The DiLog DL9062 Earth Resistance Tester has a measurement range of 20Ω to 2000Ω. This product is intended for use in measuring the resistance in earthing systems, as well as for measuring ground, low level regular and liquid resistance.
This product is also capable of performing continuity tests, featuring a measurement range for this function of 0.1kΩ to 200kΩ. A further feature of this product is that it can be used take earth potential difference measurements, of up to 200V, as well as voltage measurements for both alternating and direct current (up to 750VAC and 1000V DC).
This product has a sampling rate of 2.2 times per second and is equipped with a digital, backlit display and zero auto adjustment ensuring both efficiency and ease-of-use. Other features present on the DiLog Dl9062 Earth Resistance Tester are over-range and low battery indicators, auto power off, as well as a test hold function helping to further increase the user’s efficiency and the product's longevity of use.
This product is sturdy and its double moulded case, three additional cables, and two rods means that this product is suitable for use in rugged conditions making it ideal for testing earth resistance in a variety of environments, including electrical traction systems, power and/or telecommunications industries.
Technical Specifications |
Range |
Accuracy |
Measurement Specifications | ||
Earth Resistance |
20Ω (0.01Ω Resolution) 200Ω (0.1Ω Resolution) 2000Ω (1Ω Resolution) |
+/- 2% Rdg +/- 10 digits +/-2% Rdg +/- 3 digits +/- 2% Rdg +/- 3 digits |
Earth Voltage | 200V (0.1V Resolution) | +/- 3% + 3 digits |
Voltage AC | 750V (1V Resolution) | +/- 1.2% +/- 10 digits |
Voltage DC | 1000V (1V Resolution) | +/- 0.8% +/- 3 digits |
Resistance | 200kΩ | +/- 1.0% +/- 3 digits |
Practical Specifications | ||
Display | 3½ digit LCD 1999 digits | |
Over Voltage Category | CAT III 1000 V | |
Power Supply | 6 x 1.5 V, IEC LR | |
Dimensions | 200 x 92 x 50 mm | |
Weight | 582 g |