The DiLog DL9120 Multifunction Tester is an 18th Edition-compliant multifunction installation tester with an LCD featuring a colour-changing RGB screen for indicating PASS/FAIL results. It meets BS EN 61557 requirements and is fully protected against damage when accidentally connected across phases. In addition to this, the DiLog DL9120 Multifunction Tester offers the following measurement features:
The DiLog DL9120 Multifunction Tester is a comprehensive, cost-effective MFT designed for safety and performance.
Model | DL9120 | DL9130EV |
---|---|---|
Continuity Test | Yes | |
15 mA/200mA Selectable Current | No | Yes |
R Max (Max R1+R2 recording) | No | Yes |
Insulation Test | 250V, 500V, 1000V | 250V, 500V, 1000V |
Loop Test (3-wire no-trip) | Yes | |
2-Wire Loop Test | Yes | |
Auto Start Loop & Continuity | Yes | |
Auto Start PFC/PSC (L-PE/L-N) | Yes | |
Z Max | No | Yes |
PFC and PSC Fault Current(L-PE/L-N) | Yes | |
Phase-Phase Line Test (L-L) | Yes | |
RCD Test (AC, A, S-type) | Yes | |
Auto RCD Test | Yes | |
RCD Ramp Test | Yes | |
6 mA RDC-CC (EVSE) | No | Yes |
Auto EV RCD Test Sequence | No | Yes |
RCD Test Type B | Yes | |
Phase Rotation | Yes | |
Intelligent Full Range Protection | Yes | |
Colour RGB display | Yes | |
Remote Test Probe Include | No | Yes |
DL9120 | |
---|---|
Voltage | |
Display Range | 0V to 480V |
Measuring Range | 0V to 480V |
Resolution | 1V |
Voltage Accuracy | +/- 5% +/- 2digits |
Frequency Range | 45.0Hz - 65.0HzV |
Frequency Accuracy | +/- 1.0Hz |
Continuity | |
Display Range (200mA) | 0.01Ω to 2000Ω |
Measuring Range (200mA) | 0.10Ω to 2000Ω |
Accuracy | +/- 2% +/- 5 digit |
Resolution | 0.01Ω to 19.99Ω 20.0Ω to 199.9Ω 200Ω to 2000Ω |
Test Voltage | >4Vdc >25Vdc Open Circuit |
Test Current | >200mA |
Compliance | IEC61557-4 and IEC61557-10 |
Insulation | |
Display Range | 0.01MΩ to 200MΩ |
Measuring Range | 0.05MΩ to 200MΩ |
Accuracy | +/-5% +/-5 digits |
Resolution | 0.01MΩ to 1.99MΩ 2.0MΩ to 19.9MΩ 20MΩ to 200MΩ |
Alarm Warning | <1MΩ Screen & Audible |
Test Voltage | 250/500/1000V |
Test Voltage Specification | -0% +20% (open circuit) |
Test Current | 1mA into UN (1000Ω/V) |
Compliance | IEC61557-2 and IEC61557-10 |
No Trip Loop Impedance | |
Supply Voltage | 195-253V, 45Hz - 65Hz |
Display Range | 0.01Ω to 2000Ω |
Measuring Range | 1.00 to 1999Ω (non-trip) |
Accuracy | +/-5% +/-12 digits (to 20Ω) +/-5% +/-5 digits (to 2000Ω) |
Resolution | 0.01Ω to 9.99Ω 10.0Ω to 99.9Ω 100Ω to 2000Ω |
Test Current | <15mA RMS |
High Current Loop Impedance | |
Supply Voltage | 195-253V, 45Hz - 65Hz |
Display Range | 0.01Ω to 2000Ω |
Measuring Range | 0.10Ω to 1999Ω (high current) |
Accuracy | +/-5% +/-12 digits (to 20Ω) +/-5% +/-5 digits (to 2000Ω) |
Resolution | 0.01Ω to 9.99Ω 10.0Ω to 99.9Ω 100Ω to 2000Ω |
Test Current | 3A RMS |
Loop Test PFC Measurement | |
Display Range | 0.1A to 26.0kA |
Accuracy | +/-5% +/-5 digits |
Resolution | 0.1A to 999.9A 1.0kA to 26.0kA |
High Current Line Impedance | |
Display Range | 0.01Ω to 2000Ω |
Measuring Range | 0.10Ω to 2000Ω |
Accuracy | +/-5% +/-5 digits |
Resolution | 0.01Ω to 9.99Ω 10.0Ω to 99.9Ω 100Ω to 2000Ω |
Supply Voltages | 195V - 253V 328V - 480V |
Test Current | 3A RMS Peak |
Line Test PSC Measurement | |
Range | 0.1A to 26.0kA |
Accuracy | +/-5% +/-5 digits |
Resolution | 0.1A to 999.9A 1.0kA to 26.0kA |
RCD Trip Time Test | |
Supply Voltages | 195-253V, 45Hz - 65Hz |
RCD Types | AC, A, B & Selective |
Nominal Test Current | 10mA/30mA/100mA ( ½ , 1, 5 I∆n) 300mA/500mA ( ½, 1 I∆n) Variable Mode |
Variable RCD Test | 1mA - 500mA |
Test Current Accuracy | -0% +10% at I∆n and 5I∆n -0% +10% at ½ I∆n |
Trip Time Ranges | 0 to 2000ms ½ I∆n 0ms - 300ms I∆n general 0ms - 500ms I∆n selective 0 to 40ms 5 I∆n |
Trip Time Accuracy | +/- 5% +/- 2 digits |
Nominal Test Current | 10mA/30mA/100mA ( ½, 1, 5 I∆n) 300mA/500mA ( ½, 1 I∆n) |
Compliance | IEC61557-6 and IEC61557-10 |
RCD (Ramp) Trip Current Test | |
Range | 0.5 I∆n to 1.1 I∆n |
Accuracy | +/-5% of the expected current |
Step Size | 0.1*∆n |
Step Duration | 300ms |
Compliance | IEC61557-6 and IEC61557-10 |