Isolate problems with power quality on 3-phase electrical equipment with this power analyser from Extech.
Optimised for use in both indoor and outdoor conditions with a sun-readable numerical backlit LCD screen, the Extech 382100 performs comprehensive system analysis, with the ability to measure, display and log up to 35 different parameters. Measurements are captured automatically on the included SD card and can be ported seamlessly into MS Excel for further analysis on PC (there is space for up to 30,000 readings on the SD card).
The Extech 382100 can be used to measure voltage (both phase-to-phase and phase-to-ground), current (phase-to-ground, KW, KVA, KVAR, and PF (phase and system), KWH, KVAH, KVARH and PFH (system) and phase angle. A set of high-accuracy auto-ranging current clamps isincluded as standard with the analyser for measuring current levels from 0.2A to 1200A.
You can set the Extech 382100 to store readings across a wide range from every 2 seconds to every 2 hours, making this analyser ideal for longer studies, or complex studies where you are trying to isolate a particular fault.
If you're testing high-power distribution systems, the Extech 382100 also includes an adjustable current transformer (CT) and potential transformer (PT).
Extech 381200 Power Analyser Key Features
- Measure overall power quality on 3-phase electrical systems
- Large-size dot matrix, sun-readable, numerical backlit LCD screen
- Measure AC voltage to 600V (true RMS)
- Measure AC to 1200A
- Active power measurements to 9.999MW
- Apparent power measurements to 9.999MVA
- Reactive power measurements to 9.999MVAR
- Power factor measurements from 0.00 to 1.00
- Frequency range from 45 to 65Hz
- Phase range from -180 to +180°
- Active power energy measurements from 0.0kWh to 9.999mWHr
- Apparent power energy measurements from 0.0KVAh to 9.999MVAh
- Reactive power energy measurements from 0.0VARh to 9.999MVARh
- Includes high accuracy, auto-ranging current clamps
- 600V AC input with CAT III 600V safety rating
- Adjustable CT ratio (1 to 600) and PT ratio (1 to 1000)
- Log up to 30,000 readings on a removeable 2GB SD memory card in Microsoft Excel format
- Wide sampling rate range from 2 seconds to 2 hours
- Easy to use, on-screen menu
What's Included?
- Extech 381200 Power Analyser
- 3 x Current Clamps
- 4 x Voltage Leads with Alligator Clips
- 8 x AA Batteries
- SD Memory Card
- Universal AC Adapter (100 to 240V)
- Carrying Case
- User Manual
Extech 382100 Technical Specifications
Parameter | Range | Basic Accuracy |
---|---|---|
AC Voltage | 600.0V | ±(0.5% rdg + 0.5V) |
AC Current | 1200A | ±(0.5% rdg + 0.5A) |
Active Power | 9.999MW | ±(1.0% rdg + 0.08KW) |
Apparent Power | 9.999MVA | ±(1.0% rdg + 0.08KVA) |
Reactive Power | 9.999MVAR | ±(1.0% rdg + 0.08KVAR) |
Power Factor | 0.00 to 1.00 | ±0.04 |
Frequency Range | 45 to 65Hz | ±0.1Hz |
Phase | -180 to +180.0° | ±1° |
Active Power Energy | 0.0KVAh to 9.999MWHr | ±(2.0% rdg + 0.08KWh) |
Apparent Power Energy | 0.0kVAh to 9.999MVAh | ±(2.0% rdg + 0.08KVAh) |
Reactive Power Energy | 0.0KVARh to 9.999MVARh | ±(2.0% rdg + 0.08KVARh) |
General Specifications | ||
Datalogging | 60,000 readings (2GB SD memory card) | |
CE/CAT Rating | CE/CAT III 600V | |
Dimensions | 225 x 125 x 64mm | |
Weight | 1049g |
Reviews
SKU | 382100 |
---|---|
Manufacturer Part Code | 382100 |
Country of Origin | Taiwan |