 A/m
Resistance to Earth IEC/EN 61557-5
Effectiveness of the protective measures IEC/EN 61557-16: cutoff frequency 20 kHz (-3 dB)
Electromagnetic
compatibility
(EMC)
International IEC/EN 61326-1: Portable Electromagnetic Environment
CISPR 11: Group 1, Class B, IEC/EN 61326-2-2
Korea (KCC) Class A equipment (Industrial Broadcast & Communications Equipment)
USA (FCC) 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
Note  * In Ground Resistance measurement mode, with backlight turned off, and RF mode turned off
Wireless Radio
Frequency range 2412 MHz to 2462 MHz
Output power <10 mW
Radiofrequency certification FCC ID:T68-FBLE IC:6627A-FBLE
General Specifications 
Conductor size 40 mm (1.57 in) approximately
Dimensions (L x W x H) 283 mm x 105 mm x 48 mm (11.1 in x 4.1 in x 1.9 in)
Weight 880g (31 oz)
Fluke 1630-2 Earth Ground Loop & Leakage Clamp Datasheet Datasheets Fluke 1630-2 Earth Ground Loop & Leakage Clamp User Manual Manuals & Guides

Reviews

Additional Information
SKU 4829515
Manufacturer Part Code 4829515