Optimised to deliver versatility during both troubleshooting and preventative maintenance, the Fluke 1587T Insulation Multimeter is a reliable and simple-to-use instrument specifically designed for the telecoms industry. Ideal for when you are working on motors, generators, cables, and switchgear, this digital multimeter with a large, 6000-count, backlit display can measure the following electrical parameters:
The Fluke 1587T Insulation Multimeter includes a selectable filter for measuring the voltage and frequency of motor drives. It also supports manual- and auto-ranging and delivers automatic discharge of capacitive voltage for improved user safety. Additionally, a special remote-control probe also offers safe and easy measurement, while live circuit detection prevents insulation tests if a voltage greater than 30V is detected, and an Input Alert indicates incorrect connections.
Finally, an Auto Power Off function works to conserve the Fluke 1587T Insulation Multimeter’s battery life.
The Fluke 1587T Insulation Multimeter is an easy-to-use, dependable multimeter optimised for the telecoms industry and featuring an eclectic array of measurement functions.
Insulation Specifications | |
Measurement Range | 0.01 to 100 MΩ |
Test Voltages | 50 V, 100 V Accuracy: + 20%, -0% |
Insulation Test Current | 1 mA nominal |
Auto Discharge | Discharge time < 0.5 s for C = 1 µF or less |
Maximum Capacitive Load | Up to 1 µF load |
Multimeter Specifications | |
Voltage DC | Maximum: 1000 V Maximum Resolution: 1 mV Accuracy: ± (0.09% + 2) |
Voltage AC | Maximum: 1000 V Maximum Resolution: 0.1 mV Accuracy: ± (2% + 3) |
Current DC | Maximum: 400 mA Maximum Resolution: 0.01 mA Accuracy: ± (0.2% + 2) |
Current AC | Maximum: 400 mA Maximum Resolution: 0.01 mA Accuracy: ± (1.5% + 2) |
Resistance | Maximum: 50.0 MΩ Maximum Resolution: 0.1 Ω Accuracy: ± (0.9% + 2) |
Capacitance | Maximum: 9999 µF Maximum Resolution: 1 nF Accuracy: ± (1.2% + 2) |
Frequency | Maximum: 99.99 kHz Maximum Resolution: 0.01 Hz Accuracy: ± (0.1% + 1) |
Temperature | Maximum: -40 to 998.6°F (-40 to 537°C) Maximum Resolution: 32.1°F (0.1°C) Accuracy: ± (1% + 10) |
General Specifications | |
Temperature | Operating: -4 to 131°F (-20 to 55°C) Storage: -40 to 140°F (-40 to 60°C) |
Power Supply | 4 x AA Batteries (NEDA 15A or IEC LR6) |
Battery Life | Meter: 1000 hrs Insulation Test: > 1000 tests |
Dimensions | 8 x 4 x 2" (203 x 100 x 50 mm) |
Weight | 1.2 lbs (0.55 kg) |