FREE - PASS The Complete Guide to EET (PAT) Testing, 5th Edition
Buy a PAT testing kit and get an updated PAT Testing Guide worth £24.99. This 129 page indepth PAT testing book is a great addition to your kit. View PAT Guide
Martindale EasyPAT 2100 PAT Tester - Kit 1
Ideal for those with a larger amount of appliances to test, our Martindale EasyPAT 2100 kit gives you everything you'll need for PAT testing in one comprehensive bundle pack. In this kit, you'll get all standard accessories + a special kit with labels, adapters and much more included.
What's Included?
- Martindale EasyPAT 2100 PAT Tester
- Earth Bond Lead
- Extension Lead Adapter
- 240V Socket to 110V Plug
- Flash Gun
- Accessory Bag
- Instruction Manual
You'll also receive:
- Soft Shell Carrying Case
- Socket Tester
- eLearning PAT Testing Course - Includes Exam and Certificate
- PASS PAT Testing Logbook
- Microwave Leakage Detector
- PASSPTA21 - IEC (C13 Female) to Cloverleaf (C6 Male) PAT Adaptor
- PASSPTA29 - IEC Plug (C14) to Cloverleaf (C5) PAT Adaptor
- PASSPTA28 - IEC Plug (C14) to Fig 8 (C7) PAT Adaptor
- CK Tools AVO5050 5 Piece Insulated Screwdriver Set
- 500 x Passed PAT Testing Labels
- 500 x Circular Passed PAT Testing Labels
- 250 x Cable Wrap Labels
- 250 x Failed PAT Testing Labels
Other EasyPAT 2100 Bundles
Not sure if this is the right kit for you? This table outlines the difference between each of our EasyPAT 2100 bundles
Item Description | EasyPAT 2100 PAT Tester Essentials Kit (Bundle 1) | EasyPAT 2100 PAT Tester Professional Kit (Bundle 2) |
---|---|---|
Soft Shell Carrying Case Keep all of your equipment safe and in one place with this large-size carrying case with a customisable foam insert (The appearance of the case may vary depending on current stock) |
√ | √ |
Socket Tester Need to check if your sockets are working right? Just plug this in to a standard UK plug socket and if there's a problem, the socket tester will let you know about it! |
√ | √ |
eLearning PAT Testing Course - Includes Exam and Certificate Gain a certificate of competency to carry out PAT testing in just two hours with our online PAT course and exam. Teams of staff may be trained by purchasing the course multiple times; each staff member will be assigned a unique activation code and login. |
√ |
√ |
PASS PAT Testing Logbook Keep a record of all of your testing with our logbook. The book includes carbon-copied records, allowing you to keep one for yourself and give the other to customers or keep for a reference. |
√ | √ |
Microwave Leakage Detector When PAT testing, it's common practice to check microwaves are also not emitting high levels of radiation. With our microwave leakage detector you'll be able to do this testing with ease. |
√ | √ |
PASSPTA21 - IEC (C13 Female) You'll need this adaptor to connect your PAT tester to laptop/PC power leads and other similar equipment which has a cloverleaf-shaped connector. |
√ | √ |
PASSPTA29 - IEC Plug (C14) This adaptor is used to connect to laptop power supplies, portable projectors and other similar equipment. |
√ | √ |
PASSPTA28 - IEC Plug (C14) You'll find several appliances such as game consoles, laptop power supplies, audio/visual equipment and more use this type of connector - with this adaptor, you can connect them up to your PAT tester. |
√ | √ |
CK Tools AV05050 5 Piece Insulated Screwdriver Kit A handy set of insulated screwdrivers (suitable for live working to 1000V) suitable for a wide variety of applications. |
√ | √ |
WM1 - 500 x Passed PAT Testing Labels You'll need these every time an appliance passes a test - just tear one off, fill in the fields (appliance ID, your name, test date and next test due date) and stick on the appliance when done. |
√ | √ |
WM6500 - 500 x Circular Passed PAT Testing Labels These circular-shaped PAT labels are great for plug tops and any other appliance. The labels also include space for ticking the month/year the next test is due. |
√ | √ |
WM12 250 - 250 x Cable Wrap Labels These passed labels wrap around a wire/cable from an appliance and are recommended for use with power supplies or on appliances where you can't stick a label. They also include space for writing your appliance ID, name, test date and next test date. |
√ | √ |
WM7 250 - 250 x Failed PAT Testing Labels You won't need these as often as your passed labels, but you'll need to apply one of these whenever an appliance fails a test. If it does fail, the item should be taken out of service for repair or replacement |
√ | √ |
SimplyPats Manual PAT Testing Software Keep a database of your PAT testing information on your PC and print reports with SimplyPats Manual software. Please note that this software is manual entry; you cannot download directly from the PAT tester and you will need to type in records by hand. |
- | √ |
- PASS The Complete Guide to EET (PAT) Testing, 5th Edition - PASS-PAT-HB, typically £24.99
Martindale EasyPAT 2100 Technical Specifications
Case | Size: 330 x 263 x 144mm Weight: 5.1kg |
Temperature | Operating: 0 to 35°C Storage: -10 to 50°C |
Supply | Voltage: 110V/240V ±10% 50/60Hz Power Consumption: 10/220V A (excluding run) |
Earth Continuity Test (8A) | |
Test Voltage | 6V AC nominal with no load |
Test Current | 8A AC nominal @ 0.1Ω. 5A nominal @ 0.5Ω |
Range | 0.1 - 99Ω |
Accuracy | ±10% of reading ± 2 digits |
Earth Continuity Test (25A) | |
Test Voltage | 6V AC nominal with no load |
Test Current | 25A AC nominal @ 0.1Ω. 10A AC nominal @ 0.5Ω |
Range | 0.1 - 99Ω |
Accuracy | ±10% of reading ± 2 digits |
Earth Screen Test (100mA) | |
Test Voltage | 130mV DC nominal open circuit |
Test Current | 100mA DC nominal constant current |
Range | 0.1 - 99Ω |
Accuracy | ±10% of reading ± 1 digit |
Insulation Test | |
Test Voltage | 500V DC, -0%, +20%, at 2MΩ and 7MΩ |
Short Circuit Current | 1mA DC nominal |
Display Range | 0 to 19.9MΩ |
Accuracy of Indication | ±5% of reading ± 1 digit |
Run Current Test | |
Range | 0 to 19.9A |
Accuracy | ±10% of reading ± 1 digit |
Earth Leakage Test | |
Range | 0 to 19.9mA |
Accuracy | ±10% of reading ± 1 digit |
Flash Test | |
Test Voltage | 1.5kV AC - Class I. 3.0kV AC - Class II |
Display Range | 0 to 19.9mA AC |
Usable Range | 0-3mA AC (current trip @ 4mA nominal) (short circuit current 5mA nominal) |
Accuracy | ±5% of reading ± 1 digit |
Leads | |
Mains | 1.5m fixed lead with 13A moulded plug |
Earth Continuity | 1.5m long, detachable lead with a heavy duty, shrouded crocodile clip |
Flash Gun | A safety gun, giving extra user protection for flash testing. Compatible with the EasyPAT and MicroPAT. 4mm socket |
110/240V Adaptor | 110V 16A Plug (BS4343) to 240V 13A free socket (BS1363) |
Sockets | |
Mains | 240V 13A to Bs1363. 110V 16A to BS4343 |
Flash | 4mm high voltage safety socket |
Lamps | |
Flash | Neon lamp which illuminates when flash test is active |
Over Temperature | Red LED which illuminates when the temperature limit of the instrument is exceeded |
Fuses | |
Front Panel | 16A (FF), 1.25", HBC, ceramic |
Plug | 13A, 1", HBC, ceramic |
Internal | 3.15A (F), 5 x 20mm, HBC, ceramic |
Display | |
LCD | 0.7" high, 2 ½ digit LCD with annuciators to indicate supply voltage of the mains and units of measurement in use |
Reviews
SKU | EPAT2100BUNDLE1 |
---|---|
Manufacturer Part Code | EPAT2100BUNDLE1 |