The Fluke 1555 insulation tester, joined by the completely redesigned 1550C, is the ideal choice for digitally testing insulation resistance up to 10kV and 2TΩ. Rated best in class IEEE 43-2000, this product is capable of testing a wide range of voltage equipment including, but not limited to, generators, motors, and cables and comes with a three year warranty as well as both a CAT III and CAT IV 600 V safety rating.
The 1555 features a wide range of selectable test voltages in 50 V steps from 250 up to 1000 V and 100 V steps for anything above and beyond 1000 V. Capable of measuring both capacitance and leakage current, the unit comes equipped with voltage breakdown detection which alerts the user of any present voltage up to 600 V ac of dc. An additional guard system also exists to eliminate the effect of surface leakage current when testing high-resistance measurements.
Automatic calculation of Delectric Absorption (DAR) and Polarization Index (PI) is instantly accessible with no additional setup required.
The Fluke 1555 is extremely user friendly as it comes fully equipped with a large digital/analog LCD screen perfect for easy viewing along with 99 memory locations capable of storing user measurements. Each unit of memory stored can also be given a unique, user defined label to help keep measurements organized and easily accessible for future recall.
Additionally, the 1555 features a battery that boasts a life span of over 750 tests between charges and a timer with a 99 minute cap for those lengthy resistance testing sessions.
The Fluke 1555 is the perfect tool for taking preventative measures or providing predictive maintenance to stave off any potential equipment failures well before they occur.
Fluke 1555 Insulation Resistance Tester Key Features
- Test voltage up to 10kV
- Tests insulation resistance up to 2TΩ
- CAT III 1000V and CAT IV 600V safety ratings
- Warning function when live voltage is present
- Selectable test voltages in 50V steps from 250V to 1000V and steps of 100V above 1000V
- 99 memory locations for storage of testing records
- Long battery life lasts up to 750 tests between charges
- Automatic calculation of Dielectric Absorption (DAR) and Polarisation Index (PI)
- Guard system eliminates the effects of surface leakage current
- Combined digital and analogue LCD screen
- Capacitance and leakage current measurements
- Ramp function
- Timer
Full List of Products Included
- Fluke 1555 Insulation Resistance Tester
- Test Cables with Alligator Clips (Red, Black and Green)
- Infrared Adapter with Interface Cable
- FlukeView Forms Basic CD-ROM
- AC Power Cord
- Soft Carrying Case
- English Manual
- User Manual on CD-ROM
- Quick Reference Card
- Software License Agreement
- Registration Card
- FlukeView Forms Installation Guide
- USB-IR Cable Installation Guide
Fluke 1555 Technical Specifications
Insulation resistance measurement |
||
Test voltage (dc) |
Range (dc) |
Accuracy (± reading) |
250 V | < 200 kΩ 200 kΩ to 5 GΩ 5 GΩ to 50 GΩ > 50 GΩ |
unspecified 5 % 20 % unspecified |
500 V | 200 kΩ 200 kΩ to 10 GΩ 10 GΩ to 100 GΩ > 100 GΩ |
unspecified 5 % 20 % unspecified |
1000 V | < 200 kΩ 200 kΩ to 20 GΩ 20 GΩ to 200 GΩ > 200 GΩ |
unspecified 5 % 20 % unspecified |
2500 V | < 200 kΩ 200 kΩ to 50 GΩ 50 GΩ to 500 GΩ > 500 GΩ |
unspecified 5 % 20 % unspecified |
5000 V | < 200 kΩ 200 kΩ to 100 GΩ 100 GΩ to 1 TΩ > 1 TΩ |
unspecified 5 % 20 % unspecified |
10000 V (1555 only) |
< 200 kΩ 200 kΩ to 200 GΩ 10 GΩ to 2 TΩ > 2 TΩ |
unspecified 5 % 20 % unspecified |
Bar graph range | 0 to 1 TΩ | |
Insulation test voltage accuracy | -0 %, +10 % at 1 mA load current | |
Induced ac mains current rejection | 2 mA maximum | |
Charging rate for capacitive load |
5 seconds per μF |
|
Discharge rate for capacitive load |
1.5 s/μF |
|
Leakage current measurement |
Range: 1 nA to 2 mA |
Accuracy: ± (5 % + 2 nA) |
Capacitance measurement |
Range: 0.01 uF to 15.00 μF |
Accuracy: ± (15 % rdg + 0.03 μF) |
Timer |
Range: 0 to 99 minutes |
Resolution Accuracy: |
Live circuit warning |
Warning Range: |
Voltage Accuracy: |
General specifications |
|
Display | 75 mm x 105 mm |
Power | 12 V lead-acid rechargeable battery, Yuasa NP2.8-12 |
Charger Input (AC) | Charger Input (AC) 85 V to 250 V ac 50/60 HZ 20 VA |
This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only. | |
Dimensions | 170 mm x 242 mm x 330 mm (6.7 in x 9.5 in x 13 in) |
Weight | 3.6 kg (7.94 lb) |
Temperature (operating) | -20 ºC to 50 ºC (-4 ºF to 122 ºF) |
Temperature (storage) | -20 ºC to 65 ºC (-4 ºF to 149 ºF) |
Humidity | 80 % to 31 ºC decreasing linearly to 50 % at 50 ºC |
Altitude | 2000 m |
Enclosure sealing | IP40 |
Input overload protection | 1000 V ac |
Electromagnetic compatibility | EN 61326 |
Certifications | |
Safety compliance | CAT III 1000 V, CAT IV 600 V |
Pollution degree | 2 |
Reviews
SKU | FLUKE1555 |
---|---|
Manufacturer Part Code | 3665056 |
Model Ref | Fluke 1555 |
Country of Origin | United States |