Drummond MTL20PD-S Test Lamp and Proving Device

All Martindale Products
  • Four voltage levels
  • Dual impedance
  • PD440S Proving device
  • MTL20 Test lamp
SKU
DRUMTL20PD-S
MPN
DRUMTL20/PD-S

Read More

View All Proving Units

This kit includes the MTL20 voltage indicator and the PD440S proving unit. Provided in a heavy-denier nylon carry case with a clear window for accessing test points without removal.

The Drummond MTL20 complies with GS38 and CAT IV 600V standards and includes straight and right-angled probes. The 50, 120, 230, and 400V voltage levels are displayed on bright red LED indicators. The MTL20 discharges capacitive or phantom voltages via large red buttons on each probe, confirmed by extinguishing all LEDs.

The PD440S provides 440V output, suitable for low and high-impedance testers. It has a long battery life, a low battery indicator, and colour coding.

Key Features

  • Four voltage levels
  • Dual impedance
  • 360-degree viewing
  • Supplied with GS38 and CAT IV 600v Safety rating
  • Straight and Right-Angled Probes
  • Low Impedance function
  • Four illuminated bands for 360° AC/DC voltage indication
  • High intensity long life LEDs
  • Double insulated cable with contrasting core to identify damage
  • Twin test buttons eliminate phantom voltages (MTL20)
  • Ideal for proving low and high impedance voltage indicators, test lamps and two pole testers (PD440S)
  • Tough low profile design (PD440S)
  • Long battery life with low battery indicator and auto power off (PD440S)

What's Included?

  • PD440S Proving device
  • MTL20 Test lamp
  • 2 straight prods
  • 1 L-shaped prod
  • Instruction manual
  • TC71 Soft carry case

Videos

Drummond MTL10 and MTL20 test lamps for safe isolation

Drummond MTL10 and MTL20 test lamps for safe isolation

£190.00
£228.00 inc vat
In Stock: Available Next Working Day*
Important Notice
This item is made-to-order exclusively for you once your order is placed. As a result, it is not eligible for cancellation or return under our standard policy. Your statutory rights remain unaffected.
190 Reward Points 60 Days Return

Ask An Expert
Price Match
Technical Information
Specification
MTL20
ELECTRICAL
Maximum Working Voltage 500V AC rms, 750V DC
Nominal Voltage Threshold Indications 50, 120, 230, 400V AC/DC rms
Nominal Voltage Threshold Tolerance Conforms to BS EN 61243-3
Range detection Automatic
Response Time <0.1s
Frequency Range DC, 40-65Hz
Test Current (in) <3.5mA at 500V AC rms, 750V DC
Test Current (Switches Operated) approx. 28mA at 230V AC rms, DC
approx. 60mA at 500V AC rms, DC
Duty Ratio 30s ON (operated) / 240s OFF (recovery)
ENVIRONMENTAL
Temperature & Humidity (Operating & Storage) -10°C to 55°C, ≤ 85% R.H.
Altitude up to 2000m
Pollution Degree 2
IP Rating IP64
GENERAL
Power from the circuit under test
Dimensions 213(L) x 112(W) x 72(D) mm
Weight 350g approx.
SAFETY
BS EN 61243-3 (2010) Conforms
Conforms to BS EN 61010-1 CAT IV 600V Class II, double insulation
Probe tips comply with GS38 Yes
EMC
Conforms to BS EN 61326-1 Yes
Recommended proving unit 440V - PD440S
PD440S
Output Voltage 440V nominal
Output Frequency: 50Hz nominal
Operating Temperature -10°C to 40°C at max. 70% R.H.
Altitude up to 2000m
Pollution Degree 2
Internal Batteries 6 x 1.5V, AA alkaline batteries (IEC LR6, NEDA 15A)
Dimensions 150 x 80 x 35mm
Weight Packed 350g approx. with batteries
Includes 6 x 1.5V AA alkaline batteries, instructions
Document Downloads
Drummond MTL20PD-S Test Lamp and Proving Device Datasheet Datasheet
Additional Information
SKU
DRUMTL20PD-S
Manufacturer Part Code
DRUMTL20/PD-S

Customer Reviews

 
Drummond MTL20PD-S Test Lamp and Proving Device
£190.00
£228.00 inc vat
£190.00
£228.00 inc vat